ABB Installation Products R2T28J2-T0240 Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84…
UPC: 783786548231
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Designed for 25/28KV outdoor applications
- Accommodates cable insulation diameters from 0.84 to 1.38 inches
- Suitable for Concentric Neutral and Jacketed Concentric Neutral cables
- Includes Universal Aluminum Barrel for AL or CU conductors
- Supports #2 to 4/0 AWG conductors with copper wire lead
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 1/0 STR AWG , 1/0 COMPR AWG , 2/0 SOL AWG , 2/0 COMPT AWG |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T28J2-N2240
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Includes Copper 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1/0 /Compact or Solid 2/0
R2T28J2-T1230-B2
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .84 inch - 1.38 inch, Connector Type - Aluminum Barrel for AL Condutor only with Copper Wire Lead #2-4/0, Conductor Code - 230 -Stranded or Compressed #1 Compact or Solid 1/0. Cable Mounting Bracket - B2 - Stainless Steel - Size 1.10 inch - 1.50 inch.
R2T28J2H0220-B1
28 kv, Ranger2, Outdoor Cable Termination, Concentric Neutral/Jacketed Concentric Neutral, Insulation Range .84-1.38 inch (21-35mm), Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code 220 - Stranded or Compressed #2, Compact or Solid #1. Stainless Steel Cable Mounting Bracket .80-1.25 inch (20-32mm).
R2T28J4-N0410-B4L
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral/Jacketed Concentric Neutral Cable, Aluminum 2-Hole Spade #2-1250kcmil, Stranded or Compressed 1000 . - Cable Mounting Bracket - Stainless Steel, 1.80 inch - 2.40 inch (45-61mm). L
R2T28J4-N0330-B3
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600, Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch
R2T28J2-T0220
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For Aluminum or Copper Conductor with copper wire lead #2-4/0, Stranded or Compressed #2 /Compact or Solid #1
R2T28J2-N0300
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for 1250 kcmil
R2T28J2-N0300-B3
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed #2 /Compact or Solid #1, Stainless Steel Mounting Bracket 1.45 inch - 1.95 inchFrequently Asked Questions
What cable sizes does the R2T28 termination cover?
The R2T28 termination covers insulation diameters from 0.84 in to 2.10 in, accommodating #2 AWG through 1250 kcmil cables.
What is the compatible power system frequency?
The R2T28 termination is compatible with a power system frequency range of 48 to 62 Hz.
What is the operating ambient temperature range?
The R2T28 termination operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum altitude for R2T28 installation?
The R2T28 termination can be installed at a maximum altitude of 3300 feet (1005 m).
How many sheds does the R2T28 outdoor model have?
The 25/28kV outdoor model of the R2T28 termination features six sheds.
What is the minimum strike distance of the R2T28?
The minimum strike distance for the R2T28 termination is 14.5 inches (368 mm).
What is the creepage distance of the R2T28?
The creepage distance for the R2T28 termination is 22.8 inches (579 mm).
What is the lightning impulse withstand voltage?
The lightning impulse (BIL Dry 110 Withstand) for the R2T28 termination is 150 kV Crest.
What is the Coronal Extinction Voltage for the R2T28?
The Coronal Extinction Voltage for the R2T28 termination is 22 kV (≤ 3pC partial discharge).
What is the maximum design voltage to ground for R2T28?
The maximum design voltage to ground for the R2T28 termination is 16 kV.
How to Install the R2T28J2 Cable Termination
A comprehensive guide for installing the R2T28J2 28kV Ranger 2 Cable Termination on concentric and jacketed concentric neutral cables for indoor/outdoor applications. This procedure should only be performed by competent personnel trained in high voltage electrical equipment safety practices.
Estimated time: 1h 30m
Tools needed:
Measuring tape, Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (optional, grit 120 or finer)
Supplies needed:
R2T28J2 Termination Kit (includes termination, lubricant, tapes, mastic, gloves), Vinyl tape or binding wire, Silicone grease, Connector (if not included in kit)
- Prepare the Cable for Termination
Before starting, ensure all apparatus is de-energized. Verify the cable size fits within the R2T28J2 kit range. Train the cable into its final position and cut to the required length, ensuring sufficient neutral wire length for grounding. Prepare the cable according to the dimensions provided in the instructions, specifically 'A' from Table 1 (10.5 inches for R2T28J2) for the insulation shield cutback, and allow for the barrel depth of the terminal lug plus the specified 'X' dimension for exposed conductor length. Using 50% stretch, wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end. Bend the neutral wires back over the mastic and press them into the mastic, then secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic, using 50% stretch. Finally, wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension from the jacket end.
- Install the Terminal Lug or Connector
If using a lug or connector that will not fit through the termination core, clean the cable insulation and slide the termination body onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug onto the prepared conductor and crimp it according to the manufacturer's directions. Ensure you do not crimp the last 1/4 to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Thoroughly wipe the cable insulation with an approved solvent to ensure it is clean. Be careful not to allow the solvent to touch the semi-con insulation shield. If an abrasive is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation only, avoiding the semi-con insulation shield. Take care not to reduce the cable insulation diameter below the limits specified by the kit.
- Install the Termination Body
Create a track-resistant moisture seal between the termination insulator and the lug/connector by wrapping a band of gray silicone rubber tape (from the kit) around the base of the terminal lug. If the barrel diameter is smaller than the cable primary insulation, build up the tape band to equal the insulation diameter, otherwise, do not exceed two layers. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off. For terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end, ensuring the termination body is butted up to the leading edge of the mastic seal. Do not push or pull the termination assembly during core removal. Apply a thin film of silicone lubricant to the skirt and mastic seal area (do not lubricate skirt tabs). Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber tape, overlapping the termination insulator by approximately 1 inch and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them securely to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.