
ABB Installation Products 35PCJ1M2300 35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 783786656134
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 35kV voltage rating for medium-voltage applications
- Single-piece housing for efficient installation
- Accommodates cable insulation diameters from 1.370" to 1.630"
- Designed for 350 AWG stranded copper conductors
- ABB Installation Products quality and reliability
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 350 kcmil |
Connection | Compression |
Insulation | Yes |
Material | Copper |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Series | Style 1 |
Size | 14-3/8 inch long |
Size | 1.370-1.630 inch |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 3.2500 L |
Package Weight (Metric) | 1.4740 kg |

35PCJ1M1300
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Conductor. Conductor Size AWG Stranded 350.
25PCJ1L2330
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Copper Conductor. Conductor Size AWG Stranded 500.
25PCJ1H1230
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
35PCJ1J1230
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded #1/Solid 1/0.
25PCJ1J1270
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
25PCJ1L1330
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
15PCJ2J1270-H1270
15kV Power Cable Joint Style 2 with Universal Housing and Separate Cable Adapters. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
25PCJ1G1240
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Conductor. Conductor Size AWG Stranded 1/0 /Solid 2/0.Frequently Asked Questions
What voltage classes are available?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What conductor materials can be used?
These joints can be used with copper or aluminum conductors, accommodating a wide range of sizes up to 1250 kcmil.
Can copper connectors be used on aluminum cables?
No, copper compression connectors are for copper-to-copper connections only and should not be used on aluminum conductors.
What is the maximum conductor size supported?
The Elastimold PCJ power cable joints can accommodate conductor sizes up to 1250 kcmil.
What are the two styles of PCJ joints?
Style 1 is for straight splicing of two similar cables. Style 2 includes separate cable adapters for transition splicing of different cable sizes.
What is the continuous current rating?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
Can copper connectors be used on aluminum cables?
No, copper compression connectors are for copper-to-copper connections only and should not be used on aluminum conductors.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What voltage classes are available?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
How to Install the 15/25/35PCJ1 Series Straight Joint
This guide provides step-by-step instructions for installing the 15/25/35PCJ1 series straight joint, a permanent, fully shielded, and submersible joint for wire shielded cables. It covers cable preparation, splice installation, and final assembly for aluminum to aluminum or aluminum to copper conductors.
Tools needed:
Cable cutters, Wire strippers, Wire brush, Crimping tool, T&B WT3D tool (for 35kV cable ties)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (user supplied), DELTECt Cable ties TYD5135 (for 35kV only), #14 AWG copper wire or equivalent (if needed), Cable jacket reconstruction material (if applicable)
- Ensure Safety and Prepare Workspace
DANGER: Ensure all apparatus is de-energized before beginning installation. Inspect all components for damage, proper rating, and compatibility with mating parts. Gather all required tools and supplies, and maintain cleanliness throughout the procedure.
- Prepare Cables for Joint Installation
Overlap both cables and cut them to 12 inches (305mm) from the joint's centerline. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires, then cut both cables precisely at the joint's centerline.
- Prepare Cable 1 and Position Joint Housing
Taper the edge of Cable 1's insulation shield from 1/2 inch to 1-1/2 inches (13mm to 38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1, positioning it up to the shield wires.
- Prepare Cables for Splice Connection
Carefully remove the cable insulation and then the insulation shield from both Cable 1 and Cable 2 according to the dimensions provided in the documentation (X and Y dimensions). Exercise extreme caution to avoid cutting or nicking the cable insulation or conductor.
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them thoroughly before insertion. Immediately insert the conductors into the splice, ensuring proper depth. Crimp the splice according to the manufacturer's recommendations provided with the splice. Wipe off any excess inhibitor. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips are cleared from the splice and joint assembly area. Clean the cables where indicated and lubricate to create a ramp of lubricant at the edge of the insulation shield.
- Position Joint Housing and Secure 35kV Ties (Optional)
Slide the joint housing into its final position, ensuring proper alignment by observing and equalizing the deformation of the joint ends. For 35kV installations ONLY, install two DELTECt Cable ties on each end of the cable entrance. Position the outer ties approximately 1/4 inch (6mm) from the splice edge, then install the second ties approximately 1/4 inch (6mm) from the first, ensuring an offset of the locking heads. Use the T&B WT3D tool (not included) to tighten and trim the ties.
- Complete Grounding and Final Assembly
Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint. Insert one shield wire from each cable (if #14 AWG or larger, otherwise use separate #14 AWG copper wire or equivalent) through the joint grounding eye. Connect all joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.