ABB Installation Products K151SP-C0270 15/25kV 200 Amp, Deadbreak Straight Plug, Bails are required, but not included, order…
UPC: 783786503858
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating for medium-voltage applications
- 200 Amp continuous current rating
- Accommodates cable insulation diameters from 0.805" to 1.060"
- Aluminum compression lug for secure conductor termination
- Supports AWG 4/0 (stranded compressed) to 250 kcmil (solid) conductors
Specifications
Amperage Rating | 200 A |
Application | Designed to Terminate UD Cable having Concentric Neutral and Extruded instalation shielding |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection Type | Deadbreak Straight Plug |
Current Rating | 200 A |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | True |
Length | 8.81 IN |
Material | Housing - EPDM-Rubber |
Material | Aluminum |
Series | K151SP |
Size | 0.805 inch to 1.060 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Plug |
Voltage Rating | 15/25 kV |
Voltage Rating | 15 to 25 kV |
Width | 2.55 IN |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 0.9600 L |
Package Weight (Metric) | 0.4360 kg |

656ETP-H0270-DRG-S
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. 200ECS Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
K151SR-C0250
15/25kV 200 Amp, Deadbreak Straight Receptacle, Bails are required, but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
167DLR-H5270
200 Amp, 15kV, Loadbreak Direct Test Elbow Connector, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or Solid 250 or mmSquared 26.67.
K151SP-C0250
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K151SR-C0230
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1 or Solid 1/0 or mmSquared 42.41.
K151SP-C0230
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.805 inch to 1.060 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
168RLR-F5220-5240
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size 220 - AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact. Conductor Size 240 AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.Frequently Asked Questions
What is the K151SP product?
The K151SP is a 15/25kV, 200 Amp Deadbreak Straight Plug. It features a fully shielded, submersible molded rubber housing made with 100% peroxide-cured EPDM materials.
Are bails included with the K151SP kit?
No, bails are ordered separately and are required for installation.
Is a ground wire connection available?
Yes, the K151SP has a provision for a ground wire connection.
What conductors are suitable for copper compression lugs?
Copper compression lugs are suitable only for all copper conductors.
What is the impulse withstand rating for 15kV class?
For the 15kV voltage class, the impulse withstand (BIL) is 95kV (1.2 x 50 microsecond wave).
What is the maximum operating voltage for 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV and phase-to-phase is 26.3kV.
Does the K151SP meet industry standards?
Yes, the K151SP meets ANSI/IEEE Standard 386, Latest Revision.
What is the maximum operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
What is the continuous current rating?
The continuous current rating for both 15kV and 25kV voltage classes is 200 Amps.
What Elastimold products mate with the K151SP?
The K151SP is designed to mate with the Elastimold K151T tee splice and the K151SR straight receptacle.
How to Install the K151SP Straight Plug for High Voltage Cable Connections
This guide provides detailed instructions for installing the K151SP Straight Plug, designed for connecting solid dielectric type cables to other ELASTIMOLD products or electrical apparatus on 15kV and 25kV class systems. Proper installation by trained personnel is crucial for safety and product integrity.
Estimated time: 1h
Tools needed:
Wire brush, Crimping tool (for socket terminal), Rag, Approved solvent
Supplies needed:
K151SP Straight Plug, Conductor Contact (female), Nylon Venting Rod, Pin Installation, Lubricant (supplied), Crimp Chart, Cable (solid dielectric type), Inhibitor (in crimp barrel), Plastic pin (temporary), Silicone grease, ELASTIMOLD bail (required for mating deadbreak products), Copper wire (#14 AWG or equivalent, if not using ELASTIMOLD grounding device)
- Ensure De-energized State and Personnel Competence
Before beginning installation, ensure all apparatus is de-energized. This product must only be installed by competent personnel trained in good safety practices involving high voltage electrical equipment. Failure to follow these instructions will result in damage to the product and serious or fatal injury.
- Prepare Cable Jacket (Concentric Neutral or Copper Tape Shield)
For jacketed concentric neutral cable, cut and remove the cable jacket 8 inches from the cable end, ensuring sufficient neutral wires for grounding. For copper tape shield cable, cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the cable end. Refer to specific ECS or MA grounding device instructions if applicable.
- Prepare Cable Insulation and Conductive Shield
Remove 7/8 inch to 1 inch (or 1-3/4 inches to 1-7/8 inches for #1 stranded/compr. and #1/0 compt./solid aluminum cable) of cable insulation and conductive shield. Cut squarely, do not pencil. Wire brush bare aluminum conductors immediately and insert into the crimp barrel containing inhibitor.
- Crimp Socket Terminal
Crimp the socket terminal onto the bared conductor, holding the crimp barrel against the cable insulation. Refer to the crimp chart provided with the contact. Start crimps at the imprinted crimp line and rotate each successive crimp or indent 90 degrees. Carefully wipe any excess inhibitor from the contact and cable insulation.
- Remove Semi-conductive Shield and Clean Insulation
Temporarily remove the plastic pin. Remove the semi-conductive shield 7-3/4 inches to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut, ensuring not to cut or nick the insulation. Replace the plastic pin. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation with an approved solvent, wiping from the cable end toward the outer jacket to remove all semi-conducting residue. If using an ECS or MA grounding device, install it now per its instructions.
- Lubricate Cable and Position Collar
Slide the collar, smaller end first, onto each cable. Refer to the bailing instruction sheet. Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable as shown and to the inside of the housing. Do not substitute lubricants, as others may be harmful.
- Install Cable into Housing
Push the cable into the housing until the leading edge of the socket contact is flush with the front edge of the plug. Remove the plastic pin from the socket and discard it.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches), taking care not to cut the rod. Insert the plug assembly into the receptacle as far as possible. Pull out the nylon rod. Secure the electrical connection using an ELASTIMOLD bail, referencing Bailing Instruction Sheet (150TB-4).
- Connect System Ground
If an ELASTIMOLD grounding device is not used, connect a length of #14 AWG or equivalent copper wire (customer supplied) through the grounding tab and twist tightly. Connect this grounding assembly to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.