ABB Installation Products 755LR-J0230 600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable…
UPC: 783786361663
Contact for Pricing
Call (262) 252-1600 or email [email protected] for pricing and availability.
Overview
- 600 Amp, 35kV Deadbreak Elbow Kit
- Accommodates cable insulation diameters: 0.980" - 1.180"
- Includes insulated plug, cap, stud, lug, and cable adapter
- Aluminum compression lug for AWG/kcmil #1/0 or 50 mm² conductors
- Manufacturer: ABB - Installation Products, SKU: 755LR-J0230
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | #1 STR/COMPR AWG , 1/0 SOL/COMPT AWG |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 9.0000 L |
Package Weight (Metric) | 4.0820 kg |

755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
755LR-J0260
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
755LR-H0270-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. 200ECS Cold-Shrinkable Jacket Seal Included.
755LR-H0250
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 or Solid 3/0 or mmSquared 70.
376LRJ-5240-SG3
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. 200ECS-G3 Jacket Seal and Grounding Kit Included.
755LR-G0240-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. 200ECS Cold-Shrinkable Jacket Seal Included.
161LR-B5230
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.Frequently Asked Questions
What is the momentary current rating of the 755LR?
The 755LR has a momentary current rating of 25kA Symmetrical for 10 cycles.
What is the impulse withstand rating for the 755LR?
The 755LR has a 150kV BIL (Basic Impulse Level) impulse withstand rating.
What standards does the 755LR meet?
The 755LR elbow connector meets ANSI/IEEE Standard 386, Latest Revision.
Is the 755LR elbow connector submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
What is the continuous current rating of the 755LR?
The 755LR elbow connector has a continuous current rating of 600 Amps.
What cable insulation diameters does the 755LR support?
The 755LR supports cable insulation diameters from 0.760 inches to 2.120 inches.
What conductor sizes are compatible with the 755LR?
The 755LR is compatible with aluminum and copper conductors ranging from #2 AWG to 1250 kcmil.
What is the maximum operating voltage for the 755LR?
The 755LR elbow connector is designed for use through 35kV voltage class, with a maximum phase-to-ground operating voltage of 21.1kV.
What cable insulation diameters does the 755LR support?
The 755LR supports cable insulation diameters from 0.760 inches to 2.120 inches.
Is the 755LR elbow connector submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 755LR and 775LR Deadbreak Elbow Connectors. These connectors create fully shielded, submersible deadfront cable connections for high voltage apparatus and enable splicing or tapping of 600-ampere or 900-ampere, 35kV class systems.
Estimated time: 2h
Tools needed:
Wire strippers, Cutting tool, Wire brush, Crimping tool, Hotstick, Suitable sensing device (for capacitive test points), Torque wrench
Supplies needed:
755LR or 775LR Elbow Connector, Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant, Stud Prepack, No. 14 AWG Copper equivalent wire (for grounding), Suitable connector (for grounding wire), Tape marker, HV insulated cap(s) or connector(s) (if replacing shipping covers), Grounding device (if used), Waterproofing material (for cable jacket)
- Position Cable and Prepare Neutral Wires
DANGER: All apparatus must be de-energized during installation or removal of parts. Position the cable in its final assembled position, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the center line of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24” (610mm) from the cut end.
- Prepare the Cable for Connection
Remove the outer jacket (if applicable) and prepare the cable according to its specific type (e.g., non-jacketed concentric neutral, jacketed shield wires, flat metallic tape shield, fabric tape shield, or longitudinally corrugated shield). Refer to the provided diagrams for precise measurements for removing the outer jacket, semi-con shield, and cable insulation. For UNISHIELD* or LEAD SHEATH cable, use a 10TL cable shield adapter and its instructions. If using a 20MA or 21MA grounding device or 600ECS Jacket Cable Seal, refer to their specific installation instructions for jacket removal, shield connection, and grounding.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution to avoid cutting or nicking the cable adapter or the conductor. The length of the exposed conductor must be between 4-3/8” to 4-3/4” (111mm-121mm). If the length is outside this range, redo the assembly.
- Attach and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 7” (178mm). Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping must be between 6-7/8” to 7-5/8” (175mm-194mm). Redo assembly if dimensions are not met.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Elbow and Mating Part
WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove any protective caps from the elbow and the mating part. Hand tighten the threaded stud supplied with the elbow into the mating part, if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect Elbow to Apparatus
Push the elbow onto the mating part, carefully aligning the hole in the compression lug with the stud on the mating part.
- Connect Second Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the specific instructions supplied with that mating part.
- Install Insulating Plug and Cap (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps securely into place.
- Ground the Cable Shield
Insert one end of a wire, with ampacity at least equivalent to No. 14 AWG Copper, through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions supplied with any grounding device used, or employ an alternate grounding method if no device is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test and Reinstall Cap
CAUTION: When constructing 600A L-Kits, tighten each component to specified torque per plug connector instructions. The ELASTIMOLD deadbreak elbow connector has an integral capacitance test point to check if the circuit is energized. To use, remove the test point cap with a hotstick, peeling it off at an an angle. WARNING: This is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device as per its manufacturer’s directions. Contamination or incorrect equipment can give a false 'no voltage' reading. Treat the elbow as energized until confirmed otherwise to prevent serious injury. After testing, clean, lubricate with silicone, and replace the cap.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.