Authorized ABB Distributor (Installation Products)
ABB - Installation Products 675ETPSP-L2300-DRG - 900 Amp, 15kV, Loadbreak Elbow Tap Plug, Factory assembled Stud, which is not field removable. Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. With Insulated Cap.

ABB Installation Products 675ETPSP-L2300-DRG 900 Amp, 15kV, Loadbreak Elbow Tap Plug, Factory assembled Stud, which is not field…

UPC: 783786442485


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

The ABB 900 Amp, 15kV Loadbreak Elbow Tap Plug (SKU: 675ETPSP-L2300-DRG) is a factory-assembled medium-voltage electrical connector designed for high-reliability power distribution systems. The permanently integrated stud eliminates field removal risks, ensuring a tamper-resistant and secure connection for long-term service. This plug features a copper compression lug for high-conductivity termination, minimizing resistance and maximizing current transfer efficiency. It supports cable insulation diameters between 0.980 inch and 1.180 inch, accommodating a range of medium-voltage cable types. The plug is rated for compressed stranded conductors up to 350 kcmil, compacted solid conductors up to 400 kcmil, and mm² compact conductors up to 185 mm². An insulated cap is included to protect against accidental contact and environmental contaminants during installation and operation. Designed for use with loadbreak connectors, this component meets the demands of 15kV class systems, ensuring safe and efficient power distribution in utility, industrial, and commercial applications. The factory-assembled design reduces installation time and eliminates the need for on-site lug assembly, improving reliability and reducing maintenance costs.
  • 900 Amp, 15kV rated for medium-voltage power distribution
  • Factory-assembled stud permanently integrated, not field removable
  • Copper compression lug for high-conductivity termination
  • Supports cable insulation diameters 0.980 inch to 1.180 inch
  • Rated for compressed stranded conductors up to 350 kcmil, compacted solid conductors up to 400 kcmil, and mm² compact conductors up to 185 mm²
  • Includes insulated cap for protection against accidental contact and contaminants

Specifications

Amperage Rating
900 A
Application
900 Amps, 15kV
Color
Black
Color
Blue
Conductor Range
#1 STR/COMPR AWG , 1/0 SOL/COMPT AWG
Connection
Compression
Connection Type
Loadbreak Connector
Connection Type
Compression Lug
Current Rating
900 A
Insulation
EPDM Rubber
Material
Copper, Poly
Material
Housing - EPDM-Rubber
Material
Copper
Series
675ETPSP
Size
Cable Insulation Diameter 1.180 inch to 1.465 inch
Size
Cable Insulation Diameter 0.980 inch to 1.180 inch
Special Features
Includes Insulated Cap and Sealing Kit
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Window-Op Connector
Voltage Rating
15 kV
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, #1 Stranded Wire Size, Copper Compression Lug

162LR-B-2230

15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .635 inch - .905 inch Cable Insulation Diameter, #1 Stranded Wire Size, Copper Compression Lug
Copper-coated conductor 1,90m 63A x2

173G0412

Copper-coated conductor 1,90m 63A x2
Solenoid Valve Connectors, Accessory, Thumb screw, Cabled Form A, B, ISB, and FW ISC

V-25TB

Solenoid Valve Connectors, Accessory, Thumb screw, Cabled Form A, B, ISB, and FW ISC
600 Amp, 35kV, Deadbreak, Test and Ground Connector kit, includes Insulated cap, reducing tap plug, elbow housing, cable adapter and 0370 style compression lug. 600ATM assembly tool required, 50-60 foot/pounds torque wrench required but not included. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.

755ETP-M0300-DRG

600 Amp, 35kV, Deadbreak, Test and Ground Connector kit, includes Insulated cap, reducing tap plug, elbow housing, cable adapter and 0370 style compression lug. 600ATM assembly tool required, 50-60 foot/pounds torque wrench required but not included. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185.
900 Amp, 15kV, Loadbreak Elbow Tap Plug, Factory assembled Stud, which is not field removable. Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. With Insulated Cap.

675ETPSP-L2330-DRG

900 Amp, 15kV, Loadbreak Elbow Tap Plug, Factory assembled Stud, which is not field removable. Copper Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. With Insulated Cap.
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500.

656ETP-N0400-DRG

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 900 /Compacted Solid 1000 /mmSquared Compact 500.
600 Amp, 35kV, Deadbreak, Test and Ground Connector kit, includes Insulated cap, reducing tap plug, elbow housing, cable adapter and 0370 style compression lug. 600ATM assembly tool required, 50-60 foot/pounds torrque wrench required but not included. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.

755ETP-M0260-DRG

600 Amp, 35kV, Deadbreak, Test and Ground Connector kit, includes Insulated cap, reducing tap plug, elbow housing, cable adapter and 0370 style compression lug. 600ATM assembly tool required, 50-60 foot/pounds torrque wrench required but not included. Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 3/0 /Compacted Solid 4/0 /mmSquared Compact 95.
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Window-Op Connector Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 1000.

656ETP-N0410

600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Window-Op Connector Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 1000.

Frequently Asked Questions

What is the primary function of the 675ETP?

The 675ETP elbow tap plug permits a 200 Amp tap off of a mating 900 Amp connector. It is designed for 15kV voltage class applications.

How can I order the 675ETP with a factory-assembled stud?

To order the 675ETP with a factory-assembled stud, add "SP" to the part number. For a loose stud, add suffix "S".

What is included in the 675ETP kit?

Each kit contains one 675ETP Bushing Insert, one 1601-APC-1 Protective shipping cap, two 82-08 Lubricants, and one IS-0766 Installation Instruction.

