ABB Installation Products 755LR-H0270-S 600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable…
UPC: 075114179904
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp, 35kV rated deadbreak elbow for medium-voltage applications
- Includes insulated plug, cap, stud, lug, and cable adapter
- Compatible with 0.850" to 1.050" cable insulation diameters
- Aluminum compression lug for 4/0 AWG, 250 kcmil, or 125 mm² compact conductors
- 200ECS cold-shrinkable jacket seal for moisture and environmental protection
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | Cable Insulation Diameter 0.850 inch to 1.050 inch |
Special Features | 100 Percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected Using Standard Hand Tools and Equipment in a De-energized State. Optional Accessories allow Visible External Separation, By-Pass, Isolation, Dead-Ending, Grounding, and Testing as well as Adding Taps, Surge Arrestors, and Fault Current Indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-K0270-SG3
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
755LR-H0250
600 Amp, 35KV, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 or Solid 3/0 or mmSquared 70.
376LRJ-5240-SG3
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. 200ECS-G3 Jacket Seal and Grounding Kit Included.
755LR-G0240-S
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0. 200ECS Cold-Shrinkable Jacket Seal Included.
755LR-H0230
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded #1/ Compacted Solid 1/0 /mmSquared Compact 50.
161LR-B5230
15KV, 200 Amp, Loadbreak Elbow, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
376LR-L5270-SG3
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 1.180 inch to 1.465 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS-G3 Jacket Seal and Grounding Kit Included.Frequently Asked Questions
What is the DC withstand voltage for the 755LR?
The 755LR has a 103kV DC 15-minute withstand rating.
What is the maximum operating voltage for the 755LR?
The 755LR elbow connector is designed for use through 35kV, with a maximum phase-to-ground operating voltage of 21.1kV.
What conductor sizes are compatible with the 755LR?
The 755LR is compatible with conductor sizes from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating of the 755LR?
The 755LR elbow connector has a continuous current rating of 600 Amps.
What insulation diameter range does the 755LR support?
The 755LR supports cable insulation diameters ranging from 0.760 inches to 2.120 inches.
Is the 755LR elbow connector submersible?
Yes, the 755LR features a fully shielded, fully submersible molded rubber housing.
What standard does the 755LR meet?
The 755LR elbow connector meets ANSI/IEEE Standard 386, Latest Revision.
What is the impulse withstand rating of the 755LR?
The 755LR has a 150kV BIL Impulse Withstand rating (1.2 x 50 microsecond wave).
What items are included in a 755LR kit?
A kit includes the elbow connector housing, copper compression lug, stud, insulated plug with cap, lubricant tubes, cable adapter, and installation instructions.
What is the purpose of the 755LR elbow connector?
The 755LR is designed to provide fully shielded, dead-front submersible cable connections to high-voltage apparatus.
How to Install 755/775LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 755LR and 775LR deadbreak elbow connectors on 35kV class systems. Ensure all apparatus are de-energized before beginning installation to prevent serious or fatal injury.
Estimated time: 1h 30m
Tools needed:
Crimping tool, Wire brush, Hotstick, Suitable sensing device (for capacitive test points), Wire strippers, Measuring tape or ruler
Supplies needed:
755/775LR Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant (silicone lubricant recommended), Threaded Stud, Wire (No. 14 AWG Copper or equivalent for grounding), Suitable connector (for grounding wire), Tape marker
- Position Cable and Prepare for Cutting
Position the cable in its final assembled position, ensuring enough slack to allow for elbow removal. If applicable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product.
- Clean Cable Outer Jacket
Clean the outer jacket of the cable for a distance of 24” (610mm) from the cut end.
- Prepare Cable for Connection
Prepare the cable by removing the outer jacket (if applicable) and stripping the semi-con shield and insulation to the specified lengths (e.g., 13-5/8" for outer jacket, 11-3/8" for semi-con shield, 10-3/8" for insulation) as shown in the product's cable preparation diagrams for your specific cable type. If using a 20MA/21MA grounding device, 600ECS Jacket Cable Seal, or 10TL cable shield adapter, refer to their respective installation instructions for cable preparation.
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution to avoid cutting or nicking the cable adapter or the conductor. The length of the exposed conductor must be between 4-3/8” to 4-3/4” (111mm-121mm); otherwise, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the “Check Dimension” before crimping (it should be less than 7” or 178mm). Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-7/8” to 7-5/8” (175mm-194mm); otherwise, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify that the cable adapter is still flush with the tape marker; reposition it if necessary. Remove the tape marker.
- Prepare Mating Products
Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud (supplied with the elbow) into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that specific mating part.
- Install Insulating Plug (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps firmly into place.
- Ground the Cable Shield
Insert one end of a wire (with ampacity at least equivalent to No. 14 AWG Copper) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded, either according to the instructions supplied with a grounding device or through an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the suitable sensing device used to determine if the cable is energized. Contamination or incorrect equipment can provide a false “no voltage” indication; treat the elbow as energized until confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.