- 200 Amp, 15/25kV DeadBreak elbow configuration
- Functions as both a locking splice and a repair splice
- Bails are not required for locking splice applications
- Accommodates 4 inches of cable for repair splice applications
- Compatible with cable insulation diameters from 0.805" to 1.060"
Specifications
Amperage Rating | 200 A |
Application | Used where a new installation is required or to make repairs on existing cable installations |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Connection Type | DeadBreak elbow, Locking Splice/Repair Splice |
Current Rating | 200 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K151 |
Size | Cable Insulation Diameter 0.805 inch to 1.060 inch |
Special Features | Permanent Locking Apparatus, Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide Cured Construction includes Insulation and Conductive EPDM Materials |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Locking Splice |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

274AFLR1-D0220
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 15.5kV, Fuse Test Port - Two Direct Test Ports, Small Housing, Cable Insulation Diameter 0.890 inch - 1.220 inch / 25-31mm, Aluminum Conductor size 2 AWG Stranded Compressed, 1 AWG Solid/Compact.
K151LS-B2230
200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Cable Insulation Diameter 0.635 inch to 0.905 inch. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Includes a 01402X Copper Lug.
K151LS-B2220
200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Cable Insulation Diameter 0.635 inch to 0.905 inch. Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62. Includes a 01402X Copper Lug.
K151LS-B1250
15/25kV 200 Amp, Deadbreak Locking Splice / Repair Splice, Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K151LY-B0240
200 Amp, 15/25kV, DeadBreak elbow, Locking Y Splice, Bails are not required for Locking Splices, Cable Insulation Diameter 0.635 inch to 0.905 inch. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Includes a 01300X universal aluminum compression lug.
K676LR-F2290-SG3
900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656RLR-N0380
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.515 to 1.780 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 700/750 kcmil or Compacted Solid 900 kcmilFrequently Asked Questions
What is the primary application of the K151LS splice?
The K151LS provides a permanent, fully shielded, and fully submersible splice. It is used for new installations or repairs on existing cable installations up to 25kV.
What is the continuous current rating of the K151LS?
The K151LS has a continuous current rating of 200 Amps for both 15kV and 25kV voltage classes.
What are the insulation diameter ranges for 'W' codes A and D?
'W' code A covers 0.575 inches to 0.740 inches, and 'W' code D covers 0.890 inches to 1.220 inches.
What items are included in the K151LS kit?
Each kit contains a receptacle housing, splice pin connector, plug housing, splice socket connector, lubricant, installation instructions, and a crimp chart.
What industry standard does the K151LS meet?
The K151LS meets ANSI/IEEE Standard 386, Latest Revision.
What is the momentary current rating of the K151LS?
The momentary current rating for the K151LS is 10kA Symmetrical for 10 cycles.
What are the operating voltage limits for the 25kV class?
For the 25kV class, the maximum phase-to-ground operating voltage is 15.2kV, and the maximum phase-to-phase is 26.3kV.
What are the operating voltage limits for the 15kV class?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV, and the maximum phase-to-phase is 14.4kV.
Can the K151LS splice be installed underground?
Yes, the K151LS can be installed either directly buried or within a vault.
What pull force can the K151LS locking splice withstand?
The pin and socket interlock of the K151LS is designed to withstand pulls of up to 500 lbs.
How to Install the K151LSP Non-Separable Straight Plug
This guide provides detailed instructions for the safe installation of the K151LSP Non-Separable Straight Plug onto solid dielectric type cable and its connection to a mating K151LSR receptacle. Ensure all apparatus are de-energized before beginning installation to prevent serious or fatal injury.
Estimated time: 1h 30m
Tools needed:
Cable cutting tool, Wire strippers, Crimp tool (with appropriate dies), Wire brush, Rag, Approved solvent
Supplies needed:
Conductor Contact (female), Nylon Venting Rod, Lubricant (supplied with product), K151LSR Mating Receptacle, #14AWG or equivalent copper wire, Silicone grease, Sealing material, Solid dielectric type cable
- Prepare Cable Jacket and Shield
For Jacketed Concentric Neutral cable, cut and remove the cable jacket 8 inches from the cable end. Ensure sufficient concentric neutral wires are available for connecting to the ground point. For Copper Tape Shield cable, cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the end of the cable. If using an ECS or MA grounding device, follow its specific installation instructions for outer jacket cut back.
- Prepare Conductor Insulation
Remove 1-1/8 inches of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid or larger aluminum cable, remove 1-7/8 inches. Cut squarely; do not pencil the cut. Wire brush bare aluminum conductors immediately before proceeding to the next step.
- Crimp Socket Terminal
Immediately insert the bared conductor into the crimp barrel, ensuring the conductor remains fully seated in the connector. Crimp the socket terminal according to the crimp chart provided with the contact. Start the crimps at the crimp line imprinted on the crimp barrel and rotate each successive crimp or indent at least 90 degrees. When using aluminum cable, carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare Semi-Conductive Shield and Insulation
Temporarily remove the plastic pin. Remove the semi-conductive shield to a point 7-3/4 to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut. Do not cut or nick the insulation. Pencil the insulation 1/8 inch. Replace the plastic pin. Clean the outer jacket and thoroughly clean the insulation with a rag wet with an approved solvent, wiping from the end of the cable toward the outer jacket, to remove all traces of semi-conducting residue. If using an ECS or MA grounding device, install it now following its appropriate instructions.
- Lubricate Cable and Plug Housing
Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable as indicated in the product documentation and to the inside of the plug housing. Do not substitute lubricants, as other types may be harmful to this product or its mating product.
- Install Plug Assembly on Cable
Push the cable into the housing until the leading edge of the socket contact is flush with the front edge of the plug. Remove the plastic pin from the socket and discard it.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches), taking care to ensure the nylon rod is not cut while mating parts, which could leave material inside the interface. Insert the plug assembly into the receptacle as far as possible. When mating, the assembler will feel the contact assembly "CLICK" and lock into its final position.
- Verify Connection and Remove Nylon Rod
Verify the locking contact by pulling on the cables; do not pull the housing. If the parts separate, repeat steps 7B and 7C. Pull out and remove the nylon rod.
- Connect Grounding
If an ELASTIMOLD grounding device is not being used, connect a length of #14AWG or equivalent customer-supplied copper wire through the grounding tab and twist tightly as shown in the product diagram. Then, connect this grounding assembly to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.