ABB Installation Products K151SP-A2240 200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included…
UPC: 075114411196
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 200 Amp continuous current rating
- 15/25kV voltage rating for medium-voltage applications
- Accommodates cable insulation diameters 0.575" to 0.740"
- Copper compression lug for 1/0 or 2/0 AWG conductors
- Deadbreak design allows safe load-break disconnection
Specifications
Amperage Rating | 200 A |
Application | Designed to Terminate UD Cable having Concentric Neutral and Extruded installation shielding |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | Fully Shielded, Fully Submersible |
Insulation | EPDM Rubber |
Length | 8.81 in |
Length | 223.774 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for ground wire connection. Wide cable range with minimum number of sizes. No Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Straight Plug |
Voltage Rating | 15 to 25 kV |
Width | 2.55 in |
Width | 64.77 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-J0240-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. Cold-Shrinkable Jacket Seal Included.
262LRJS-E5250
25kV, 200 Amps, Loadbreak Elbow, Built in Jacket Seal, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Bi-Metal Conductor, Conductor Size 2/0 Stranded/Compressed, 3/0 Solid/Compact. With Test Point. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installation Instruction Sheet and Crimp Chart.
K655DLR-N0410-S
15/25kV, 600 Amp, Direct Test Elbow with Cold-Shrinkable Jacket Seal, DeadBreak, Cable Insulation 1.515-1.780 inches, Aluminum Compression Lug, Conductor Size 1000 Stranded/Compressed
K656SR-G2240-S
600 Amp, 15/25kV, 600 Series Straight Receptacle with cable adapter, lug and retaining ring. Cable Insulation Diameter 0.760 inch to 0.950 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 1/0 or Compacted Solid 2/0. S - Cold Shrinkable Jacket Seal.
756LR-QAC05
35kV, 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Shearbolt Lug and Cable Adapter). Tin-Plated Aluminum Shearbolt Lug. Cable Insulation Diameter 1.9 inch to 2.12 inch. Conductor Size Range for Compressed / Stranded / Compacted 1500 kcmil. 35 kV Only.
168RLR-J5260-SG3
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG Compressed Stranded 3/0 or Solid Compact 4/0. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring. Includes Elbow Connector Housing, Long Bi-Metal Compression Lug, Probe Wrench, Probe, Hose Clamp, Crimp Chart, Installation Instructions and Tube of Lubricant.
162LR-B2200
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, #2 Stranded Wire Size. Copper Compression Lug
CL 8222 K
Flood Seal, Direct Burial Service Cluster, Kit of Two Assemblies with Finished Cable Length of 12 inches. (Kit1 - CL 3104 and Kit2 - CL 40-2104). Kit1. CL 3104 - Boot plus (2) 1/0 STR AL Cables 15.487 x .965, (1) 1/0 STR AL Cable 15.487 x 1.5, (1) #4 STR AL Cable 15.487 x .765, (1) RRS 2010 - Radiating Rib, Aluminum Compression Splice, 2/0 to 1/0, Aluminum. 3.000 inch Long x Widest Diameter .812 inch. Center Stop. Gray Cap and Yellow Cap, Oxide Inhibiting Compound. Flood Seals assembled on 1/0 and #4 Wires. Kit2. CL 40-2104 - Boot plus (2) 1/0 STR AL Cables 15.487 x .965, (1) 4/0 STR AL Cable 15.487 x 2.05, (1) #4 STR AL Cable 15.487 x .965, RRS 40 - (attached to 4/0 Wire) Radiating Rib, Aluminum Compression Splice, 4/0, Aluminum. 4.300 inch long x .876 inch at widest Diameter. Center Stop. Pink Caps. Contains Oxide Inhibitor. Flood Seals assembled on 1/0 and #4 Wires.Frequently Asked Questions
What cable insulation diameters does this elbow support?
The K151SP-A2240 supports cable insulation diameters from 0.575 inch to 0.740 inch.
What conductor sizes are compatible with this elbow?
The elbow is compatible with 1/0 or 2/0 AWG compressed stranded or solid compact conductors (53.49 mm²).
What is the voltage rating of this deadbreak elbow?
The K151SP-A2240 has a voltage rating of 15/25kV.
What type of lug does this elbow use?
The elbow uses a copper compression lug for conductor termination.
Is a bail included with the K151SP-A2240?
No, bails are required for installation but must be ordered separately.
Can this elbow be used for load-break connections?
Yes, the deadbreak design allows for safe disconnection under load without interrupting service.
How to Install the K151SP Straight Plug Connector
This guide provides step-by-step instructions for installing the K151SP Straight Plug, designed for connecting solid dielectric type cables on 15kV and 25kV class systems. Ensure all safety precautions are followed for high voltage electrical equipment.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Crimp tool, Wire brush, Measuring tape, Rag
Supplies needed:
K151SP Straight Plug kit (includes plug, contact, nylon rod, lubricant), Solid dielectric type cable, Approved solvent, Silicone grease, Elastimold bail (for mating connection), #14 AWG copper wire (if not using Elastimold grounding device), Sealing material (for grounding wires)
- Prepare the Cable Jacket
DANGER: Ensure all apparatus is de-energized before starting. For jacketed concentric neutral cable, cut and remove the cable jacket 8 inches from the cable end, ensuring sufficient neutral wires for grounding. For copper tape shield cable, cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the cable end. If using an ECS or MA grounding device, follow its specific jacket cut-back instructions.
- Prepare Cable Insulation and Conductive Shield
Remove 7/8 inch to 1 inch of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid aluminum cable, remove 1-3/4 inches to 1-7/8 inches. Cut squarely, do not pencil. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel, which contains inhibitor.
- Crimp the Socket Terminal
Crimp the socket terminal onto the bared conductor, holding the crimp barrel against the cable insulation. Refer to the crimp chart provided with the contact. Start crimps at the imprinted crimp line and rotate each successive crimp or indent 90 degrees. Carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare for Plug Assembly
Temporarily remove the plastic pin. Remove the semi-conductive shield 7-3/4 inches to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut. WARNING: Do not cut or nick the insulation. Replace the plastic pin. Pencil the insulation 1/8 inch. Clean the outer jacket and thoroughly clean the insulation with an approved solvent, wiping from the cable end toward the outer jacket to remove all semi-conducting residue. If using an ECS or MA grounding device, install it now according to its instructions.
- Lubricate and Position Collar
Slide the collar, smaller end first, onto each cable. Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable and to the inside of the housing. WARNING: Do not substitute lubricants, as others may be harmful to the product or its mating part.
- Install Cable into Housing
Push the cable into the housing until the leading edge of the socket contact is flush with the front edge of the plug. Remove the plastic pin from the socket and discard it.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches). Exercise care to ensure the nylon rod is not cut during mating, which could leave material inside the interface. Insert the plug assembly into the receptacle as far as possible. Pull out and remove the nylon rod. Secure the electrical connection using an ELASTIMOLD bail, referencing the Bailing Instruction Sheet (150TB-4).
- Complete Grounding Connection
If an ELASTIMOLD grounding device is not being used, connect a length of customer-supplied #14 AWG or equivalent copper wire through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.