- 25kV rated loadbreak repair elbow with integrated test point
- Extended length contact and housing (3-1/4 inch net gain)
- Supports cable insulation diameter: 0.665 inch to 0.895 inch
- Bi-Metal Compression Lug for #2/AWG compressed stranded or #1/AWG solid conductors (33.62 mm²)
- Includes 02509X long Bi-Metal Contact for enhanced conductivity
Specifications
Amperage Rating | 200 A |
Application | Designed for connecting to and operating 25kV Class, 125kV BIL apparatus |
Color | Black |
Conductor Range | #2 STR/COMPR AWG , #1 SOL/COMPT AWG |
Connection | Compression |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 11.71 in |
Length | 297.434 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured insulation, insert and jacket. Provision for hot stick operation, Provision for ground wire connection. Wide cable range with minimum number of sizes. Extended Length Housing and Compression Lug - plus 3-1/4 inch (82.6mm). Non-Corrosive Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Repair Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 8.4 in |
Width | 213.36 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-F5220
25kV, 600 Amp, Deadbreak Elbow, No Sealing Kit, without Test Point, Cable Insulation .640-.820 inches, Bi-Metal Lug, Conductor Size AWG Compressed/Stranded #2 or Compacted/Solid #1 or mm2 Compact 35.
273ELR-88110-5270
25kV, 200 Amp, Extended Elbow, No Sealing Kit, 200 Amp, 25kV, Loadbreak Repair Elbow Connector, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. Cable Insulation Diameter 0.880 inch to 1.100 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67.
262LR-E5230
25kV, 200 Amps, Loadbreak Elbow, no Sealing Kit, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Bi-Metal Conductor, Conductor Size #1 Stranded/Compressed, 1/0 Solid/Compact. With Test Point. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installion Instruction Sheet and Crimp Chart.
262LR-E5240
25kV, 200 Amps, Loadbreak Elbow, no Sealing Kit, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Bi-Metal Conductor, Conductor Size 1/0 Stranded/Compressed, 2/0 Solid/Compact. With Test Point. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installion Instruction Sheet and Crimp Chart.
262LR-E5230-SG2
25kV, 200 Amps, Loadbreak Elbow, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Bi-Metal Conductor, Conductor Size #1 Stranded/Compressed, 1/0 Solid/Compact. With Test Point. 200ECS-G2 Jacket Seal and Grounding Kit Included. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installion Instruction Sheet and Crimp Chart.
274ELR-7495-5230
200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact. No Sealing Kit, Cable Insulation Diameter 0.740 inch to 0.950 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49.
274ELR-88110-5230
200 Amp, 25kV, Loadbreak Repair Elbow Connector with Test Point, Repair Elbow has extended length contact and elbow housing resulting in a net gain of 3-1/4 inches in length. Includes 02509X long Bi-Metal Contact., No Sealing Kit, Cable Insulation Diameter 0.880 inch to 1.100 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded #1/Solid 1/0 /mmSquared 42.41.
262LR-E5250-SG2
25kV, 200 Amps, Loadbreak Elbow, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Bi-Metal Conductor, Conductor Size 20/ Stranded/Compressed, 3/0 Solid/Compact. With Test Point. 200ECS-G2 Jacket Seal and Grounding Kit Included. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installation Instruction Sheet and Crimp Chart.Frequently Asked Questions
What is the catalog number for the test point cap?
The catalog number for the test point cap is 156-7.
Is a jacket seal recommended for these connectors?
Yes, a 200ECS jacket seal is available and highly recommended. It can be included by adding an "-S" suffix to the catalog number.
What voltage classes are available for these connectors?
The elbow connectors are available for 15 kV and 25 kV voltage classes.
Where are these Elastimold elbows manufactured?
Elastimold 200 A repair and replacement elbows are designed, molded, and tested in Albuquerque, New Mexico, USA.
What standards do these elbow connectors comply with?
These elbow connectors are IEEE 386 compliant, ANSI certified, and Rural Utilities Service (RUS) accepted.
Do these elbows include a test point?
Both repair and replacement elbows are available with an optional built-in capacitive test point to allow testing of the circuit for the presence of voltage.
How much length does the replacement elbow add?
The replacement elbow connector provides a net gain of 8 7/8 inches in length compared to a standard elbow.
How much length does the repair elbow add?
The repair elbow connector provides a net gain of 3 1/4 inches in length compared to a standard elbow.
What is the primary use of these elbow connectors?
These elbow connectors are designed for transitioning from live-front to dead-front equipment, especially during switchgear and transformer replacement, to address varying bushing heights and short cable lengths.
What is the catalog number for the test point cap?
The catalog number for the test point cap is 156-7.
How to Install 273ELR/274ELR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and initial setup of 273ELR and 274ELR Loadbreak Elbow Connectors, including cable preparation, assembly, grounding, and optional voltage testing.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Crimp Tool, Wire Brush, Hotstick
Supplies needed:
Elbow Connector Housing, Compression Lug, Probe, Lubricant (Do Not Substitute), Copper wire (No. 14 AWG / 2.5mm or equivalent), Grounding connector, Silicone grease
- Perform Pre-Installation Checks and Train Cable
DANGER: Ensure all apparatus is de-energized before beginning installation. Inspect all package contents for completeness and damage. Verify all components fit properly with the cable and mating products. Train the UD cable to ease future operation, ensuring a minimum of 20 inches beyond the end of the cable pad mount transformer. For new installations, cut the excess cable squarely at the center line of the bushing.
- Prepare Cable and Install Compression Lug
Unwrap and bind concentric neutral wires 13 inches back from the cable end. Remove the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Immediately wire brush the bare aluminum conductors. Install the compression lug, rotating it to spread the inhibitor. Position the lug so its contact threaded hole aligns with the bushing bore. Crimp the lug starting at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable.
- Remove Insulation Shield and Clean Cable Insulation
Remove the insulation shield 10 inches from the end of the compression lug. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue, ensuring the surface is straight, smooth, and squared without any nicks or cuts.
- Assemble Elbow Housing and Install Probe
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; DO NOT SUBSTITUTE. Slide the elbow connector onto the cable with a back-and-forth twisting motion. Wipe off all excess grease. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends. If installing a 274ELR, lubricate the test point cap and assemble it tightly.
- Connect Concentric Neutral Wires to Ground
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow and twist it tight, taking care not to damage the eye. Twist all neutral wires and the wire from the grounding eye together, then connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Connect Elbow to Mating Bushing Plug
DANGER: Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Securely fasten a hotstick to the loadbreak connector pulling eye. Place the elbow connector receptacle over the bushing plug, inserting the elbow male contact until the first slight resistance is felt. Immediately push the elbow home with a fast, firm, straight motion to engage the internal lock on the elbow and bushing interface. DO NOT OPERATE BY HAND.
- Verify Circuit Status with Voltage Test (274ELR only)
If using a 274ELR connector, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Test with a suitable sensing device made for capacitive test points to determine if the cable is energized. Contamination or incorrect equipment can provide a false 'no voltage' indication. Treat the elbow as energized until confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone grease and replace it tightly.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.