ABB Installation Products K676LR-J2270 15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud…
UPC: 075114375337
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating for medium-voltage applications
- 900 Amp continuous current rating
- DeadBreak design with integrated test point for safety and diagnostics
- Accommodates cable insulation diameters from .980 to 1.180 inches
- Compatible with 4/0 AWG stranded/compressed or 250 kcmil solid/compact conductors
Specifications
Amperage Rating | 900 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 13 in |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide-Cured Construction includes Insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and Equipment in a de-energized State. Non-Corrosive Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CETP-J0270
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Intergral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.980 to 1.180 inches (24.9-30.0mm). Aluminum Conductor Material, Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. No Sealing Kit.
655LINK-CLRF0380BDRG
600 Amp, Dead Break, Elbow Connector, Cam-Op Connector Kit, 15KV, Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 700/750, Solid 900.
655LINKCLRL0360BDRG
600 Amp, 15kV, Deadbreak Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
655LINKCLRJ0300BDRG
600 Amp, 15kV, Deadbreak Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
K656CY-M0360
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size 650 kcmil Stranded Compressed or 750 kcmil Compacted Solid.
K656LR-L0230-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 1 or Compact/Solid 1/0 or mm2 Compact 50. Cold-Shrinkable Jacket Seal Included.
756LR-L0300
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size kcmil Compressed Stranded 350 or Compacted Solid 400 or mmSquared Compact 185.
K656CH-M0360
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size 650 Stranded Compressed or 750 kcmil Compacted Solid.Frequently Asked Questions
Can the elbow be connected while energized?
No, the elbow connector must be connected or disconnected using standard hand tools and equipment in a de-energized state.
What is the K676LR elbow connector used for?
The K676LR provides fully shielded, dead-front submersible cable connections to high-voltage apparatus, usable through 28kV.
What conductor sizes are compatible with the K676LR?
The K676LR is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
What cable insulation diameters does the K676LR support?
The K676LR supports cable insulation diameters ranging from .640 in to 1.935 in.
What is the maximum operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV, and phase-to-phase is 14.4kV.
What is the maximum operating voltage for 28kV class?
For the 28kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV, and phase-to-phase is 28kV.
What is the continuous current rating of the elbow?
The K676LR elbow connector has a continuous current rating of 900 Amps for both 15kV and 28kV voltage classes.
What is the momentary current rating?
The momentary current rating for the K676LR is 25kA Symmetrical for 10 cycles.
What is the K676LR elbow connector used for?
The K676LR provides fully shielded, dead-front submersible cable connections to high-voltage apparatus, usable through 28kV.
What conductor sizes are compatible with the K676LR?
The K676LR is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe and proper installation of 600-ampere and 900-ampere deadbreak elbow connectors on 15kV and 25kV class systems. DANGER: All apparatus must be de-energized during installation or removal of parts. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Suitable sensing device (for capacitive test points), Torque wrench
Supplies needed:
655/675LR or K655/K675LR Elbow Connector Kit (includes Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), No. 14 AWG Copper wire (or equivalent ampacity), Suitable connector (for grounding wire), HV insulated cap(s) or connector(s) (if replacing shipping covers), Silicone lubricant
- Inspect Components
Check the package contents to ensure they are complete and undamaged. Inspect all components for damage, proper rating, and compatibility with the cable and/or mating products.
- Assemble Cable and Cut
Assemble the cable in its final position, ensuring enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable
Prepare the cable by removing the outer jacket (if applicable) and other layers to the specified dimensions: Cable Insulation at 9-3/4” (248mm), Semi-con Shield at 10-3/4” (273mm), and Tape Marker at 12-3/4” (324mm) from the mating product centerline. For specific cable types (e.g., UNISHIELD, Lead Sheath) or if using grounding devices (20MA/21MA) or seals (600ECS), consult their respective installation instructions for detailed preparation.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the exposed conductor length is between 4-1/4” – 4-9/16” (108mm-116mm); otherwise, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (this dimension should be less than 6-3/8”). Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter is between 6-3/8” to 7-1/8” (162mm-181mm); otherwise, redo the assembly.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Make sure the cable adapter is still flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
Remove any protective shipping covers from the elbow and the mating part, replacing them with appropriate HV insulated caps or connectors if submerging or energizing. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug Cap (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down firmly until the cap snaps into place.
- Ground the Cable Shield
Insert one end of a wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; ground according to the instructions supplied with any grounding device, or through an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test
WARNING: The voltage test point is a capacitance device; it is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling off at an angle rather than pulling directly. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized, following the manufacturer’s directions for the meter used. Contamination, moisture, dirt, or using the wrong equipment can provide a false 'no voltage' indication. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.