ABB Installation Products K675LR-N-5410 900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable…
UPC: 783786543571
Documents & Media
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 900 Amp continuous current rating at 15/25kV
- Accommodates cable insulation diameters from 1.515" to 1.780"
- Supports compressed stranded conductors up to 1000 kcmil
- Fully shielded, submersible molded rubber housing with 100% peroxide-cured EPDM
- Meets ANSI/IEEE Standard 386 for deadbreak applications
Specifications
Amperage Rating | 900 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 1000 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Current Rating | 900 A |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Material | Bi-Metal, Insulated |
Material | Bi-Metal Compression Lug |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | 1.515-1.780" Cable Insulation Diameter, 1000 kcmil Conductor |
Size | 1.515 inch to 1.780 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CYP0410P0410P041
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, with 3 X ( Cable Insulation Diameter 1.725 inch to 1.935 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. )
K655SR-K2330
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300. Length 17 inches, Diameter 4-1/4 inch.
K656DLR-N0410
600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed Stranded 1000.
K656CY-G0250-SG1
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included.
K655YSR-K0310
600 Amp Separable Cable Joints, Straight Receptacle, 15/25KV, Dead Break, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 400 kcmil or Solid Compact 450/500 kcmil or 202.68 mmSquared. Length 17 inch, Widest Diameter 4.19 inch. Includes Straight Receptacle Housing, Cable Adapter, Lug, Adapter Retaining Ring, Washer and Bolts, Lubricant, Installation Instruction Sheet and Crimp Chart.
K676LR-H5270
15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation .850-1.050 inches, Bi-Metal Compression Lug, Conductor Size AWG 2/0 Stranded/Compressed or 3/0 Compact/Solid.
K655SR-F0240
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.640 inch to 0.820 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
755LR-K0250-S
35kV 600 Series Deadbreak Elbow without Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70. 200ECS Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
Is the K675LR-N-5410 suitable for submersible applications?
Yes, the K675LR-N-5410 features a fully shielded, submersible molded rubber housing designed for dead-front submersible cable connections.
What is the continuous current rating of the K675LR-N-5410?
The K675LR-N-5410 has a continuous current rating of 900 Amps.
Does the K675LR-N-5410 meet any industry standards?
Yes, the K675LR-N-5410 meets ANSI/IEEE Standard 386, the latest revision for deadbreak connectors.
Can the K675LR-N-5410 be used with metallic tape shield or drain wire cables?
Yes, but an ECS cable seal grounding device is recommended when used with metallic tape shield or drain wire cables.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 655/675LR and K655/K675LR deadbreak elbow connectors, including cable preparation, lug crimping, and connection to mating parts.
Estimated time: 1h
Tools needed:
Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable sensing device
Supplies needed:
Elbow, Cable adapter, Compression lug, Insulating plug, Lubricant, Threaded stud, Wire (at least No. 14 AWG Copper), Suitable connector (for grounding), HV insulated cap(s) or connector(s), Silicone lubricant
- Prepare Cable for Installation
Ensure all apparatus is de-energized before starting. Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for 24” (610mm) or up to the bent back neutral wires. Inspect all parts for damage, rating, and compatibility. Remove any shipping covers and replace with appropriate HV insulated caps or connectors before energizing.
- Prepare Cable End
Follow the specific cable preparation instructions (e.g., for jacketed, non-jacketed, Unishield, or lead sheath cables) as detailed in the product documentation, including outer jacket removal and shield connection. Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Install Conductor and Crimp Lug
Remove protruding cable insulation, cutting it even with the cable adapter end. Do not cut or nick the adapter or conductor. Verify exposed conductor length is 4-1/4” to 4-9/16” (108mm-116mm). For copper, fully insert the conductor into the compression lug. For aluminum, wire brush and immediately insert. Measure the 'Check Dimension' (must be < 6-3/8”). Crimp the lug per instructions. Wipe excess inhibitor. Verify lug-to-adapter distance is 6-3/8” to 7-1/8” (162mm-181mm).
- Install Elbow and Prepare Mating Parts
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further, ensuring the adapter remains flush with the tape marker. Remove the tape marker. Remove protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the supplied threaded stud into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant. DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED.
- Connect Elbow to Mating Parts
Push the elbow onto the first mating part, aligning the compression lug hole with the stud. Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage threads, and hand tighten. Torque the mating part according to its specific instructions. If using an insulating plug, clean and lubricate the inner surface of the voltage detection cap and push it onto the elbow until it snaps into place.
- Ground Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper) through the grounding eye and twist to form a small loop, avoiding damage to the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions for the grounding device or use an alternate method. Waterproof the cable jacket at this point to prevent moisture from entering the cable. CAUTION: When constructing 600amp L-Kits, ensure each component is tightened to the specified torque per the instructions provided.
- Perform Voltage Test (Optional)
WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Remove the test point cap with a hotstick, peeling it off at an angle. Test with a suitable sensing device designed for capacitive test points to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.