ABB Installation Products 756LR-M0270-S 35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and…
UPC: 783786408702
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating with 600A continuous current capacity
- Fully shielded, submersible molded rubber housing for reliable performance
- Integrated test point for safe voltage verification and fault detection
- Cold-shrinkable jacket seal for moisture-resistant cable termination
- Compatible with 1.370-1.630" cable insulation and 4/0-250 kcmil conductors
Specifications
Amperage Rating | 600 A |
Application | 35 kv, 600 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Connection Type | Compression Lug |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.370 inch to 1.630 inch |
Special Features | 35kV, 600 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. S - Cold-Shrinkable Jacket Seal |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Width | 12.28 in |
Width | 311.912 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.9000 L |
Package Weight (Metric) | 4.0370 kg |

755LRTP-L0270-DRG
600 Amp, 35kV, Stick-Op Connector Kit with Test Point, Insulated Cap and Reducing Tap Plug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
756LR-H0240
600 Amp, 35KV, DeadBreak, Elbow with Test Point, with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
756LR-L0290
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 300 /Compacted Solid 350 /mmSquared Compact 150.
756LR-L0280
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300.
756LR-L2270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Copper Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
756LR-M0280
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 250 /Compacted Solid 300.
756LR-L0320
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550.Frequently Asked Questions
What is the primary application of the 756LR?
It provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What AC withstand voltage does the product meet?
It meets a 50kV AC one-minute withstand voltage.
How is the elbow connected or disconnected?
It can be connected or disconnected using standard hand tools and equipment in a de-energized state.
Is the 756LR elbow submersible?
Yes, it features a fully shielded, fully submersible molded rubber housing.
Which industry standard does the product meet?
The product meets ANSI/IEEE Standard 386, Latest Revision.
What is the momentary current rating?
The momentary current rating is 25kA Symmetrical for 10 cycles.
What DC withstand voltage does the product meet?
It meets a 103kV DC 15-minute withstand voltage.
What is the impulse withstand rating (BIL)?
The impulse withstand (BIL) rating is 150kV (1.2 x 50 microsecond wave).
What is the continuous current rating of the elbow?
The continuous current rating for the elbow is 600 Amps.
What is the maximum phase-to-ground operating voltage?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
How to Install 756LR/776LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 756LR and 776LR Deadbreak Elbow Connectors on 35kV class systems, including cable preparation, crimping, and connection to mating apparatus.
Estimated time: 1h 30m
Tools needed:
Cable cutter, Wire strippers, Crimping tool, Wire brush (for aluminum conductors), Torque wrench, Hotstick, Capacitive voltage sensing device, Cleaning cloths
Supplies needed:
756LR/776LR Deadbreak Elbow Connector kit (includes elbow, cable adapter, compression lug, lubricant, threaded stud), Insulating plug (if used), No. 14 AWG copper wire (or equivalent), Suitable ground connector, Silicone lubricant
- Ensure De-energized State and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all components of the 756LR/776LR kit for damage, proper rating, and compatibility with mating parts. Ensure all required tools and supplies are at hand and maintain cleanliness throughout the procedure.
- Position and Prepare Cable
Position the cable in its final assembled location, ensuring enough slack for elbow removal. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer jacket of the cable for a distance of 24 inches (610mm). Prepare the cable by removing the outer jacket (if applicable) and other layers according to the specific cable type (e.g., non-jacketed concentric neutral, jacketed shield wires) and the precise dimensions provided in the documentation.
- Install Cable Adapter and Prepare Conductor
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker. Carefully remove the protruding cable insulation by cutting it even with the end of the cable adapter, taking care not to cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-3/8 inches to 4-3/4 inches (111mm-121mm); otherwise, redo this assembly step.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it must be less than 7 inches (178mm). Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-7/8 inches to 7-5/8 inches (175mm-194mm); otherwise, redo this assembly step.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Connect Elbow to Mating Apparatus
WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean. Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite End and Torque Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the specific instructions supplied with that mating part.
- Install Insulating Plug (Optional) and Ground Cable Shield
If an insulating plug is used as a mating part, clean and lubricate the inner surface of its voltage detection cap and place it on the elbow, pushing down hard until it snaps into place. CAUTION: The insulating plug provides a means for detecting system voltage; follow voltage test directions if applicable. Ground the cable shield: Insert one end of a No. 14 AWG copper wire (or equivalent ampacity) through the grounding eye and twist to make a small loop without damaging the eye. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded according to the instructions supplied with any grounding device, or via an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Optional)
CAUTION: When constructing 600amp L-Kits, tighten each component to specified torque per instructions provided with plug connectors. If the connector is equipped with an integral capacitance test point, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Treat the elbow as energized until a 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.