Authorized ABB Distributor (Installation Products)
ABB - Installation Products 15PCJ1H2250 - 15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.

ABB Installation Products 15PCJ1H2250 15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…

UPC: 783786266609


Documents & Media
BrochureInstallation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 15PCJ1H2250 is a 15kV power cable joint designed for reliable electrical connections in industrial applications. Manufactured by ABB - Installation Products, this Style 1 joint features a single-piece housing for straightforward installation and robust performance. It is engineered to accommodate cable insulation diameters ranging from 0.850 inches to 1.050 inches, ensuring compatibility with a variety of medium-voltage power cables. The joint is suitable for copper conductors, supporting both stranded 2/0 AWG and solid 3/0 AWG conductor sizes. This specification ensures it can handle the current requirements for many industrial power distribution systems. The UNSPSC code for this product is 39121452. The single-piece housing design simplifies the termination process, reducing installation time and the potential for errors. This product is a critical component for maintaining the integrity and safety of medium-voltage power networks, providing a secure and durable connection point for power cables. Its construction is intended to offer long-term reliability in demanding electrical environments. The precise insulation diameter range and conductor size compatibility make it a versatile choice for electricians and engineers working with medium-voltage infrastructure.
  • 15kV rated power cable joint
  • Style 1 with single-piece housing
  • Accommodates 0.850" - 1.050" insulation diameter
  • For copper conductors: 2/0 AWG stranded / 3/0 AWG solid
  • ABB - Installation Products manufacturer

Specifications

Application
For Direct Burial, Vault, Submersible and Other Severe Service Applications
Color
Black
Conductor Range
2/0 STR AWG , 3/0 SOL AWG
Connection
Compression
Insulation
Yes
Material
Copper
Material
EPDM Rubber
Number Of Conductors
2
Series
Power Cable Joint Style 1
Size
14-3/8 inch long
Size
0.850 inch to 1.050 inch
Special Features
Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable
Standard
IEEE Standard 404
Type
Power Cable Joint
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.

15PCJ1F2250

15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.

15PCJ2M1380

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.

15PCJ2L1330

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.

15PCJ1H1250-1240

15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 2/0 /Solid 3/0. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.

15PCJ2L1380

15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 750.
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Conductor. Conductor Size AWG Solid 500.

25PCJ1LM1310

25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Conductor. Conductor Size AWG Solid 500.
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.

25PCJ1H1260-1240

25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 3/0 /Solid 4/0. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch.

35PCJ1K

35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch.

Frequently Asked Questions

What is the insulation diameter range for this ABB cable joint?

The ABB 15PCJ1H2250 power cable joint is designed to accommodate cable insulation diameters ranging from 0.850 inches to 1.050 inches.

What conductor sizes does the 15PCJ1H2250 support?

This ABB cable joint supports copper conductors of 2/0 AWG stranded and 3/0 AWG solid sizes.

What is the voltage rating of the 15PCJ1H2250?

The 15PCJ1H2250 is a 15kV power cable joint, indicating its suitability for medium-voltage applications.

What type of housing does this ABB cable joint feature?

The ABB 15PCJ1H2250 features a single-piece housing for its Style 1 power cable joint.

How to Install a Single Core Joint (15PCJ1H2250)

This guide provides step-by-step instructions for the permanent installation of a fully screened, submersible single core joint on extruded solid dielectric cables. It covers essential cable preparation, conductor splice installation, and joint housing assembly.

Estimated time: 1h 30m

Tools needed:

Wire strippers, Utility knife, Crimping tool, Wire brush, Cleaning cloth, Measuring tape or ruler, Heat gun, Sandpaper, Soldering iron (optional, if not using constant force springs)

Supplies needed:

Joint Housing, PVC tape, Conductor splice (copper or aluminum, compatible with cable), Lubricant (supplied with joint), Cleaning solvent, Flat copper braid, Constant force springs (optional, for screen restoration), Mastic tape, Heat shrink

  1. De-energize Apparatus and Ensure Safety

    DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Failure to follow these instructions will result in damage to the product and serious or fatal injury.

  2. Inspect Parts and Prepare Workspace

    Inspect all parts for damage, rating, and compatibility with mating parts. Ensure the contents of the package are complete and undamaged. Have all required tools at hand and maintain cleanliness throughout the procedure.

  3. Train Cables and Remove Jacket

    Train the cables into their final position and square cut, leaving approximately 5mm between cables. Store the heat shrink on either cable. Remove the jackets of both cables to the dimensions specified in the provided tables (e.g., dimension 'A').

  4. Remove Metallic Tape Screen

    Carefully remove the cable metallic tape screen for the distance shown in the provided tables (e.g., dimension 'B'). Secure the ends with PVC tape, ensuring the PVC tape stays on the copper tape and does not overlap onto the non-metallic screen.

