Contact for Pricing
Overview
- 15/25kV Voltage Rating
- 200 Amp Continuous Current Rating
- Accommodates 0.635" to 0.905" Cable Insulation Diameter
- Aluminum Compression Lug for 2/0 AWG Stranded / 3/0 AWG Solid Conductors
- Deadbreak Locking Splice for Reliable Cable Repair and Termination
Specifications
Amperage Rating | 200 A |
Application | Used where a new installation is required or to make repairs on existing cable installations |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 9.54 in |
Length | 242.316 mm |
Material | Housing - EPDM-Rubber |
Special Features | Permanent Locking Apparatus, Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide Cured Construction includes Insulation and Conductive EPDM Materials |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Locking Splice |
Voltage Rating | 15 to 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.0100 L |
Package Weight (Metric) | 0.9120 kg |

168FLR3B0250
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Large Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Aluminum Conductor size 2/0 AWG Stranded/Compressed, 3/0 AWG Solid/Compact.
K151LY-B0240
200 Amp, 15/25kV, DeadBreak elbow, Locking Y Splice, Bails are not required for Locking Splices, Cable Insulation Diameter 0.635 inch to 0.905 inch. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Includes a 01300X universal aluminum compression lug.
K676LR-F2290-SG3
900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656RLR-N0380
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.515 to 1.780 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 700/750 kcmil or Compacted Solid 900 kcmil
K151LS-B0260
200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Cable Insulation Diameter 0.635 inch to 0.905 inch. Includes a 01400X universal aluminum compression lug.
K676LR-G2260
15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation .850-1.050 inches, Copper Compression Lug, Conductor Size 3/0 Stranded/Compressed or 4/0 Solid/Compact.
K656RLR-L0380
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.Frequently Asked Questions
What are the key features of the K151LS splice?
The K151LS locking splice is permanent, fully shielded, and fully submersible.
What is the maximum voltage rating for the K151LS?
The K151LS is designed for use up to 25kV.
What is the Basic Impulse Level for the 25kV class?
The Basic Impulse Level (BIL) for the 25kV voltage class is 125kV.
What is the maximum operating voltage for the 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 15.2kV and phase-to-phase is 26.3kV.
What is the Basic Impulse Level for the 15kV class?
The Basic Impulse Level (BIL) for the 15kV voltage class is 95kV.
What is the continuous current rating for K151LS?
The K151LS has a continuous current rating of 200 Amps for both 15kV and 25kV voltage classes.
What is the momentary current rating for K151LS?
The K151LS has a momentary current rating of 10kA Symmetrical for 10 cycles.
What is the maximum operating voltage for the 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV and phase-to-phase is 14.4kV.
What cable insulation diameters does K151LS accept?
The K151LS accepts cable insulation diameters ranging from 0.575 inches to 1.220 inches.
What is the momentary current rating for K151LS?
The K151LS has a momentary current rating of 10kA Symmetrical for 10 cycles.
How to Install the K151LSP Non-Separable Straight Plug
This guide provides step-by-step instructions for installing the K151LSP Non-Separable Straight Plug, including cable preparation, crimping, and connection to a mating K151LSR receptacle. Ensure all safety precautions are followed during installation.
Estimated time: 1h 30m
Tools needed:
Wire brush, Rag, Crimp tool (refer to crimp chart)
Supplies needed:
Conductor Contact (female), Nylon Venting Rod, Plastic Pin, Lubricant, Approved solvent, Silicone grease, #14AWG or equivalent copper wire
- Perform Pre-installation Safety Checks
DANGER: All apparatus must be de-energized during installation or removal of parts. Ensure all components are checked for damage, proper rating, and compatibility with mating parts. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices. Have all required tools and supplies at hand and maintain cleanliness throughout the procedure.
- Prepare the Cable Jacket
For Jacketed Concentric Neutral cable, cut and remove the cable jacket 8 inches from the cable end, allowing sufficient concentric neutral wires for grounding. For Copper Tape Shield cable, cut and remove the cable jacket 7-1/2 inches from the cable end, then remove the copper tape shield 6-1/2 inches from the cable end. If using an ECS or MA grounding device, follow its specific jacket cut-back instructions.
- Prepare Cable Insulation and Conductor
Remove 1-1/8 inches of cable insulation and conductive shield. For #1 stranded/compressed and #1/0 compressed/solid or larger aluminum cable, remove 1-7/8 inches. Cut squarely, do not pencil. Wire brush bare aluminum conductors and immediately insert them into the crimp barrel.
- Crimp the Socket Terminal
Crimp the socket terminal onto the bared conductor, ensuring the conductor remains fully seated in the connector. Refer to the crimp chart provided with the contact. Start crimps at the crimp line imprinted on the barrel and rotate each successive crimp or indent at least 90 degrees. If using aluminum cable, carefully wipe any excess inhibitor from the contact and cable insulation.
- Prepare Semi-Conductive Shield and Insulation
Temporarily remove the plastic pin. Remove the semi-conductive shield to a point 7-3/4 inches to 7-13/16 inches back from the end of the socket with a straight, smooth, squared cut. DO NOT CUT OR NICK THE INSULATION. Pencil the insulation 1/8 inch. Replace the plastic pin. Clean the outer jacket and thoroughly clean the insulation with a rag wet with an approved solvent, wiping from the end of the cable toward the outer jacket. If using an ECS or MA grounding device, install it now.
- Lubricate Cable and Housing
Keep the cable insulation and plug clean. Apply the supplied lubricant sparingly to the cable as shown and to the inside of the housing. DO NOT SUBSTITUTE other lubricants, as they may be harmful to this product or its mating product.
- Install Plug onto Cable
Push the cable into the housing until the leading edge of the socket contact is flush with the front edge of the plug. Remove the plastic pin from the socket and discard it.
- Connect to Mating Receptacle
Lubricate the nose of the plug with silicone grease. Place the nylon rod into the receptacle face until it bottoms (approximately 1-3/4 inches), taking care not to cut the rod. Insert the plug assembly into the receptacle as far as possible until you feel the contact assembly 'CLICK' and lock into its final position.
- Verify Connection and Remove Nylon Rod
Verify the locking contact by pulling on the cables; DO NOT PULL THE HOUSING. If the parts separate, repeat steps 8B and 8C. Once verified, pull out the nylon rod.
- Ground the Connector
If an ELASTIMOLD grounding device is not being used, connect a length of #14AWG or equivalent customer-supplied copper wire through the grounding tab and twist tightly. Connect the grounding assembly of the connector to the system ground by merging it with the cable shield of each cable. Seal the grounding wires and connections to prevent corrosion.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.