ABB Installation Products 755LR-N0400 600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable…
UPC: 783786368761
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 35KV rating for high-voltage applications
- Includes insulated elbow, plug, cap, stud, lug, and cable adapter
- Accommodates cable insulation diameters from 1.515" to 1.780"
- Aluminum compression lug for secure conductor termination
- Supports stranded conductors up to 900 kcmil, compacted solid up to 1000 kcmil, and mm² compacted up to 500 mm²
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 900 kcmil , 1000 kcmil |
Connection Type | Elbow Connector |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.515 inch to 1.780 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Voltage Rating | 35kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 8.8900 L |
Package Weight (Metric) | 4.0330 kg |

755LR-Q0400
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.900 inch to 2.120 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500.
167RLR-G-5220
200 Amp, 15kV, Loadbreak Replacement Elbow Connector without Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #2/Solid #1/mmSquared 33.62. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
376LR-J5250-S
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS Jacket Seal Included.
168ELR-88110-5260
200 Amp, 15kV, Loadbreak Repair Elbow Connector with Test Point, Cable Insulation Diameter 0.880 inch to 1.100 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
168RLR-H5240
15kV 200 Amp, Loadbreak Replacement Elbow Connector with Test Point. Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
755LR-N0330-S
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
755LR-J0310
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 400 /Compacted Solid 450 /mmSquared Compact 240.Frequently Asked Questions
What is the primary application of the 755LR elbow connector?
The 755LR elbow connector provides fully shielded, dead-front submersible cable connections to high-voltage apparatus.
What is the impulse withstand rating (BIL) for the 755LR?
The 755LR has a 150kV BIL impulse withstand rating (1.2 x 50 microsecond wave).
What materials are used in the 755LR's construction?
The 755LR features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
How is the 755LR connected or disconnected?
The 755LR can be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
Is the 755LR elbow connector submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
What is the corona extinction voltage for the 755LR?
The corona extinction voltage for the 755LR is 26kV AC at 3pC sensitivity.
What AC withstand voltage can the 755LR handle for one minute?
The 755LR can withstand 50kV AC for one minute.
What is the continuous current rating of the 755LR?
The 755LR has a continuous current rating of 600 Amps.
What is the maximum operating phase-to-ground voltage?
The maximum phase-to-ground operating voltage for the 35kV class is 21.1kV.
What insulation diameters does the 755LR support?
The 755LR supports insulation diameters ranging from 0.760 inches to 2.120 inches.
How to Install 755LR/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 755LR and 775LR deadbreak elbow connectors, designed for fully shielded, submersible high voltage cable connections on 35kV class systems.
Estimated time: 1h 30m
Tools needed:
Cable preparation tools, Crimping tool, Wire brush, Torque wrench, Hotstick, Suitable sensing device for capacitive test points
Supplies needed:
755LR or 775LR Elbow, Cable Adapter, Compression Lug, Insulating Plug (if applicable), Lubricant, Stud Prepack (threaded stud), No. 14 AWG Copper wire (or equivalent for grounding), Suitable grounding connector, Waterproofing material (for cable jacket), Mating part/Apparatus Bushing, Silicone lubricant
- De-energize and Inspect Components
DANGER: Ensure all apparatus in the work area are de-energized before starting installation. Verify the package contents are complete and undamaged, and all components fit properly with the cable and mating products.
- Position and Cut Cable
Position the cable so it is located in its final assembled position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24 inches (610mm) from the cut end.
- Prepare Cable for Termination
Remove the outer jacket (where applicable) and prepare the cable insulation, semi-con shield, and tape marker according to the specific cable type and dimensions provided in the full installation instructions.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Carefully remove the protruding cable insulation, cutting it even with the end of the cable adapter. Ensure the exposed conductor length is between 4-3/8 inches (111mm) and 4-3/4 inches (121mm). Do not cut or nick the cable adapter or conductor.
- Crimp Compression Lug
For aluminum conductors, wire brush the conductor immediately before insertion. Fully insert the conductor into the compression lug. Measure the 'Check Dimension' (must be less than 7 inches/178mm). Crimp the lug following its specific instructions. Wipe all excess inhibitor from the lug and cable adapter surface. Verify the post-crimp distance from the lug end to the cable adapter is 6-7/8 to 7-5/8 inches (175-194mm).
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Confirm the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products for Connection
DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite End of Elbow
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, hand tighten, and then torque it according to the instructions provided with that specific mating part.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down firmly until it snaps into place.
- Ground the Cable Shield
Insert one end of a No. 14 AWG Copper wire (or equivalent) through the grounding eye and twist to form a small loop. Connect this wire to ground using a suitable connector. Ensure the cable shield is grounded as per grounding device instructions or an alternate method. Waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test
Remove the test point cap using a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Test with a suitable sensing device designed for capacitive test points to determine if the circuit is energized. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point. Treat the elbow as energized until 'no voltage' is confirmed by other means.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.