ABB Installation Products K656CH-M0360 600 Amp, 15/25 kV, Separable H Joint package 4-Way with Test Point, Cable Insulation…
UPC: 075114376327
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600A continuous current rating with 25kA symmetrical momentary rating
- Supports 650 stranded compressed or 750 kcmil compacted solid conductors
- Cable insulation diameter range: 1.370 inch to 1.630 inch
- Fully shielded, submersible design with 100% peroxide-cured EPDM rubber
- Integral capacitive test point for safe voltage verification without de-energization
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 650 kcmil , 750 to 800 kcmil |
Connection | Compression |
Connection Type | Compression Lug, Separable H Joint |
Connection Type | Compression Lug |
Current Rating | 600 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Ip Rating | Fully Submersible |
Length | 37.27 in |
Length | 946.658 mm |
Material | Aluminum |
Material | EPDM Rubber, Aluminum |
Material | Housing - EPDM-Rubber |
Mounting Type | Compact Design for Vaults/Manholes |
Poles | 4P |
Series | K656CH |
Size | 1.370-1.630 inch Insulation Diameter |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Special Features | Fully Shielded, Fully Submersible, 100 Percent Peroxide Cured EPDM Molded Rubber. Includes Integral Capacitive Test Point. Reusable Components Reduce Inventory and other Costs |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable H-Joint Assembly |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 8.12 in |
Width | 206.248 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-M0360-SG3
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400. 200ECS-G3 Jacket Seal and Grounding Kit Included.
756LR-L0230-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed Stranded #1 or Compacted Solid 1/0. Cold-Shrinkable Jacket Seal Included.
655CETPH0270
15kV, 600 Amp, Combo T Reducing Tap Plug with Stud, Cable Adapter, Lug and Insulated Cap Kit. Cable Insulation .850-1.050 inches. Universal Aluminum Connector Type, Connector Size 4/0 Stranded/Compressed or 250 Compact/Solid. No Test Point.
755LR-N5330
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.515 inch to 1.780 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.
K656LR-G5220
15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation .760 to .950 inch. Bi-Metal Compression Lug, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid
262LRJS-B5210
28kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .635 inch - .905 Inch Cable Insulation Diameter, #3 Stranded/Compressed or #2 Compact/Solid Wire Size, Bi-Metal Compression Lug.
K656ETP-K0330-DRG
600 Amp, Test and Ground Connector Kit, 25KV, Capacitive Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.Frequently Asked Questions
What is included in a complete K656CH joint package?
A complete package includes an insulated bus bar, straight receptacle housing, retaining rings, cable size adapters, lugs, bolts, and washers.
Does the K656CH separable joint include a test point?
Yes, the K656CH joint includes an integral capacitive test point.
What is the momentary current rating of the K656CH joint?
The momentary current rating is 25kA Symmetrical for 10 cycles for both 15kV and 25kV classes.
Which industry standards does the K656CH joint meet?
The K656CH joint meets ANSI/IEEE Standard 386, Latest Revision.
What are the 25kV class operating voltage limits?
For the 25kV class, max phase-to-ground operating voltage is 16.2kV and max phase-to-phase is 28kV.
What is the continuous current rating for the K656CH joint?
The continuous current rating for the K656CH joint is 600 Amps for both 15kV and 25kV voltage classes.
What are the 15kV class operating voltage limits?
For the 15kV class, max phase-to-ground operating voltage is 8.3kV and max phase-to-phase is 14.4kV.
What is the K656CH separable "H" joint used for?
It joins cables in a disconnectable 4-way joint, suitable for small vaults, manholes, and direct-buried applications.
What is the design of the K656CH separable "H" joint?
It is a fully shielded, fully submersible, 4-way disconnectable cable joint based on a 4-way bus bar, made of 100% peroxide cured EPDM molded rubber.
What is included in a complete K656CH joint package?
A complete package includes an insulated bus bar, straight receptacle housing, retaining rings, cable size adapters, lugs, bolts, and washers.
How to Install K656 Series Deadbreak Receptacles
This guide provides detailed instructions for the safe and proper installation of K656 series deadbreak receptacles, including cable preparation, crimping, and final assembly for high voltage applications.
Estimated time: 2h
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire brush (for aluminum cable), Cable stripping tools (for jacket, semi-con, insulation), Rag, Approved safety solvent, Assembly tool (650ATY or 600RRT)
Supplies needed:
Lubricant (supplied or ELASTIMOLD approved), No. 14 AWG copper wire (or equivalent), HV insulated cap(s) or connector(s), Conductive copper strip (for flat metallic tape shielded cable)
- Prepare for Installation and Inspect Components
Ensure all apparatus is de-energized before beginning installation. Inspect all components for damage, proper rating, and compatibility with mating parts. Confirm the package contents are complete and undamaged. Read the entire instructions before proceeding and gather all required tools. DANGER: All apparatus must be de-energized during installation or removal of part(s). Do not touch or move energized products in the work area. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment.
- Prepare the Cable and Slide Initial Components
Wipe the outer jacket of the cable clean for a distance of 38 inches. Cut the cable end squarely to ensure maximum available length for crimp growth. If using an ECS grounding device, slide the ECS tube onto the cable a distance of 38 inches. Then, slide the receptacle housing onto the cable a distance of 30 inches.
- Perform Cable Specific Preparation
Follow the specific cable preparation procedure based on your cable type. For Jacketed Concentric Neutral Cable (Part A), remove the cable jacket 13-3/4 inches from the end, bend neutral wires back, and remove the semi-con 10-1/4 inches from the end. For Flat Metallic Tape Shielded Cable with Semi-con Shield (Part B), remove the outer jacket 13-3/4 inches from the end, remove the tape shield 11-1/4 inches from the end, and remove the semi-con shield 10-1/4 inches from the end. In both cases, bevel the insulation end at a 45-degree angle approximately 1/4 inch back and thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket.
- Install Cable Adapter and Retaining Ring
Apply supplied or ELASTIMOLD approved lubricant sparingly along the prepared cable and generously inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until its end is flush with the tape marker (if applicable). Remove any protruding cable insulation by cutting it even with the end of the cable adapter, ensuring not to cut or nick the adapter or conductor. The exposed conductor should measure 4 3/4 to 5 inches. Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor now measures 4 3/8 to 4 3/4 inches.
- Crimp the Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately fully insert it into the crimp connector, which contains inhibitor. Measure the distance from the end of the connector to the holding collar; it should be 6 3/4 to 7 inches. Confirm the bolt holes in the crimp connectors are positioned properly to align with the bolt holes of the mating part. Crimp the connectors following the instructions packaged with them, rotating each crimp 90 or 180 degrees. After crimping, re-measure the distance from the end of the connector to the holding collar, ensuring it is still 6 3/4 to 7 inches.
- Assemble and Torque Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten all bolts. Clean and lubricate the splice area. Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. Do not attempt to move or reposition any part of the assembly after the bolts are tightened.
- Install Receptacle Housing and Vent
Apply supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied). Use an assembly tool (650ATY or 600RRT) to slowly slide the receptacle housing completely over the splice section. Once fully seated, remove the venting rod. WARNING: If using the 600RRT tool, do not place your hand on the threaded rod or guide shaft with the assembly tool in place.
- Complete Grounding and Final Checks
If an ECS grounding device is used, complete its installation according to its specific instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly without damaging the eye. Connect this wire to ground. Check all cable adapters to ensure they are located properly and remove all vinyl tape markers. Remember to repeat steps 4 through 7 for any remaining cables to be joined.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.