ABB Installation Products 655LINK-CLRF0380BDRG 600 Amp, Dead Break, Elbow Connector, Cam-Op Connector Kit, 15KV, Cable Insulation…
UPC: 783786435340
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp continuous current rating for medium-voltage systems
- Dead break design allows safe de-energization before disconnection
- Cam-Op connector with hotstick operation for easy installation and maintenance
- Compatible with compressed stranded (700/750 AWG) and solid (900 AWG) conductors
- Cable insulation diameter range: 0.640 to 0.820 inches (16.3 to 20.8 mm)
- Aluminum Compression Lug for 700/750 AWG Stranded or 900 AWG Solid conductors
Specifications
Amperage Rating | 600 A |
Application | External Visible Break, Testing, Grounding and Isolation |
Color | Black |
Conductor Range | 700 to 750 kcmil , 900 kcmil |
Connection | Compression |
Insulation | True |
Material | EPDM-Rubber |
Size | 20.50 inches from edge of Lever to Bushing Flange |
Special Features | Easily Installed or Removed by Hotstick Operation of the Cam Action Disconnect Lever |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Cam_OP Connector Kit |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

655LRTPFB-M5380-DRG
600 Amp, 15KV, Stick Op Connector Kit, Fixed Bolt, Insulating Cap, Stick Op Load Break Reducing Tap Plug, Elbow Housing, Cable Adapter and Threaded Lug, Cable Insulation Diameter 1.370 inch to 1.630 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
655LINKCLRL0360BDRG
600 Amp, 15kV, Deadbreak Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
655LINKCLRJ0300BDRG
600 Amp, 15kV, Deadbreak Cam-Op Connector Kit with Insulated Cap, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
K656CY-M0360
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size 650 kcmil Stranded Compressed or 750 kcmil Compacted Solid.
K656LR-L0230-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 1 or Compact/Solid 1/0 or mm2 Compact 50. Cold-Shrinkable Jacket Seal Included.
756LR-L0300
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size kcmil Compressed Stranded 350 or Compacted Solid 400 or mmSquared Compact 185.
K656CH-M0360
600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size 650 Stranded Compressed or 750 kcmil Compacted Solid.
756LR-L0230-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed Stranded #1 or Compacted Solid 1/0. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
How do I determine the correct X code for ordering?
Choose the proper compression lug code from the Conductor Code Table based on the conductor size.
What are the applications of the CAM-OP Connector Kit?
It's used for hotstick operations on de-energized primary feeder or network circuits, allowing external visible break, testing, grounding, and isolation.
What is the maximum operating voltage for this kit?
The maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase voltage is 14.4kV.
What is the continuous current rating of the kit?
The CAM-OP Connector Kit has a continuous current rating of 600 Amps.
What ANSI/IEEE standard does this product meet?
The product meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand voltage (BIL)?
The impulse withstand (BIL) is 95kV (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage?
The AC one-minute withstand voltage is 34kV.
What is the DC fifteen-minute withstand voltage?
The DC fifteen-minute withstand voltage is 53kV.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 Cycles.
How do I determine the correct W code for ordering?
Determine the cable's insulation diameter and select the insulation letter code from the W table that best straddles this diameter.
How to Install the LINK-C Deadbreak Cam Link Operable Connector System
This guide provides step-by-step instructions for installing the LINK-C 600 amp deadbreak connector, enabling a fully shielded, submersible connection between cable and apparatus, with an optional 200 amp tap.
Estimated time: 2h 30m
Tools needed:
600ATM Operating Tool, Torque wrench, Socket wrench (for 1 inch hex), Hot stick, Wire strippers
Supplies needed:
ELASTIMOLD supplied lubricant, #14 AWG or #12 AWG solid copper wire, Appropriate grounding connector, HV insulated cap(s) or connector(s)
- Perform Pre-Installation Checks and Safety Procedures
DANGER: All apparatus must be de-energized during installation or removal of parts. All deadbreak connectors must be de-energized before operating. All 200A deadbreak connectors must be mechanically secured with bails when connected. Inspect all parts for damage, proper rating, and compatibility with mating parts. Check package contents for completeness. Read all instructions thoroughly before starting. Have all required tools ready and maintain cleanliness. If supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Install the 600 Amp Elbow onto the Cable
Install the 600 amp elbow onto the cable according to the installation instructions supplied with the elbow. Ensure the elbow is positioned such that it will align correctly with the stand-off plug.
- Prepare and Install the Bushing Extender
Clean and thoroughly lubricate the apparatus bushing and both interfaces of the 600 amp bushing extender with ELASTIMOLD supplied lubricant. Install the bushing extender onto the apparatus bushing. Insert the 600ATM operating tool into the retainer contact and engage its internal hex broach. Insert the retainer contact into the bushing extender and thread it into the apparatus bushing using a suitable tool applied to the 1” hex portion of the 600ATM. Torque to 50-60 ft-lbs.
- Prepare and Install the 600 Amp Elbow onto the Epoxy Standoff Plug
Clean and thoroughly lubricate the epoxy standoff plug and both interfaces of the 600 amp elbow with ELASTIMOLD supplied lubricant. Install the elbow onto the epoxy standoff plug. Insert the 600AMT operating tool into the retainer contact and engage its internal hex broach. Insert the retainer contact into the 600 amp elbow through the hole in the compression lug and thread it into the epoxy standoff plug using a suitable tool applied to the 1” hex portion of the 600AMT. Torque to 50-60 ft-lbs.
- Install the Alignment Bracket
Remove the bushing extender clamp and elbow clamp from the alignment bracket. Position the alignment bracket on the bushing extender at a dimension of 2.5 inches (63.5mm) from the grounding eye. Assemble the bushing extender clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until the clamp tabs are flush with each other and tight on both sides.
- Position and Secure the Elbow in the Alignment Bracket
Position the elbow in the alignment bracket such that the elbow cuff is lined up evenly with the bushing extender cuff. Assemble the elbow clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until the clamp tabs are flush with each other and tight on both sides. Ensure the elbow clamp notch faces the cable entrance of the elbow.
- Clean, Lubricate, and Insert the Link
Clean and thoroughly lubricate both 600 ampere interfaces of the Link with ELASTIMOLD supplied lubricant. Align the Link such that when inserted into the bushing extender and elbow, it is perpendicular to the switch faceplate. Insert the Link into the bushing extender and elbow, ensuring both lever arms are on the inside of the alignment bracket legs.
- Engage and Secure the Link
Engage the pivot pin into the slots in the alignment bracket legs. While pushing inward, move the lever arms downward using a hot stick eye. This action will engage the roller pin and move the Link inward. Continue moving the lever arms until they are perpendicular to the alignment bracket leg.
- Ground the System and Install Mating Products
Ground the elbow: Feed a #14 AWG or #12 AWG solid copper wire through the grounding eye on the elbow, twist it tight, and connect it to ground. Clean and lubricate the 200 amp interface on the Link. Ground, then install the desired mating product on the 200 amp interface according to its supplied installation instructions. Ground the cable: If using concentric neutral cable, twist the concentric neutral wires together and connect to ground using an appropriate connector. If 20MA or 21MA grounding devices are used, connect the ground lead from the device to ground using a suitable connector. For three-phase installations, ensure all grounds from all three phases are tied to a common ground point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.