ABB Installation Products R2T15J1-H0300 15 kv, Ranger2 Terminator, OutDoor, Concentric Neutral/Jacketed Concentric Neutral, .64…
UPC: 783786383627
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15 kV voltage rating with 9.5 kV max design voltage to ground
- Supports conductor sizes: #2 AWG to 500 kcmil (standard/compressed 350 kcmil, compact/solid 400 kcmil)
- Non-tracking silicone housing with superior weathering and memory characteristics
- Four sheds for enhanced creepage and strike distances in outdoor applications
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 350 to 400 kcmil |
Connection Type | 1-Hole Spade |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Mounting Type | Outdoor |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.64-1.12 inch |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T15J1-N0300
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 300 -Stranded or Compressed 350 Compact or Solid 400.
PCT1-3
15kV, Housing Only, Pre-Molded Cable Termination, 2-Hole Spade Lug, For use with Insulation Diameter Range from .830 inch to 1.180 inch.
PCT2-3
25kV, Housing Only, Pre-Molded Cable Termination, 2-Hole Spade Lug, For use with Insulation Diameter Range from .830 inch to 1.180 inch.
69TCT232231PNAN
69kV, Transmission Cable Termination (TCT). Base and Top Module, Housing Size 3, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size 31P, Metallic Screen Kit - Not Required, Armour Kit - Jacketing Tape and Mastic, No Bracket Required.
R2T15J1-N0380
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250 kcmil, Stranded or Compressed 700, Compact or Solid 900.
R2IT15J1-N0380
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 750 Stranded/Compressed or 900 Compact/Solid
69TCT23NNNNNNBN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3 - Bore Diameter 1.975 inch, Type of Connection - None, Connector Type - None, Conductor Size - None, Metallic Screen Kit - None, Armour Kit - Heat Shrink, No Bracket Required
R2T15M4-N2360-B3
15 kv, Cable Terminator Ranger2, Outdoor, Cable Type - Tape Shield/Wire Shield/UniShield, Insulation Range 4 - 1.30 inch to 2.10 inch (33 mm to 53 mm), Connector Type N2 - Copper 2-Hole Spade #2-1250 kcmil, Conductor Code 360 - Compressed 650/Compact 750, Cable Mounting Bracket B3 - Material Stainless Steel - Size - 1.45 inch to 1.95 inch (37mm - 50mm)Frequently Asked Questions
What is the voltage rating of the ABB R2T15J1-H0300?
The ABB R2T15J1-H0300 has a voltage rating of 15 kV.
What types of conductors can this terminator accommodate?
This terminator accommodates aluminum 1-hole spade connectors for conductor sizes #2 to 500 kcmil, including standard/compressed 350 kcmil and compact/solid 400 kcmil.
What is the insulation range for this terminator?
The ABB R2T15J1-H0300 supports an insulation range from 0.64 inches to 1.12 inches.
Is this terminator suitable for outdoor use?
Yes, the ABB R2T15J1-H0300 is specifically designed for outdoor applications.
What type of neutral is featured on this terminator?
This terminator features a Concentric Neutral/Jacketed Concentric Neutral configuration.
How to Install 15kV & 28kV Ranger 2 Cable Termination (R2T15/28J)
This guide provides step-by-step instructions for installing the Ranger 2 Cable Termination for 15kV and 28kV indoor/outdoor applications on concentric and jacketed concentric neutral cables, including cable preparation, lug installation, and termination sealing.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (optional, grit 120 or finer), Vinyl tape or binding wire, Gloves
Supplies needed:
Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Connector (if not included in kit), Cable Support Bracket (optional), Vinyl tape, Binding wire
- Observe Safety Precautions and Prepare for Installation
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices. Failure to follow instructions will result in damage and serious injury. Before starting, check package contents for completeness and damage, verify all components fit the cable and mating products, read the entire instructions, and have all required tools at hand while maintaining cleanliness.
- Prepare Cable Dimensions and Initial Mastic Application
Verify the cable size fits within the kit's range. Train the cable into position and cut it to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable using the specified dimensions, accounting for the depth of the terminal lug and additional exposed conductor distance for aluminum lugs/connectors as per Table 1 and the provided figures. Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end, cutting it flush without overlap.
- Secure Neutral Wires and Final Mastic/Tape Seal
Bend the neutral wires back over the mastic and secure them to the cable jacket 4-6 inches (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and the first mastic band with 50% stretch, cutting it flush. Finally, wrap two half-lapped layers of vinyl tape around the mastic seal, maintaining the 1/4 inch (6mm) dimension.
- Install the Lug or Connector
If using lugs other than Elastimold copper or aluminum lugs that will not fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug and crimp it according to its directions. Do not crimp the last 1/4 inch to 3/8 inch of the connector. After crimping, remove any excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring the solvent does not touch the semi-con insulation shield. If an abrasive must be used, apply it only to the insulation, not the semi-con insulation shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit's allowed range.
- Apply Initial Moisture Seal and Silicone Grease
IMPORTANT: Create a track-resistant moisture seal between the termination insulator and the lug/connector using the gray silicone rubber tape from the kit. Wrap a band of silicone tape around the base of the terminal lug; if the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If the barrel diameter is smaller, use the tape strip to form the tape band equal to the insulation diameter. Cover the edge of the semi-con insulation shield with a liberal coating of silicone grease to fill the step at the semi-con cut-off.
- Install Termination Body and Remove Core
For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning the terminator with the forward edge of the mastic seal. Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Do not push or pull on the termination assembly while removing the core material.
- Complete Sealing and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. With the termination installed, complete the lug area moisture seal using the remaining gray silicone rubber tape. Overlap the termination insulator by approximately 1 inch and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Twist the concentric neutral wires together and connect them to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.