Authorized ABB Distributor (Installation Products)
ABB - Installation Products K656RLR-N0380 - 600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.515 to 1.780 inch. Aluminum Compression Lug. Conductor Size Compressed Stranded 700/750 kcmil or Compacted Solid 900 kcmil

ABB Installation Products K656RLR-N0380 600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable…

UPC: 075114242851


Documents & Media
Installation InstructionsManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 600 Series Deadbreak Replacement Elbow, SKU K656RLR-N0380, is engineered for reliable 15/25kV applications with a 600 Amp rating. This replacement elbow is designed to fit cable insulation diameters ranging from 1.515 to 1.780 inches, ensuring compatibility with a defined range of medium-voltage cables. It features an integrated test point for convenient and safe testing procedures, a critical aspect of maintaining system integrity and operational readiness. The elbow is equipped with an aluminum compression lug, specifically sized for compressed stranded conductors of 700/750 kcmil or compacted solid conductors of 900 kcmil. This precise conductor sizing ensures a secure and efficient electrical connection, minimizing resistance and heat buildup. Manufactured by ABB - Installation Products, this component is built to meet the demanding requirements of electrical distribution and transmission systems. Its deadbreak design provides a fully shielded, submersible, and separable connection, offering a high level of safety and performance in various environmental conditions. The inclusion of a test point simplifies diagnostic and maintenance routines, allowing for voltage checks without de-energizing the entire circuit, thereby enhancing operational efficiency and reducing downtime.
  • 600 Amp, 15/25kV operating voltage
  • 600 Series Deadbreak design
  • Integrated test point for diagnostics
  • Accommodates cable insulation diameters from 1.515 to 1.780 inches
  • Aluminum compression lug for 700/750 kcmil stranded or 900 kcmil compacted solid conductors

Specifications

Amperage Rating
600 A
Application
Used where Cable has been severed and is not long enough to reach the Elbow
Color
Black
Conductor Range
700 to 750 kcmil , 900 kcmil
Connection
Compression
Environmental Conditions
All Weather Conditions
Insulation
True
Length
31.56 in
Length
801.624 mm
Material
Housing - EPDM-Rubber
Special Features
Fully Shielded, Fully Submersible Molded Rubber Housing, 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Rubber. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Non-Corrosive Capacitive Test Point
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Replacement Elbow Connector with Test Point
Voltage Rating
15 to 25 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

K656CY-L0380

15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Cable Insulation Diameter 0.635 inch to 0.905 inch. Includes a 01400X universal aluminum compression lug.

K151LS-B0260

200 Amp, 15/25kV, DeadBreak elbow, Locking Splice/Repair Splice, Bails are not required for Locking Splices, When used as a repair splice, the assembled length allows 4 inches for cable replacement/repair. Cable Insulation Diameter 0.635 inch to 0.905 inch. Includes a 01400X universal aluminum compression lug.
15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation .850-1.050 inches, Copper Compression Lug, Conductor Size 3/0 Stranded/Compressed or 4/0 Solid/Compact.

K676LR-G2260

15/25kV, 900 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation .850-1.050 inches, Copper Compression Lug, Conductor Size 3/0 Stranded/Compressed or 4/0 Solid/Compact.
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.

K656RLR-L0380

600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
900 Amp, Elbow Connector, with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, 15/25KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size Compressed Stranded 500 kcmil or Compacted Solid 600 kcmil.

K676LR-L2330

900 Amp, Elbow Connector, with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, 15/25KV, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Compression Lug. Conductor Size Compressed Stranded 500 kcmil or Compacted Solid 600 kcmil.
600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.

K656RLR-M0410

600 Amp, 15/25kV, 600 Series Deadbreak, Replacement Elbow with Test Point, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.

K676LR-F2240-SG3

900 Amp, 15/25kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
200 Amp, 15/25kV, DeadBreak elbow, Locking Y Splice, Bails are not required for Locking Splices, Cable Insulation Diameter 0.805 inch to 1.060 inch. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. Includes an aluminum compression lug.

K151LY-C1270

200 Amp, 15/25kV, DeadBreak elbow, Locking Y Splice, Bails are not required for Locking Splices, Cable Insulation Diameter 0.805 inch to 1.060 inch. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. Includes an aluminum compression lug.

Frequently Asked Questions

What is the maximum cable insulation diameter for this elbow?

This ABB deadbreak elbow is designed to fit cable insulation diameters ranging from 1.515 to 1.780 inches.

What conductor sizes are compatible with this replacement elbow?

The elbow is compatible with compressed stranded conductors of 700/750 kcmil or compacted solid conductors of 900 kcmil.

What is the voltage rating of the K656RLR-N0380 elbow?

The ABB K656RLR-N0380 deadbreak elbow is rated for 15/25kV applications.

Does this elbow have a test point?

Yes, the K656RLR-N0380 features an integrated test point for convenient testing.

What type of lug is included with this deadbreak elbow?

This replacement elbow comes with an aluminum compression lug.

How to Install the K655RLR High Voltage Connector

This guide provides detailed instructions for installing the K655RLR connector, designed for fully shielded connections to high voltage apparatus up to 28kV class systems. It covers assembly, cable preparation, and final connection.

