ABB Installation Products 376LR-J-5240 35kV 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980…
UPC: 783786663378
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating with 200 Amp current capacity
- Loadbreak capability for safe energized circuit disconnection
- Built-in test point for circuit verification without service interruption
- Bi-metal compression lug compatible with copper and aluminum conductors
- Accommodates cable insulation diameters from 0.980" to 1.180"
- Supports 1/0 AWG compressed stranded and 2/0 AWG solid conductors
- Molded-in semi-conductive shield for uniform electrical stress distribution
- Hot stick operation rated for safe installation and maintenance
Specifications
Amperage Rating | 200 A |
Application | 35 kv, 200 Amp |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Push-In |
Connection Type | Compression |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Material | Bi-Metal Compression Lug |
Material | Housing - EPDM-Rubber |
Series | 376LR |
Size | Conductor: 1/0 AWG (stranded) / 2/0 AWG (solid), Cable Insulation: 0.980-1.180" |
Size | Cable Insulation Diameter 0.980 inch to 1.180 inch |
Special Features | 35kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Non-Corrosive Capacitive Voltage Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.1400 L |
Package Weight (Metric) | 1.4240 kg |

375LR-H5240
200 Amp, 35kV, Loadbreak Elbow Connector without Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
376LR-J-5230
35kV 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
168ELR-7495-5260
15kV 200 Amp, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Cable Insulation .740-.950 inches, Bi-Metal Contact. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
168RLR-G-5230
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.760 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
274ELR-7495-5250
200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. Cable Insulation Diameter 0.740 inch to 0.950 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
168RLR-F-5260
200 Amp, 15kV, Loadbreak Replacement Elbow Connector with Test Point, Cable Insulation Diameter 0.640 inch to 0.820 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01. Repair Elbow has extended length contact and elbow housing resulting in a net gain of 8-7/8 inches in length. Includes 00400X long Bi-Metal Contact.
K151SP-B2260
200 Amp, 15/25kV, Deadbreak Elbow, Straight Plug, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Includes a copper compression lug. Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
K151SR-B0270
200 Amp, 15/25kV, Deadbreak Elbow, Straight Receptacle, Bails are required but not included, order separately. Cable Insulation Diameter 0.635 inch to 0.905 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 4/0 or kcmil Solid 250 or mmSquared 126.67.Frequently Asked Questions
What is the voltage rating of the 376LR Elbow Connector?
The 376LR Elbow Connector is rated for 35kV voltage class, with a maximum phase-to-ground operating voltage of 21.1kV and a maximum phase-to-phase voltage of 36.6kV.
What items are included in the 376LR Elbow Connector kit?
Each kit contains an elbow connector housing, a bi-metal compression lug, a probe, a probe wrench, a tube of lubricant, installation instructions, and a crimp chart.
What is the corona extinction voltage rating?
The corona extinction rating is 26kV AC at 3p.C. sensitivity.
Is the 376LR Elbow Connector submersible?
Yes, the 376LR Elbow Connector features a fully shielded, fully submersible molded rubber housing.
What is the fault close rating for the 376LR?
The 376LR has a 10kA Sym, 10 Cycles Momentary & Fault Close rating.
What is the impulse withstand rating of the connector?
The connector has a 150kV BIL Impulse Withstand rating, based on a 1.2 x 50 microsecond wave.
Does the 376LR have a voltage test point?
Yes, the 376LR is equipped with an integral, non-corrosive capacitive voltage test point.
What type of conductors are compatible with the compression lugs?
Bi-metal compression lugs are suitable for both copper or aluminum conductors, while copper compression lugs are for copper conductors only.
What standards does the 376LR Elbow Connector meet?
The 376LR Elbow Connector meets ANSI/IEEE Standard 386, Latest Revision.
Can the 376LR connector be operated while energized?
Yes, it includes provisions for energized operation using standard hot stick tools, allowing loadmaking/loadbreak operation and a visible disconnect.
How to Install 375LR/376LR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and initial setup of 375LR and 376LR Loadbreak Elbow Connectors, including cable preparation, elbow assembly, and grounding.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Crimp tool, Wire brush, Hotstick, Suitable sensing device
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), Copper wire (No. 14 AWG / 2.5mm), Appropriate connector, HV insulated cap(s) or connector(s), Silicone grease
- De-energize Apparatus
Ensure all apparatus is de-energized during installation or removal of parts, except for test point caps and indicators that can be installed and operated energized. Failure to follow this instruction will result in serious or fatal injury.
- Inspect Components and Shipping Covers
Check the package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products. If supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Check Probe Threads
Thread the probe into the compression lug by hand. If resistance is encountered prior to full assembly, check for damage and replace the damaged component.
- Prepare Workspace
Have all required tools at hand and maintain cleanliness throughout the procedure.
- Train Cable
Train the cable as shown in the diagram to ease operation. Cut any excess cable squarely at the center line of the bushing.
- Prepare Cable End
Unwrap and bind concentric neutral wires 8-1/2 inches back from the end of the cable. Remove the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor.
- Install Compression Lug
Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread inhibitor. Position the compression lug so the contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable.
- Prepare Insulation Shield
Remove the insulation shield as shown in the diagram. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the lubricant supplied. DO NOT SUBSTITUTE. Keep insulation clean of dirt and grime.
- Assemble Elbow onto Cable
Slide the elbow connector onto the cable with a back-and-forth twisting motion. Wipe off all excess grease.
- Align Elbow and Lug
Align the elbow with the compression lug's threaded hole.
- Thread and Tighten Probe
Thread the probe into the lug by hand, taking care not to cross-thread. The probe must turn freely for approximately four turns before becoming snug. Tighten with the probe wrench until the wrench bends.
- Connect Grounding Wire
Using a separate copper wire (No. 14 AWG / 2.5mm or equivalent), insert one end through the grounding eye on the elbow. Twist it tight, taking care not to damage the eye.
- Connect Neutral Wires to Ground
Twist all neutral wires and connect them to ground using an appropriate connector. Provide adequate slack in wires for elbow operation.
- Lubricate Mating Surfaces (if de-energized)
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY IF the transformer and elbow are known to be de-energized.
- Perform Voltage Test (376LR only)
For 376LR connectors, remove the test point cap with a hotstick, peeling it off at an angle. Use a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Treat the elbow as energized until the "no voltage" test point indication is confirmed by other means.
- Replace Test Point Cap (376LR only)
After voltage detection, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.