ABB Installation Products 776LR-J5240-S 900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786390663
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 900 Amp continuous current rating for medium voltage applications
- Cold-shrinkable jacket seal for environmentally resistant connections
- Bi-metal compression lug compatible with 1/0 AWG to 2/0 kcmil conductors
- Non-corrosive capacitive test point for safe voltage verification
- Bi-metal compression lug for 1/0 AWG (compressed stranded) to 2/0 kcmil (compacted solid) conductors
Specifications
Amperage Rating | 900 A |
Application | 35 kV, 900 Amps |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Compression |
Connection Type | Elbow with Test Point, Insulated Plug, Cap, Stud, Lug and Cable Adapter |
Connection Type | Compression Lug |
Current Rating | 900 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal Compression Lug, Cold-Shrinkable Jacket Seal |
Material | Bi-Metal, Cold-Shrinkable |
Series | 600 Series |
Series | 600 Series Elbow |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Size | Cable Insulation Diameter 0.980" - 1.180" |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. S - Cold Shrinkable Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 9.6400 L |
Package Weight (Metric) | 4.3730 kg |

375LR-H5240
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
776LR-P2380-SG3
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included. Cable Insulation Diameter 1.725 inch to 1.935 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-N0350
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 600 /Compacted Solid 600.
776LR-P5410-S
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.725 inch to 1.935 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000. Cold-Shrinkable Jacket Seal Included.
775LR-J2230
900 Amp, 35kV, 600 Series Elbow with insulated plug, cap, stud, lug and cable adapter. Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
756LR-Q0400-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.900 inch to 2.120 inch. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500. Cold-Shrinkable Jacket Seal Included.
756LR-P0400-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.725 inch to 1.935 inch. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500. Cold-Shrinkable Jacket Seal Included.
776LR-N2330
900 Amp, 35kV, 600 Series Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 1.515 inch to 1.780 inch. Copper Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300.Frequently Asked Questions
What is the 776LR's primary application?
The 776LR provides fully shielded, dead-front submersible cable connections for high-voltage apparatus.
What are the operating voltage limits?
The maximum phase-to-ground operating voltage is 21.1kV, and the maximum phase-to-phase voltage is 36.6kV.
Is the housing submersible?
Yes, the 776LR features a fully shielded, fully submersible molded rubber housing.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 cycles.
What is the continuous current rating?
The continuous current rating for the 776LR is 900 Amps.
What are the withstand voltage ratings?
The 776LR has a 150kV BIL impulse withstand, 50kV AC one-minute withstand, and 103kV DC 15-minute withstand.
What standard does the 776LR meet?
The 776LR meets ANSI/IEEE Standard 386, Latest Revision.
What products are compatible with the 776BLR?
The 776BLR can be mated with Elastimold products like 775CP, 775BIP, 775ETP, 775SOP, 775S1, 775J2, 775J3, and 775J4.
What cable insulation diameters are supported?
Supported cable insulation diameters range from 0.760 in to 2.120 in.
What conductor sizes are compatible?
It is compatible with #2 AWG to 1250 kcmil aluminum and copper conductors.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for installing 755/775LR Deadbreak Elbow Connectors, designed for fully shielded, submersible deadfront cable connections on 35kV class systems.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools (strippers, knives), Wire brush, Crimping tool, Torque wrench, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
755/775LR Deadbreak Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), No. 14 AWG Copper wire (or equivalent ampacity), Suitable grounding connector, Silicone lubricant, Waterproofing material for cable jacket
- Prepare for Installation and Safety Check
DANGER: Ensure all apparatus is de-energized during installation or removal. Do not touch or move energized products in the work area. Inspect all parts (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack) for damage, correct rating, and compatibility with mating parts. Verify all required tools and supplies are at hand and maintain cleanliness throughout the procedure.
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. If using concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24” (610mm) from the cut end.
- Prepare Cable End
Refer to the specific cable type (e.g., non-jacketed concentric neutral, jacketed shield wires, etc.) and the provided diagrams. Remove the outer jacket (if applicable) and prepare the cable end, ensuring the cable insulation, semi-con shield, and tape marker are cut to the specified lengths (e.g., 10-3/8”, 11-3/8”, 13-5/8” from the end) as detailed in the diagrams.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor Length
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Avoid cutting or nicking the cable adapter or the conductor. Verify the length of the exposed conductor is between 4-3/8” to 4-3/4” (111mm-121mm). If not, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the “Check Dimension” before crimping; it must be less than 7” (178mm). If not, redo the assembly. Crimp the compression lug according to the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-7/8” to 7-5/8” (175mm-194mm). If not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Connect Elbow to Mating Part
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. If the mating part lacks a stud, hand tighten the threaded stud (supplied with the elbow) into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Connect Opposite End of Elbow (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert the mating part into the elbow, engage the threads, and hand tighten. CAUTION: Torque the mating part to the specified value according to the instructions supplied with the plug connectors.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper wire (or equivalent) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. Ground the cable shield according to the instructions supplied with the grounding device, or via an alternate method if no device is used. Waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points and follow its manufacturer's directions. Contamination or incorrect equipment can give a false "no voltage" indication. Treat the elbow as energized until the "no voltage" test point indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.