Estimated time: 1h 30m

Tools needed:

Hex wrench (supplied), Torque wrench (with 9/16" socket), Wire brush (for aluminum cable), Wire strippers, Rag, Approved safety solvent, Assembly tool (650ATY or 600RRT), Hotstick, Suitable sensing device

Supplies needed:

K655RLR connector kit (Elbow, Cable Adapter, Compression Connector, Insulating Plug, Receptacle, Test Point Cap, "I" Adapter, Bolt & Washer Prepack, Retaining Ring, Lubricant, Crimp Chart), Cable, Mating apparatus/bushing, Semi-con sleeve (if needed), Electrical tape, No. 14 AWG copper wire (or equivalent), Suitable wire connectors, Silicone grease, Nylon venting rod (supplied)

  1. Prepare for Installation and Safety Check

    DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products. This product must be installed only by competent personnel trained in high voltage electrical equipment safety. Check the package contents for completeness and damage. Inspect all components for proper fit with the cable and/or mating products. Gather all required tools and maintain cleanliness throughout the procedure.

  2. Assemble "I" Adapter into Elbow

    Remove protective caps from the elbow. Clean and lubricate the "I" adapter and the inside of the elbow with the supplied lubricant; do not substitute. Assemble the "I" adapter into the elbow until the spade contact bottoms inside. Ensure the flat side of the "I" contact faces away from the apparatus.

  3. Prepare and Connect Elbow to Mating Part

    Remove protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud (supplied with the elbow) into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. Position the elbow so the flat side of the "I" contact faces away from the apparatus. Push the elbow onto the mating part, aligning the hole in the "I" adapter lug with the stud on the mating part.

  4. Connect Mating Part to Opposite End of Elbow

    Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions. If an insulating plug is used, clean and lubricate the inner surface of the voltage detection cap, then place it on the elbow, pushing down hard until it snaps into place.

  5. Prepare Cable for Receptacle Housing

    Slide the receptacle housing onto the cable. Holding the cable in place, cut the cable 1 3/4" from the center of the bolt hole in the "I" adapter. Remove the semi-con shield 11 1/8" from the center of the bolt hole in the adapter; if the shield dimension exceeds this, restore it with a semi-con sleeve (not supplied). At 1" from the end of the semi-con shield, wrap two turns of tape as a marker. Bevel the end of the insulation at a 45-degree angle approximately 1/4" back.

  6. Clean Cable Insulation and Install Cable Adapter

    Thoroughly clean the insulation to remove all traces of semi-conducting residue by wiping with a rag soaked in an approved safety solvent, always wiping from the end of the cable toward the outer jacket. Apply supplied lubricant sparingly along the cable. Lubricate the inside of the cable adapter. Slide the adapter, small end first, over the cable with a twisting motion until its end is flush with the tape marker.

  7. Trim Cable Insulation and Secure Retaining Ring

    Remove the protruding cable insulation by cutting it even with the end of the cable adapter, being careful not to cut or nick the adapter or conductor. Verify the exposed conductor length is between 4 3/16" to 5 1/8"; if not, redo the assembly. Assemble the aluminum retaining ring over the conductor and snug it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw until the wrench twists. As a check, measure the exposed conductor; it should be in the range of 4 5/16" to 4 7/8".

  8. Prepare and Pre-check Compression Connector

    Remove the protective cap from the compression connector. If using aluminum cable, wire brush the conductor and immediately insert it into the crimp connector (which contains inhibitor), ensuring it's fully inserted into the crimp barrel. As a final check, bolt the crimp connector onto the "I" Adapter and tighten to 25 ft/lbs. Position all components on all cables as shown. Properly train the cable into its final position and mark the alignment points on the retaining ring and the outside surface of the crimp connector.

  9. Crimp Connector and Final Bolt Assembly

    Remove the bolted contact from the "I" Adapter. Align the marks on the retaining ring and the crimp connector to confirm proper orientation. Crimp the connectors following their packaged instructions, rotating each crimp 90 or 180 degrees. After crimping, measure the distance from the end of the connector to the holding collar; if over 7 1/8", do not proceed and recheck all previous work. Ensure the flat surface of the "I" Adapter aligns with the flat surface on the crimp connector with no gaps. Assemble the washers and bolt: flat washer against the spade contact, then the Belleville washer (concave side down), then the hex-head bolt. Hand tighten the bolt. Using a torque wrench with a 9/16" socket, tighten the bolt to 50 to 60 ft-lbs. Do not move or reposition any part of the assembly after the bolt is tightened.

  10. Lubricate Adapters and Slide Receptacle Housing

    Clean and lubricate the outside of the cable adapter and the "I" adapter with the supplied lubricant. Slide the receptacle housing over the cable adapter and up to the position shown. Insert the nylon venting rod (supplied).

  11. Use Assembly Tool and Seat Receptacle

    Attach the appropriate assembly tool (650ATY or 600RRT) as shown in its instructions. For 650ATY, ensure the "U" yoke is over the "I" Adapter and the "C" yoke over the receptacle housing, then slowly raise the handle to slide the housing. For 600RRT, place the tool as shown and turn the hex nut to slide the housing (WARNING: Do not place hand on threaded rod or guide shaft). Remove the vent rod. Remove the assembly tool. Rotate the receptacle approximately 1/8" clockwise then 1/8" counterclockwise by hand to ensure it is seated.

  12. Ground Concentric Neutral Cable

    Connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly without damage. Gather concentric neutral wires and connect them together with the grounding wires using suitable connectors. The metallic shield of the cable must be grounded using standard utility practices. If the cable is jacketed, waterproof the jacket at this point to prevent moisture entry.

  13. Perform Voltage Test (Verification)

    Remove the test point cap with a hotstick, peeling it off at an angle. Using a suitable sensing device, determine if the circuit is energized. DO NOT USE CONVENTIONAL VOLTAGE MEASURING EQUIPMENT. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Contamination or incorrect measuring equipment can provide a false "no voltage" indication. Treat the elbow as energized until the "no voltage" indication is confirmed by other means to prevent serious or fatal injury. After voltage detection, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.