ABB Installation Products K656YDSR-M0380 15-25kV 600 Series Deadbreak Direct Test Straight Receptacle Elbow with Test Point…
UPC: 783786949472
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15-25kV voltage rating for medium-voltage systems
- Deadbreak design allows safe installation without load interruption
- Test point enables non-invasive voltage detection
- Supports cable insulation diameters from 1.370" to 1.630"
- Aluminum compression lug for 700/750 AWG or 900 kcmil conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 700 to 750 kcmil , 900 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Direct Test Straight Receptacle Elbow with Test Point |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

656ETP-M0380-DRG
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 700/750 kcmil or Compacted Solid 900 kcmil.
252LR-B5210
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635-0.905 inches (16.13-22.99mm), Bi-Metal Lug, Conductor Size 210 - #3 Stranded/Compressed, #2 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-A5250
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575-0.740 inches (14.61-18.80mm), Bi-Metal Lug, Conductor Size 250 - 2/0 Stranded/Compressed, 3/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
K656CY-DP0593491
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, (1) M0360 - Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 650 or Compacted Solid 750 or mmSquared Compact 400. (2) L0320 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Compacted Solid 500/550. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included. K656CY-M0360-L0320-L0320-SG1
K656CY-DP0593492
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, (2) M0360 - Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 650 or Compacted Solid 750 or mmSquared Compact 400. (1) L0320 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Compacted Solid 500/550. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included. K656CY-M0360-M0360-L0320-SG1
K656CY-DP0595084
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, (1) L0320 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Compacted Solid 500/550. (2) G0250 - Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 or Compacted Solid 3/0 or mmSquared Compact 70. Cold Shrinkable Seal with Copper Rod and Crimp Connector Included. K656CY-L0320-G0250-G0250-SG1
K656CY-DP0590523
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, (2) M0380 - Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 700/750 or Compacted Solid 900. (1) K0300 - Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 350 or Compacted Solid 400 or mmSquared Compact 185. K656CY-M0380-M0380-K0300
K656CY-DP0594897
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point, (2) K0270 - Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Compacted Solid 250 or mmSquared Compact 125. (1) M0320 - Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 450 or Compacted Solid 500/550. K656CY-(2)K0270-(1)M0320Frequently Asked Questions
What items are included in the K656YDSR kit?
Each kit includes a straight receptacle housing, lubricant, installation instructions, cable adapter, aluminum compression lug, adapter retaining ring, crimp chart, and bolts and washers.
Is the K656YDSR submersible?
Yes, the K656YDSR features a fully shielded, fully submersible molded rubber housing.
What is the momentary current rating?
The momentary current rating for both 15kV and 25kV voltage classes is 25kA Sym for 10 Cycles.
What is the continuous current rating?
The continuous current rating for both 15kV and 25kV voltage classes is 600 Amp.
What are the 25kV class operating voltage limits?
For the 25kV class, the maximum phase-to-ground operating voltage is 16.2kV and maximum phase-to-phase is 28kV.
What are the 15kV class operating voltage limits?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV and maximum phase-to-phase is 14.4kV.
What standard does the K656YDSR meet?
The K656YDSR meets ANSI/IEEE Standard 386, Latest Revision.
What conductor sizes are compatible with K656YDSR?
The K656YDSR is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors. It supports insulation diameters from .640 in to 1.935 in.
What is the K656YDSR designed for?
The K656YDSR provides a fully shielded, submersible cable connection on 15/25kV high-voltage “I”, “Y”, or “H” Bus.
What is the K656YDSR designed for?
The K656YDSR provides a fully shielded, submersible cable connection on 15/25kV high-voltage “I”, “Y”, or “H” Bus.
How to Install Deadbreak Receptacles with Direct Access Port
This guide provides detailed instructions for installing K656DCY, K656DCH, and K656DI deadbreak receptacles, designed to splice and tap solid dielectric cables for high-current applications. It covers cable preparation, assembly, and initial setup.