  5. Remove Non-Metallic Screen

    WARNING: DO NOT NICK, CUT OR DAMAGE THE INSULATION SURFACE OR CONDUCTOR STRANDS. Carefully remove the cable non-metallic screen from both cables to the point specified in the provided tables (e.g., dimension 'D').

  6. Bevel Cable 1 Edge and Cut Insulation

    Bevel the edge of Cable 1. Cut the insulation to the conductor to dimension 'E' (indicated in the provided tables) from the end of both cables. DO NOT remove the insulation at this stage.

  7. Install PVC Tape Marker on Cable 2

    Install a PVC tape marker on Cable 2 to dimension 'B' (as specified in the tables) to accurately locate the splice later.

  8. Apply PVC Tape over Metallic Screen on Cable 1

    Beginning at the jacket and proceeding 10mm beyond the end of the metallic screen, apply one layer (half lapped) of PVC tape over the metallic screen on Cable 1. WARNING: The forward edge and any other sharp edges of the metallic screen must be covered with PVC tape to prevent damage to the joint housing when storing it on the PVC taped portion of the cable.

  9. Install PVC Tape Marker on Cable 1

    Install a different color PVC tape marker on Cable 1 to dimension 'B' (as specified in the tables) to locate the splice later.

  10. Lubricate Splice Housing Entrances

    Lubricate both cable entrances of the splice housing using the supplied lubricant.

  11. Clean and Lubricate Cable 1 Surfaces

    Clean and lubricate the insulation, cable non-metallic screen, and PVC taped portion of the cable metallic tape screen on Cable 1.

  12. Store Joint Housing onto Cable 1

    Store the joint housing onto Cable 1, sliding it up to the jacket. DO NOT STORE THE SPLICE HOUSING ON THE EXPOSED METALLIC TAPE SHIELD.

  13. Remove Cable Insulation

    Remove the cable insulation from both cables to dimension 'E' (as specified in the tables). DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR.

  14. Wire Brush Exposed Conductors

    Wire brush the exposed conductors of both cables thoroughly to ensure good electrical contact.

  15. Insert Conductors into Splice

    Immediately insert the conductors from both cables into the conductor splice. Ensure that both conductors are fully seated in the splice. DO NOT CRIMP at this stage.

  16. Verify Insulation Distance (Before Crimping)

    Check the distance between the insulations. If it exceeds the 'Check Dim (Before)' value in the provided table (e.g., dimension 'F'), DO NOT PROCEED. Review the instructions and redo the assembly without exceeding this distance.

  17. Crimp Conductor Splice

    Crimp the conductor splice according to the crimp chart provided with the specific connector. Ensure a secure and proper crimp.

  18. Remove Protrusions and Filings

    Remove any sharp protrusions or burrs from the crimped splice. Metal chips or filings must be removed from the splice joint assembly area prior to sliding the joint housing.

  19. Wipe Excess Inhibitor and Verify Insulation Distance (After Crimping)

    Wipe off all excess inhibitor from the splice. Check the distance between the cable insulations again. If it exceeds the 'Check Dim (After)' value in the provided table, DO NOT PROCEED. Review the instructions and redo the assembly without exceeding this distance.

  20. Clean Core Surfaces

    WARNING: REMOVE ALL CONTAMINANTS FROM THE SURFACE OF THE INSULATION. Clean the conductor, connector, and Cable 2 insulation surfaces with cleaning solvent and a clean cloth. Always wipe towards the screen end.

  21. Lubricate Insulation Surfaces

    Lubricate the cable insulation surfaces using the lubricant supplied. Always wipe toward the screen end to provide a build-up or ramp of lubricant at the edge of the non-metallic screen.

  22. Slide Joint Housing into Final Position

    Slide the joint housing over the crimp connector into its final position. Measure the distance between the joint housing and the PVC tape marker on each side. The distance 'X' should be equal on both sides of the joint housing.

  23. Remove PVC Tape

    Remove the PVC tape applied in Step 8 to expose 25mm of the copper tape shield on each side of the joint housing.

  24. Wrap Flat Copper Braid

    Wrap flat copper braid around each end of the joint housing, continuing the ends over the metallic tape screen for 20mm on each side.

  25. Attach Copper Braid Ends

    Attach each end of the copper braid to the metallic tape screen by soldering or by using a constant force spring.

  26. Sand Cable Jackets

    Lightly sand the outer surface of the jacket of both cables for a distance of 130mm from the joint housing.

  27. Heat Sanded Areas

    Heat both sanded areas for approximately 15 seconds using a heat gun. DO NOT BURN THE CABLES.

  28. Wrap Mastic Tape

    Wrap two layers of mastic tape at the edge of the jacket on both cables, overlapping onto the joint housing.

  29. Position and Shrink Heat Shrink

    Position the heat shrink (previously stored on Cable 1) over the center of the assembly. Begin shrinking the heat shrink at the center and work towards the ends, ensuring a tight and uniform seal.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.