Can the loadbreak interface be operated when energized?

Yes, the loadbreak interface of the 675ETP is specifically designed for energized operation. This allows for safe and efficient use.

What type of insulation and jacket does it use?

The 675ETP uses peroxide-cured insulation and jacket. This material provides durability and performance.

Does the 675ETP include a seating indicator?

Yes, the 675ETP features a Seating Indicator. This provides a visual check to confirm that mating components are properly installed.

What products are compatible with the 675ETP?

The 675ETP mates with products like K675BLR, K675BE, 167DR, 167DRG, 167ESA-XX, 165LR, 165LRJS, 167ELR, 167RLR, 167DLR, 167DELR, and 160GLR.

What is the impulse withstand rating (BIL) for this product?

The impulse withstand (BIL) rating for the 675ETP is 95kV. This is based on a 1.2 x 50 microsecond wave.

What ANSI/IEEE standard does the 675ETP meet?

The 675ETP meets ANSI/IEEE Standard 386, Latest Revision. This ensures compliance with industry standards.

What is the continuous current rating for the deadbreak interface?

The deadbreak interface has a continuous current rating of 900 Amps. This applies to the deadbreak connection.

How to Install the LINK-C Deadbreak Cam Link Operable Connector System

This guide provides step-by-step instructions for the safe and proper installation of the LINK-C Deadbreak Cam Link Operable Connector System, including mounting, wiring, and grounding procedures.

Estimated time: 2h

Tools needed:

Hot stick, 600ATM (Operating Tool), Torque wrench, Suitable 1-inch hex tool, Welding equipment (if applicable), Wire strippers

Supplies needed:

ELASTIMOLD supplied lubricant, 3/8-16 x 2 inch studs (3, if applicable), Hex nuts (3/8-16), Lockwashers, Spacers (optional, not supplied), #14 AWG or #12 AWG solid copper wire, Appropriate grounding connectors, HV insulated cap(s) or connector(s) (if replacing shipping covers)

  1. Prepare and Ensure Safety

    DANGER: Before beginning, ensure all apparatus are de-energized. Inspect all components for damage, rating, and compatibility with mating parts. Gather all required tools and supplies. If the product is supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.

  2. Install 600 Amp Elbow (Prerequisite)

    Install the 600 amp elbow onto the cable according to the installation instructions supplied with the elbow. Ensure that the elbow is positioned such that it will align correctly with the standoff plug or apparatus bushing during subsequent steps.

  3. Mount Standoff Plug (Conditional)

    If your installation requires a mounted standoff plug, weld three 3/8-16 x 2” studs to the faceplate according to customer standard practice and specified dimensions. Install three hex nuts onto the studs to support the standoff plug, ensuring it aligns with the bushing. Position the standoff plug over the three studs, resting on the nuts or optional spacers. Install a lockwasher and hex nut on each stud and tighten to 12 ft-lbs torque. Verify the top surfaces of the apparatus bushing and standoff plug are in-line; re-adjust nuts as required.

  4. Assemble Bushing Extender and Elbow

    Clean and thoroughly lubricate the apparatus bushing and both interfaces of the 600 amp bushing extender with ELASTIMOLD supplied lubricant. Install the bushing extender onto the apparatus bushing. Insert the 600ATM tool into the retainer contact and engage its internal hex broach. Insert the retainer contact into the bushing extender and thread it into the apparatus bushing using a suitable tool applied to the 1” hex portion of the 600ATM, torquing to 50-60 ft-lbs. Repeat the cleaning, lubricating, and installation process for the 600 amp elbow onto the epoxy standoff plug, torquing to 50-60 ft-lbs.

  5. Install and Align Bracket

    Remove the bushing extender clamp and elbow clamp from the alignment bracket. Position the alignment bracket on the bushing extender at a dimension of 2.5 inches (63.5mm) from the grounding eye. Assemble the bushing extender clamp to the alignment bracket with the supplied hardware, torquing by alternating sides until the clamp tabs are flush with each other and tight. Position the elbow in the alignment bracket such that the elbow cuff is lined up evenly with the bushing extender cuff. Assemble the elbow clamp to the alignment bracket, torquing until tabs are flush and tight, ensuring the clamp notch faces the cable entrance of the elbow.

  6. Insert LINK-C Connector

    Clean and thoroughly lubricate both 600 ampere interfaces of the LINK-C connector with ELASTIMOLD supplied lubricant. Align the Link such that when inserted into the bushing extender and elbow, the Link is perpendicular to the switch faceplate. Insert the Link into the bushing extender and elbow, ensuring both lever arms are on the inside of the alignment bracket legs. Engage the pivot pin into the slots in the alignment bracket legs. While pushing inward, move the lever arms downward using a hot stick eye, thus engaging the roller pin and moving the Link inward. Continue moving lever arms until perpendicular to the alignment bracket leg.

  7. Grounding and Final Connections

    Ground the elbow: Feed a #14 AWG or #12 AWG solid copper wire through the grounding eye on the elbow, twist it tight, and connect it to ground. Clean and lubricate the 200 amp interface on the Link. Ground, then install the desired mating product on the 200 amp interface according to its specific installation instructions. Ground the cable: If concentric neutral cable is used, twist the concentric neutral wires together and connect to ground using an appropriate connector. If 20MA or 21MA grounding devices are used, connect the ground lead from the device to ground using a suitable connector. For three-phase installations, all grounds from all three phases must be tied to a common ground point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.