Estimated time: 2h
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire brush (for aluminum cable), Wire strippers, Rag, 650ATY assembly tool OR 600RRT assembly tool, Hotstick tool (for test cap), Specific meter and test cap (for direct test)
Supplies needed:
Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Lubricant (supplied), Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod (supplied), ECS sealing device (optional), Tape, Approved safety solvent, Conductive copper strip (for flat metallic tape shielded cable), No. 14 AWG copper wire (for grounding)
- Prepare for Installation and Safety Checks
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, rating, and compatibility with mating parts. Check package contents for completeness. Wipe the outer jacket of the cable clean for a distance of 38 inches. If using an ECS sealing device, slide the tube onto the cable 38 inches. Slide the receptacle housing onto the cable 30 inches.
- Prepare the Cable (Select Type)
Follow the specific procedure for your cable type. For Jacketed Concentric Neutral Cable: From the cable end, remove 13-3/4 inches of jacket and 10-1/4 inches of semi-con, taking care not to damage neutral wires or insulation. Bend neutral wires back. Wrap two turns of tape 1 inch from the semi-con end. Bevel the insulation end at a 45-degree angle for 1/4 inch. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until flush with the tape marker. For Flat Metallic Tape Shielded Cable with Semi-con Shield: From the cable end, remove 13-3/4 inches of outer jacket. Remove 11-1/4 inches of tape shield, wrap a conductive copper strip around the edge, and wrap two turns of tape over the end of the tape shield and copper strip, with the tape edge 11-1/4 inches from the outer jacket end. Remove 10-1/4 inches of semi-con shield. Bevel the insulation end at a 45-degree angle for 1/4 inch. Thoroughly clean the insulation with an approved safety solvent, wiping from the cable end toward the outer jacket. Apply lubricant sparingly along the cable and inside the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until flush with the tape marker.
- Assemble Retaining Ring and Crimp Connector
Remove any protruding cable insulation, cutting it even with the end of the cable adapter. Do not cut or nick the adapter or conductor. The exposed conductor should measure 4-3/4 to 5 inches. Assemble the aluminum retaining ring over the conductor and snug firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor measures 4-3/8 to 4-3/4 inches. Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor and immediately fully insert it into the crimp connector containing inhibitor. Measure the distance from the end of the connector to the retaining ring; if over 7 inches, redo previous work. Repeat cable preparation and this step for all remaining cables to be joined. Prior to crimping, confirm components are positioned as shown in the instructions, ensuring bolt holes in the crimp connectors align with the mating part.
- Crimp Connectors and Secure Splice
Crimp each connector following the instructions packaged with the connectors. Rotate each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if over 7 inches, redo previous work. Assemble the washers and bolt in the following order: flat washer against spade contact, Belleville washer (concave side down), hex-head bolt. Hand tighten. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after bolts are tightened. Using a torque wrench with a 15/16 inch socket, tighten each bolt to 50 to 60 ft. lbs.
- Install Receptacle Housing
Apply supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied). Use either the 650ATY or 600RRT assembly tool to slide the receptacle housing over the splice section. WARNING: Do not place hands on the threaded rod or guide shaft with the assembly tool in place. Remove the venting rod once the housing is in place. Repeat the lubrication and housing installation steps for any remaining cables.
- Final Checks and Grounding
Check all cable adapters to ensure they are located properly and remove all vinyl tape markers. Complete the installation of any ECS grounding device according to its instructions. Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings. Make a small loop and twist tightly, taking care not to damage the eye, and connect to ground.
- Perform Direct Voltage Test (Optional)
To perform a direct test, a specific meter and test cap are required. DANGER: Not following these instructions or inserting objects other than the test cap can cause serious or fatal injury. The elbow access port provides direct access to the cable conductor. Contact with the uncovered port or insertion of objects other than the insulated cap or voltage test cap can cause serious or fatal injury. Removal of the insulated cap and installation of the voltage test cap must be done with a hotstick tool following instructions packaged with the voltage test cap. Refer to the operating instructions included with the meter and test cap for voltage measurement.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.