ABB Installation Products R2IT15M1N0220 Ranger2 Termination for 15KV indoor application, cable insulation diameter .64 - 1.12…
UPC: 783786055296
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15KV indoor application rating
- Accommodates cable insulation diameter from .64 to 1.12 inches
- Compatible with Tape Shield, Wire Shield, and Unshielded cable types
- Supports conductor code 220 (stranded/compressed #2, compact/solid #1)
- Includes aluminum 2-hole spade connector for 1250 kcmil conductors
Specifications
Application | Cable Termination, Indoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | #2 STR AWG , #2 COMPR AWG , #1 SOL AWG , #1 COMPT AWG |
Earthing | Products Includes Their Own Grounding System |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Indoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT10220-5
15kV, Single Piece Terminator (Class 1), One-Hole Spade Lug. Power Cable Termination, Conductor Size - #2 Stranded/Compressed or #1 Compact/Solid, Use for Insulation Diameter Range from .640 to 1.070 inches.
R2T35M4N0410
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000
R2T35M4N0350
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 650 /Compact or Solid 750
R2T35M4N0330
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600
R2T15J2-N0330
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64-1.12 for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade
R2T15J2-N0330-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 500 /Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
R2T28J2-T1240
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum Barrel For Aluminum Conductor only with copper wire lead #2-4/0, Stranded or Compressed 1/0 /Compact or Solid 2/0
R2T15J2-T0270
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire leadFrequently Asked Questions
Is this termination suitable for outdoor use?
No, the ABB Ranger2 termination is specifically designed for 15KV indoor applications.
What is the maximum cable insulation diameter for this termination?
The ABB Ranger2 termination supports cable insulation diameters up to 1.12 inches.
What cable shield types are compatible with this termination?
This termination is compatible with Tape Shield, Wire Shield, and Unshielded cable types.
What conductor sizes does conductor code 220 support?
Conductor code 220 supports stranded or compressed #2 conductors, and compact or solid #1 conductors.
What size spade connector is included with this termination?
This termination includes an aluminum 2-hole spade connector for 1250 kcmil conductors.
How to Install the 15kV Ranger 2 Shrink-Fit Silicone Rubber Termination
This guide provides detailed instructions for installing the 15kV Ranger 2 Shrink-Fit Silicone Rubber Termination (R2IT15M) for indoor applications on tape, wire, or UniShield cables. It covers cable preparation, ground braid installation, lug connection, cleaning, and final termination placement.
Estimated time: 1h 30m
Tools needed:
Crimping tool, Wire strippers, Measuring tape, Soldering iron, Utility knife, Gloves
Supplies needed:
15kV Ranger 2 Shrink-Fit Silicone Rubber Termination Kit (R2IT15M), Vinyl electrical tape, Silicone lubricant (grease), Solvent saturated pads, Aluminum oxide abrasive (120 grit or finer, optional), Terminal lug or connector
- De-energize and Prepare Work Area
DANGER: Ensure all apparatus in the work area are de-energized before beginning installation. Do not touch or move energized products. Failure to follow this instruction can result in serious or fatal injury. This product must be installed only by competent personnel trained in high voltage safety practices. Inspect all kit contents for completeness and damage. Verify all components are compatible with the cable and mating products. Read the entire instructions before starting and have all required tools at hand, maintaining cleanliness throughout the procedure.
- Prepare the Cable for Termination
Verify the cable size fits within the insulation range specified in the Termination Selection Chart. Train the cable into its final position and cut it to the required length, allowing for the terminal lug depth and any aluminum lug growth allowance (1/4" to 3/4" depending on conductor size). Carefully remove the cable jacket, semi-conductive layer, and insulation according to the dimensions provided in the instructions for your specific cable type (Tape Shield, Wire Shield, or UniShield). For tape-shielded cables, secure the tape shield edge with a single wrap of the supplied copper foil tape to prevent unrolling. For wire-shielded cables, bend 1 inch (25mm) of exposed shield wires back to the jacket edge. For UniShield cables, follow specific instructions for pulling shield wires through the semi-conductive jacket, bending them back, and removing the semi-conductive jacket layers.
- Install the Ground Braid
Wrap one band of vinyl tape around the cable jacket 1/4 inch (6mm) from the jacket end; this serves as a marker. Position the preformed ground braid with its short tail over the cable shield (tape, wire, or UniShield wires) and the solder block centered over the vinyl tape marker. Secure the ground braid to the cable jacket using vinyl tape. Apply a second vinyl tape band directly over the original tape marker and ground braid solder block, maintaining the 1/4 inch (6mm) dimension. Wrap the ground braid around the cable shield for one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Wrap the spring in the same direction as the ground braid and cinch it after the final winding. Secure the spring with two wraps of vinyl tape.
- Install the Terminal Lug or Connector
Before proceeding, check that the termination body assembly will fit over the selected lug. If it does not, clean the cable insulation and slide the termination body onto the cable before installing the lug (do not remove the core at this time). Position the connector or lug onto the prepared conductor and crimp it according to the manufacturer's directions. Ensure you do not crimp the last 3/8 inch to 1/2 inch of the connector. After crimping, remove any excess oxide inhibitor and all sharp crimp flashings or edges.
- Clean Cable Insulation and Lug
Wipe the cable insulation thoroughly with solvent-saturated pads. Exercise caution to prevent the solvent from touching the semi-conductive insulation shield. If abrasive cleaning is necessary, use it only on the insulation and not on the semi-conductive insulation shield. Use only aluminum oxide abrasive, grit 120 or finer, and be careful not to reduce the cable insulation diameter below the kit's specified allowance.
- Install the Silicone Rubber Termination Body
Apply a liberal coating of silicone grease (lubricant) to the edge of the semi-conductive insulation shield (or semi-conductive jacket for UniShield cables) to fill the step at the semi-con cut-off. Slide the termination body onto the cable. Align the termination's edge (or skirt) with the forward edge of the vinyl tape marker previously applied. Carefully begin to remove the core by pulling counter-clockwise. Recheck the termination's position and continue to remove the core, ensuring not to push or pull on the termination assembly during this process. Finally, connect the installed ground braid to the system ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.