ABB Installation Products R2T35M4N0410 Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38…
UPC: 783786055555
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Non-tracking silicone housing with superior weathering resistance
- Shrink-fit housing for simplified installation and field-removable center core
- Supports tape shield, wire shield, and unshielded cables (.84-1.38" insulation)
- Aluminum 2-hole spade connector for #2-1250 kcmil stranded/compressed conductors
- Eight sheds for optimal creepage and strike distances (16.8" minimum strike distance)
Specifications
Application | Cable Termination, Outdoor Application, 35kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 1000 kcmil |
Connection Type | 2-Hole Spade |
Current Rating | 1250 kcmil |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.84-1.38 inches |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T35J4-N0410
Ranger2 Termination for 35KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neutral and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000
R2T35M4N0350
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 650 /Compact or Solid 750
R2T35M4N0330
Ranger2 Termination for 35KV outdoor application, cable insulation diameter .84 - 1.38 inches for Cable Type - Tape Shield, Wire Shield, and Unshielded Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 500 /Compact or Solid 600
R2T15J2-N0330
Ranger2 Termination for 15KV indoor application, cable insulation diameter .64-1.12 for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade
R2T15J2-N0330-B2
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84-1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed 500 /Compact or Solid 600. Plated Mild Steel Mounting Bracket 1.10 inch - 1.50 inch (28-38mm)
R2T28J2-T1240
Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter .84 - 1.38 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum Barrel For Aluminum Conductor only with copper wire lead #2-4/0, Stranded or Compressed 1/0 /Compact or Solid 2/0
R2T15J2-T0270
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .84 - 1.38 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Universal Aluminum Barrel For AL or CU Conductor w/copper wire lead
R2T15J4-N0380
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2 to 1250 kcmil. 750 kcmil Stranded or 900 kcmil SolidFrequently Asked Questions
What is the voltage rating of the ABB Ranger2 termination?
The ABB Ranger2 termination has a voltage rating of 35 kV, suitable for high-voltage outdoor applications.
What cable insulation diameters does this termination support?
This termination supports cable insulation diameters ranging from 0.84 to 1.38 inches.
What types of cables can be terminated with this product?
This termination is designed for tape shield, wire shield, and unshielded cable types.
What is the size range for the included aluminum spade connector?
The aluminum 2-hole spade connector is suitable for #2 to 1250 kcmil stranded or compressed conductors.
What is the manufacturer of the Ranger2 termination?
The manufacturer of the Ranger2 termination is ABB - Installation Products.
How to Install the R2T35M 35kV Ranger 2 Shrink-Fit Silicone Rubber Termination
This guide provides step-by-step instructions for installing the 35kV Ranger 2 Shrink-fit Silicone Rubber Termination specifically for tape shield cables in indoor/outdoor applications. Ensure all apparatus is de-energized and follow high voltage safety practices throughout the installation to prevent serious injury or product damage.
Tools needed:
Wire strippers, Measuring tape or ruler, Crimping tool, Soldering iron, Solvent saturated pads, Aluminum oxide abrasive (120 grit or finer, if needed), Scissors or utility knife
Supplies needed:
R2T35M Termination Kit (includes silicone rubber termination halves, lubricant, gray silicone rubber electrical tape, constant force spring, preformed ground braid, sealing mastic, copper foil tape, gloves), Vinyl tape, Terminal lug or connector (compatible with cable), Approved solvent, Semi-conductive rubber tape (e.g., Scotch No. 13, if cable has cloth or paper semi-con shield)
- Prepare the Cable
De-energize all apparatus before beginning. Verify the cable size fits within the termination's insulation range. Train the cable into position and cut it to the required length. Prepare the cable by removing the jacket, semi-conductive layer, and insulation according to the specified dimensions, allowing for terminal lug depth and aluminum lug growth. Secure the edge of the tape shield with a single wrap of the supplied copper foil tape to prevent unrolling.
- Install the Ground Braid
Wrap one band of sealing mastic around the cable jacket 1/4 inch (6mm) from the jacket end, stretching it 50%. Position the preformed ground braid with the short tail over the tape shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket with vinyl tape and press the solder block into the mastic. Apply a second mastic band over the solder block and the first mastic, then wrap two half-lapped layers of vinyl tape over the mastic seal. Wrap the ground braid around the cable tape shield once, trim any excess, and secure it with the constant force spring, wrapping the spring in the same direction as the braid. Cinch the spring after the final winding and secure it with two wraps of vinyl tape. If using cloth or paper semi-conductive insulation shield, overwrap it with one half-lapped layer of highly stretched semi-conductive rubber tape.
- Install the Lug or Connector
Check that the termination assembly will fit over the selected lug. If the lug will not fit through the termination core, clean the cable insulation and slide the termination onto the cable before installing the lug (do not remove the core yet). Position the connector or lug and crimp it according to the manufacturer's directions, ensuring not to crimp the last 3/8 inch to 1/2 inch of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings and edges after crimping.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with approved solvent-saturated pads, taking care not to let the solvent touch the semi-conductive insulation shield. If abrasive material is necessary, use only aluminum oxide abrasive (120 grit or finer) on the insulation, avoiding the semi-conductive shield, and ensure not to reduce the cable insulation diameter below the kit's allowed range.
- Install the Termination Body
Create a track-resistant moisture seal by wrapping a band of gray silicone rubber electrical tape around the base of the terminal lug. If the barrel diameter is smaller than the cable primary insulation, build up the tape band to equal the insulation diameter. Liberally coat the edge of the semi-conductive insulation shield with silicone grease. For the lower termination with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom. Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise from the loose end, ensuring the termination body, not the core, butts against the leading edge of the mastic seal. Do not push or pull the termination assembly during core removal. If installing a second housing, pull its core down within one coil of the bottom, slide it over the cable, and carefully pull the core counter-clockwise, overlapping the first termination by 1-1/2 inches (40mm).
- Complete Termination Sealing and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, avoiding the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape, overlapping the termination insulator by approximately 1 inch and extending the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration. Connect the ground braid to the system ground. Finally, confirm that the High-K step does not exceed 1.5 inches.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.