ABB - Installation Products K675BIP - 15/25kV, 900 Amp, Deadbreak, Insulating Plug with Cap.

ABB Installation Products K675BIP 15/25kV, 900 Amp, Deadbreak, Insulating Plug with Cap.

UPC: 783786626915


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call (262) 252-1600 or email [email protected] for pricing and availability.

Overview

The ABB K675BIP is a 15/25kV, 900 Amp deadbreak insulating plug designed for safe and reliable electrical connections in medium-voltage systems. This fully rated plug meets ANSI/IEEE Standard 386 and is compatible with Elastimold® K675/6BLR, K675BE, and K675BVS 900 Amp connectors. Its deadbreak design allows for secure termination and disconnection in de-energized states using standard hand tools, ensuring operator safety and preventing accidental contact with live parts. The integrated capacitive test point (hex nut) enables voltage verification without disassembly, while the molded rubber sealing cap provides environmental protection when not in use. Rated for 8.3kV phase-to-ground and 14.4kV phase-to-phase at 15kV class (21.1kV/36.6kV at 25kV class), the K675BIP delivers 900 Amp continuous current with 25kA symmetrical momentary rating. Ideal for utility substations, industrial power distribution, and critical infrastructure where dependable insulation and current carrying capacity are essential.
  • 15/25kV voltage rating with 900 Amp continuous current capacity
  • Deadbreak design for safe connection/disconnection in de-energized states
  • Integrated capacitive test point (hex nut) for voltage verification
  • Molded rubber sealing cap included for environmental protection
  • Meets ANSI/IEEE Standard 386 with 25kA momentary rating

Specifications

Application
15/25 kV, 900 Amps
Connection Type
Deadbreak
Current Rating
900 A
Material
Copper
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Insulating Plug with Cap
Voltage Rating
15/25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.6300 L
Package Weight (Metric)
0.7390 kg
900 Amp, 35kV, 600 Series Elbow with Test Point Housing only, with Stud.

776BLR

900 Amp, 35kV, 600 Series Elbow with Test Point Housing only, with Stud.
15/25kV 600 Series Deadbreak Insulated Plug (with Cap), Factory assembled stud which is not field removable.

K650BIPSP

15/25kV 600 Series Deadbreak Insulated Plug (with Cap), Factory assembled stud which is not field removable.
600 Amps, Dry Type, Long Shank Bushing for Air Applications

K600-TBC

600 Amps, Dry Type, Long Shank Bushing for Air Applications
600 Amp, 15/25kV, Insulated Cap with Test Point, with Stud.

K676DR

600 Amp, 15/25kV, Insulated Cap with Test Point, with Stud.
600 Amp, 15/25 KV, Elbow, with Test Point Housing only, Without Stud

K656BLRN

600 Amp, 15/25 KV, Elbow, with Test Point Housing only, Without Stud
15/25kV 600 Series Deadbreak Insulated Plug (with Cap), Loose Stud.

K650BIPS

15/25kV 600 Series Deadbreak Insulated Plug (with Cap), Loose Stud.
15/25kV, 900 Amp Deadbreak, Elbow Housing without Test Point, with Stud.

K675BLR

15/25kV, 900 Amp Deadbreak, Elbow Housing without Test Point, with Stud.
15/25kV 600 Series Deadbreak Reducing Tap Well wih factory assembled stud which is not field removable.

K650RTWSP

15/25kV 600 Series Deadbreak Reducing Tap Well wih factory assembled stud which is not field removable.

Frequently Asked Questions

What is the momentary current rating?

The momentary current rating is 25kA Symmetrical for 10 Cycles for both 15kV and 28kV voltage classes.

What is the impulse withstand rating for 28kV class?

For the 28kV voltage class, the impulse withstand (BIL) is 140kV.

What is the impulse withstand rating for 15kV class?

For the 15kV voltage class, the impulse withstand (BIL) is 95kV.

What items are included in the K675BIP kit?

Each kit contains one K675BIP insulating plug with cap, one tube of lubricant (82-08), and one installation instruction (IS-0230).

What standard does the K675BIP meet?

The K675BIP meets ANSI/IEEE Standard 386, Latest Revision.

What is the continuous current rating of the K675BIP?

The K675BIP has a continuous current rating of 900 Amps for both 15kV and 28kV voltage classes.

What are the 28kV class operating voltage limits?

For the 28kV class, the maximum phase-to-ground operating voltage is 16.2kV, and the maximum phase-to-phase is 28kV.

What are the 15kV class operating voltage limits?

For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.

What connectors are compatible with the K675BIP?

The K675BIP attaches and insulates Elastimold® K675/6BLR, K675BE, and K675BVS 900 Amp connectors.

What is the K675BIP insulating plug?

The K675BIP is a 15/25kV 900 Amp Deadbreak Insulating Plug with a test point. It attaches and insulates specific Elastimold® 900 Amp connectors.

How to Install 15/25/35kV 600/900 AMP Deadbreak Plug and Well Products

This guide provides step-by-step instructions for installing 15/25/35kV 600/900 AMP Deadbreak Plug and Well products, including mating with elbows or bushing extensions and performing voltage tests.

Estimated time: 30m

Tools needed:

Torque wrench, ELASTIMOLD 600SW spanner wrench, Hotstick, Suitable sensing device for capacitive test points

Supplies needed:

15/25/35kV 600/900 AMP Deadbreak Plug or Well, Lubricant (supplied), 15/25/35kV 600/900 AMP Elbow or Bushing Extension, HV insulated cap(s) or connector(s), Silicone lubricant

  1. De-energize Apparatus and Inspect Parts

    DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts. Verify package contents are complete and undamaged, and all components fit correctly with cables and/or mating products. Have all required tools at hand and maintain cleanliness throughout the procedure.

  2. Remove Shipping Covers (if applicable)

    If the product is supplied with protective shipping cover(s), remove these shipping cover(s) and replace with the appropriate HV insulated cap(s) or connector(s) before submerging or energizing the circuit.

  3. Prepare and Lubricate Plug/Well and Mating Part

    Remove protective caps from the plug or well product. If the 600amp mating interface is not equipped with a stud, hand tighten the stud (supplied with elbow/bushing extension) into a 600amp interface on the plug or well. Lubricate both the elbow/bushing extension and its mating part as indicated with ONLY the lubricant supplied. DO NOT SUBSTITUTE other lubricants, as they may be harmful to the products. Be sure to keep surfaces of the elbow and mating parts clean.

  4. Connect Plug/Well to Elbow/Bushing Extension

    Push the plug or well firmly into the elbow or bushing extension and engage the threads.

  5. Torque Tighten the Connection

    Use a torque wrench to tighten the connection. For an Insulating Plug, apply 50 to 60 foot-pounds of torque. For a Connector Plug, Tap Plug, or Tap Well, use a torque wrench with an ELASTIMOLD 600SW spanner wrench, applying an indicated torque of 40 to 48 foot-pounds. For K651 and 750 Rubber Connecting Plugs, refer to special instructions IS-0915.

  6. Install Voltage Detection Cap (if insulating plug is used)

    If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.

  7. Remove Test Point Cap

    Using a hotstick, remove the test point cap. When removing the cap, PEEL OFF AT AN ANGLE rather than pulling directly in line with the test point assembly.

  8. Perform Voltage Test

    WARNING: The voltage test point is a capacitance device; it is NOT directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter that is used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, etc., around the test point or use of the wrong measuring equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means.

  9. Replace Test Point Cap

    After voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant and replace it firmly on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.