ABB Installation Products K656LR-E0240 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…
UPC: 075114392310
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25 kV voltage rating with 600 Amp continuous current capacity
- Integrated test point for safe voltage checks without de-energizing the system
- Accommodates cable insulation diameters from 0.530 inch to 0.680 inch
- Supports conductor sizes from 1/0 AWG compressed/stranded to 2/0 AWG compact/solid
- Complete installation kit includes elbow housing, aluminum compression lug, stud, insulated plug, lubricant, cable adapter, instructions, and crimp chart
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection Type | Deadbreak Elbow with Test Point |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K656LR |
Size | 0.530-0.680 inch (cable insulation diameter) |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-H0240
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0.
M465LR-G2240
35kV, 630 Amp, Deadbreak Elbow, No Test Point, IEC-IEEE, No Sealing Kit. Cable Insulation Diameter 0.760 to 0.95 inch, Copper Lug, Wire Range 1/0 Stranded/Compressed or 2/0 Solid Compact. 10.36 inch (264.1mm) x 13 inch (330.2mm) from Bottom to Center of Bushing. Includes Elbow Connector Housing, Compression Lug, Stud, Insulated Plug with Cap, Lubricant, Cable Adapter, Installation Instructions and Crimp Chart.
162LRJSC5270-CS782C
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 inch Cable Insulation Diameter. Wire Size 1/0 Stranded/Compressed, 2/0 Solid/Compact, 53.49 mm2. Bi-Metal Compression Lug. ANSI/IEEE Standard 386. Includes Elbow Connector Housing, Compression Lug, Probe, Lubricant, V.D Cap-Peroxide, Butyl Auto Tape, Contact Adapter Ring, Crimp Chart, Installation Instructions. Boxed Individually.
162LRJSB5240-CS782C
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter. Wire Size 1/0 Stranded/Compressed, 2/0 Solid/Compact, 53.49 mm2. Bi-Metal Compression Lug. ANSI/IEEE Standard 386. Includes Elbow Connector Housing, Compression Lug, Probe, Lubricant, V.D Cap-Peroxide, Butyl Auto Tape, Contact Adapter Ring, Crimp Chart, Installation Instructions. Boxed Individually.
262LR-C5240-CS2089
25kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug. Includes 62 inch Ground Lead Installed Through Grounding Eye Utilizing Rivet.
252LR-D2120
12/20 (24) kV, 250 Amp, Deadbreak, Elbow Connector with Test Point, No Sealing Kit, Cable Insulation Diameter - 22.61mm - 30.99mm, Copper Compression Lug, Conductor Size 120mm. Includes Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Bail Assembly, Tube of Lubricant, Installation Instructions, Crimp Chart and V.D. Cap-Peroxide. IEC Standard.
162LR-B5240-CS2089
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Includes 62 inch Ground Lead Installed Through Grounding Eye Utilizing Rivet.
K656LR-JAC02
15/25kV, 600 Amps, Separable Cable joint Elbow with Test Point, Includes Elbow Connector Housing, Insulated Plug with Cap, Stud, Shear Bolt Lug, Cable Adapter and Lubricant. Cable Insulation Range 0.98 to 1.18 inch. Shear Bolt Lug AC02 Range 4/0 to 500 kcmil Stranded - Compressed - Solid - Compact.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
The K656LR is designed for up to 28kV. For the 15kV voltage class, the max operating voltage is 8.3kV phase-to-ground. For the 28kV voltage class, it is 16.2kV phase-to-ground.
What conductor sizes can the K656LR accommodate?
It can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for the K656LR connector?
The connector is suitable for insulation diameters ranging from 0.640 inches to 1.935 inches.
What standards does the K656LR elbow connector meet?
The K656LR meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous current rating of the K656LR?
The K656LR has a continuous current rating of 600 Amps.
What is the momentary current rating for the K656LR?
It has a momentary current rating of 25kA Sym for 10 Cycles.
What is the impulse withstand rating for the 28kV voltage class?
For the 28kV voltage class, the impulse withstand rating is 140kV BIL (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage for the 15kV class?
The AC one-minute withstand voltage for the 15kV voltage class is 34kV.
What is the AC one-minute withstand voltage for the 28kV class?
The AC one-minute withstand voltage for the 28kV voltage class is 45kV.
What is the corona extinction rating for the 28kV voltage class?
For the 28kV voltage class, the corona extinction is 21.5kV AC at 3pC sensitivity.
How to Install Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors. These connectors provide fully shielded, submersible cable connections to high voltage apparatus and enable splicing or tapping of 600-ampere or 900-ampere systems.
Estimated time: 2h
Tools needed:
Wire strippers, Measuring tape or ruler, Crimping tool, Wire brush (for aluminum conductors), Torque wrench, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
Elbow connector (655/675LR or K655/K675LR), Cable adapter, Compression lug, Insulating plug (if used), Lubricant, Threaded stud (if mating part not equipped), Ground wire (No. 14 AWG Copper equivalent or greater), Suitable ground connector, Waterproofing material for cable jacket, Tape marker, Inhibitor
- Perform Initial Safety Checks and Gather Materials
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Ensure all package contents are complete and undamaged. Verify all components fit properly with the cable and/or mating products. Have all required tools and supplies at hand and maintain cleanliness throughout the procedure.
- Prepare the Cable
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket (if applicable) and prepare the cable according to the specific type (e.g., Unishield, Jacketed, Non-Jacketed) and dimensions provided in the product documentation.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the lug. Measure the 'Check Dimension' before crimping; it should be less than 6-3/8 inches. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until the elbow cannot advance further. Ensure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Connect to the Mating Part (First End)
WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Secure the Elbow to the Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect the Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part. CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to the specified torque per instructions.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield
Insert one end of a ground wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device, or through an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test and Secure Cap
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter used. Test with a suitable sensing device designed for capacitive test points to determine if the cable is energized. Contamination, moisture, or incorrect equipment can give a false 'no voltage' indication; treat the elbow as energized until confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.