ABB Installation Products R2T15M2-N0280 Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38…
UPC: 783786669042
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15KV outdoor application termination
- Accommodates cable insulation diameter 0.84 - 1.38 inches
- Compatible with Tape Shield, Wire Shield, and UniShield cable types
- Includes aluminum 2-hole spade connector for #2-1250 kcmil conductors
- Supports stranded/compressed 250 kcmil, compact, or solid conductors
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 250 to 300 kcmil |
Connection Type | Aluminum 2-Hole Spade #2-1250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84 inch - 1.38 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15M1H0280-B2
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 280 -Stranded or Compressed 250 Compact or Solid 300. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.
R2T15M2-N0310
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 400 /Compact or Solid 500
R2T15M2-N0300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
R2T15M2-N0270
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.84 - 1.38 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 4/0 /Compact or Solid 250
R2T15M1T0270
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Universal Aluminum Barrel for AL or CU Condutor with Copper Wire Lead #2-4/0, Conductor Code - 270 -Stranded or Compressed 4/0 Compact or Solid 250.
R2T15M1N0260
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 260 -Stranded or Compressed 3/0 Compact or Solid 4/0.
R2T15M1H0240
Ranger2 Termination, Outdoor, 15kV, Tape Shield/Wire Shield/Unishield Cable Type, .64-1.12 inch Cable Insulation, Aluminum 1-Hole Spade #2-500 kcmil Connector Type, 1/0 Stranded/Compressed or 2/0 Compact/Solid Conductor Size.
R2T15M1-T1270-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12 inches for Cable Type - Tape Shield/Wire Shield/ UniShield. includes Aluminum Barrel For Aluminum Conductor only with copper wire lead #2-4/0, Stranded or Compressed 4/0 /Compact or Solid 250. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)Frequently Asked Questions
What cable insulation diameters does the ABB Ranger2 termination support?
The ABB Ranger2 termination supports cable insulation diameters ranging from 0.84 to 1.38 inches.
What cable types are compatible with this ABB termination?
This ABB termination is compatible with Tape Shield, Wire Shield, and UniShield cable types.
What conductor sizes can the aluminum spade connector accommodate?
The aluminum 2-hole spade connector accommodates conductors from #2 AWG to 1250 kcmil, including stranded or compressed 250 kcmil, compact, or solid types.
Is this ABB termination suitable for indoor use?
The ABB Ranger2 termination is specifically designed for 15KV outdoor applications.
How to Install the R2T15M2-N0280 Shrink Fit Silicone Rubber Termination on Tape Shielded Cables
This guide provides step-by-step instructions for installing the R2T15M2-N0280 15kV Shrink Fit Silicone Rubber Termination on tape shielded cables, covering cable preparation, ground braid installation, lug connection, and termination application.
Estimated time: 1h 30m
Tools needed:
Cable cutter, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, if needed)
Supplies needed:
R2T15M2-N0280 Shrink Fit Silicone Rubber Termination kit, Lubricant, Gray silicone rubber electrical tape, Constant force spring, Preformed ground braid, Sealing mastic, Copper foil tape, Gloves, Terminal lug or connector, Oxide inhibitor, Vinyl tape, Scotch® No. 13 semi-conductive rubber tape (for cloth/paper semi-con shields)
- Prepare Cable
DANGER: All apparatus must be de-energized during installation. Verify the cable size fits within the insulation range specified in the Termination Selection Chart. Train the cable into its final position and cut it to the required length. Prepare the cable according to the dimensions provided in Table 1 for 'Jacket Removal Length' (Dimension A) and allow for terminal lug depth plus aluminum lug growth allowance (1/4" to 3/4" depending on Kcmil). Secure the tape shield edge with a single wrap of the supplied copper foil tape to prevent unrolling.
- Install Ground Braid
Using 50% stretch, carefully wrap one band of mastic around the cable jacket 1/4" (6mm) from the jacket end. Position it carefully as it also serves as a termination marker. Cut the mastic flush without overlapping. Position the preformed ground braid with the short tail over the tape shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket with vinyl tape and press the solder block into the mastic. Apply a second mastic band over the solder block and previously applied mastic, maintaining the 1/4" (6mm) dimension, and cut flush. Wrap two half-lapped layers of vinyl tape around the mastic seal. Wrap the ground braid around the cable tape shield one complete wrap, trim any excess, and secure with the constant force spring. Wrap the spring in the same direction as the ground braid, cinch it after the final winding, and secure with two wraps of vinyl tape. For cloth or paper semi-con insulation shields, overwrap the shield with one half-lapped layer of highly stretched semi-conductive rubber tape.
- Install Lug or Connector
Ensure the termination assembly fits over the selected lug. If it does not, clean the insulation and slide the termination onto the cable before installing the lug; do not remove the core at this time. Position the connector/lug and crimp it according to the manufacturer’s directions. Do not crimp the last 3/8" to 1/2" of the connector. Remove excess oxide inhibitor and all sharp crimp flashings and edges after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent. Do not allow the solvent to touch the semi-con insulation shield. If an abrasive is necessary, use it only on the insulation (not the semi-con shield). Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit's allowance.
- Install Termination
Create a track-resistant moisture seal by wrapping a band of the supplied gray silicone rubber electrical tape around the base of the terminal lug. If the barrel diameter is equal to or greater than the cable primary insulation, do not exceed 2 layers. If smaller, use the tape to build up the band to the insulation diameter. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Continue removing the core without pushing or pulling on the termination assembly. Apply a thin film of silicone lubricant to the skirt and mastic seal area (do not lubricate the skirt tabs). Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1" and extending over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect the ground braid to the system ground. Confirm that the High-K step does not exceed 1.5".
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.