ABB Installation Products 756LR-L2240-SG3 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 075114177238
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV 600 Series Deadbreak Elbow
- Integrated Test Point with Insulated Plug and Cap
- Copper Compression Lug for 1/0 AWG Stranded / 2/0 AWG Solid Conductors
- Accommodates Cable Insulation Diameter: 1.180" - 1.465"
- Cold Shrinkable Seal with Copper Braid and Constant Force Spring
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. SG3 Sealing Kit - Cold Shrinkable Seal with Copper Braid and Constant Force Spring |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

375LR-H5240
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
756LR-J0240
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
756LR-J0250
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 2/0 /Compacted Solid 3/0 /mmSquared Compact 70.
756LR-M0270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-K0240-S
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Cold-Shrinkable Jacket Seal Included.
756LR-M0270-S
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold-Shrinkable Jacket Seal Included.
756LR-H0240
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
756LR-L0290
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.Frequently Asked Questions
What is the maximum operating voltage for this deadbreak elbow?
The ABB 756LR-L2240-SG3 is rated for 35kV operation.
What conductor sizes can this elbow accommodate?
It is designed for 1/0 AWG compressed stranded or 2/0 AWG compacted solid conductors.
What is the range for cable insulation diameter?
The cable insulation diameter range for this elbow is 1.180 inches to 1.465 inches.
Does this deadbreak elbow include a test point?
Yes, this model features a test point with an insulated plug and cap.
What type of lug is included with this elbow?
This deadbreak elbow comes with a copper compression lug.
What type of sealing mechanism is used?
It utilizes a cold shrinkable seal for installation.
Are a copper braid and spring included?
Yes, a copper braid and constant force spring are included with this elbow.
How to Install 756/776LR Deadbreak Elbow Connectors
This guide provides comprehensive instructions for the safe and proper installation of 756/776LR Deadbreak Elbow Connectors, designed for fully shielded, submersible cable connections on 35kV class systems.
Estimated time: 2h
Tools needed:
Cable cutter, Wire strippers, Utility knife, Wire brush, Crimping tool, Hotstick, Voltage sensing device
Supplies needed:
756/776LR Elbow Connector kit, HV insulated caps (if needed), No. 14 AWG Copper wire (or equivalent), Suitable grounding connector, Waterproofing material, Silicone lubricant
- Ensure Safety and Inspect Components
DANGER: De-energize all apparatus in the work area before beginning installation. Do not touch or move energized products. Inspect all parts of the 756/776LR connector kit for completeness, damage, proper rating, and compatibility with mating parts. If supplied with shipping covers, remove them and replace with appropriate HV insulated caps or connectors before energizing or submerging.
- Position and Cut Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable precisely 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end to ensure a clean working surface.
- Prepare Cable Insulation and Shield
Follow the specific instructions for your cable type (UNISHIELD, LEAD SHEATH, Jacketed, or Non-Jacketed) to remove the outer jacket and prepare the cable insulation and semi-con shield to the specified dimensions (e.g., 10-3/8", 11-3/8", 13-5/8" tape markers). Refer to the detailed diagrams in the product documentation for precise measurements.
- Bevel and Lubricate Cable Insulation
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean the cable insulation, then lubricate it, always working towards the semi-con shield.
- Install Cable Adapter
Install the cable adapter, small end first, onto the lubricated cable insulation. Push it until it is flush with the edge of the tape marker previously applied during cable preparation.
- Expose Conductor
Carefully remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm); if not, redo the assembly.
- Install Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it. Measure the 'Check Dimension' before crimping (must be less than 7 inches/178mm). Crimp the lug according to its supplied instructions. Wipe off excess inhibitor. After crimping, the distance from the lug end to the cable adapter must be 6-7/8 inches to 7-5/8 inches (175mm-194mm); if not, redo.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter, pushing until it cannot advance further. Verify the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare and Connect Mating Product
DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it lacks one. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part, aligning the compression lug hole with the stud.
- Connect Second Mating Product (If Applicable)
If connecting a second mating part (e.g., for splicing or tapping), clean and lubricate its mating surface. Insert this mating part into the opposite end of the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug (If Used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of its voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place. CAUTION: The insulating plug provides a means for detecting system voltage; follow voltage test directions.
- Ground Cable Shield and Waterproof
Insert one end of a No. 14 AWG Copper wire (or equivalent) through the grounding eye, twist to form a small loop, and connect it to ground using a suitable connector. Ensure the cable shield is grounded, either via a grounding device or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the cap's inner surface with silicone lubricant and replace it.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.