ABB Installation Products 262LR-D2260 25/28kV, 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 075114345682
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25/28kV voltage rating for medium-voltage applications
- 200 Amp continuous current rating
- Integrated test point for safe circuit testing
- Accommodates cable insulation diameters from 0.890-1.220 inches
- Suitable for conductor sizes 260 - 3/0 AWG stranded/compressed and 4/0 AWG solid/compact
Specifications
Amperage Rating | 200 A |
Application | 25/28kV, 200 Amp, Loadbreak Connector |
Color | Black |
Conductor Range | 3/0 STR/COMPR AWG , 4/0 SOL/COMPT AWG |
Connection | Push-In |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Size | 8.20 inch (208.3 mm) X 9.03 inch (229.4 mm), 2.86 inch (72.6 mm) Diameter |
Special Features | 15kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 25 to 28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

376LR-J-5260
200 Amp, 35kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.980 inch to 1.180 inch. Bi-Metal Compression Lug, Conductor Size AWG Compressed Stranded 3/0 /Solid 4/0 /mmSquared 85.01.
162LR-B5240-SG2
200 Amp, 15kV, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. 200ECS-G2 Jacket Seal and Grounding Kit Included.
262LR-D2240
25/28kV, 200 Amp, Loadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.890-1.220 inches (22.61-30.99mm), Copper Lug, Conductor Size 240 - 1/0 Stranded/Compressed, 2/0 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Tube of Lubricant, Crimp Chart and Installations Instructions. 9.03 x 8.20 inches, 2.86 inch diameter.
262LR-E5250
25kV, 200 Amps, Loadbreak Elbow, Cable Insulation Diameter 1.090-1.310 inches, (27.69-33.27 mm), Bi-Metal Conductor, Conductor Size 2/0 Stranded/Compressed, 3/0 Solid/Compact. With Test Point. Kit Contains Elbow Connector Housing, Compression Lug, Probe, Probe Wrench, Lubricant, Installation Instruction Sheet and Crimp Chart.
755LR-M0280
600 Amp, 35kV, 600 Series Deadbreak Elbow (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation Diameter 1.370 inch to 1.630 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil Compressed Stranded 250, Solid 350.
161LR-C5270-S
15kV, 200 Amp Loadbreak Elbow Connector without Test Point. Cable Insulation Diameter 0.805 - 1.060 inches. Bi-Metal Conductor. Conductor Size 270 - 4/0 Stranded/Compressed or 250 kcmil Sold/Compact. S - Cold-Shrinkable Jacket Seal. Length 9.03 inches, 7.44 inch Width (without counting Probe). 2.92 Diameter.
K655LRTP-G0220-DRG
600 Amp, 25kV, Stick-Op Connector Kit with Insulated Cap. Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size AWG or kcmil, Compressed Stranded #2/Compacted Solid #1/mmSquared Compact 35.
676LRTP-K2330-DRG
900 Amp, 15kV Stickop Connector Kit With Test Point, No Sealing Kit. Cable Insulation Diameter 1.090 inch to 1.310 inch. Conductor Size Compressed Stranded 500 kcmil or Compacted Solid 600 kcmil or mmSquared Compact 250/300 kcmil. Copper Conductor Only.Frequently Asked Questions
What is the maximum operating voltage for this elbow connector?
The ABB 262LR-D2260 loadbreak elbow connector is rated for 25/28kV.
What conductor sizes can this connector accommodate?
This connector is designed for conductor sizes 260 - 3/0 AWG stranded/compressed and 4/0 AWG solid/compact.
What is the range of cable insulation diameters supported?
The connector supports cable insulation diameters from 0.890 to 1.220 inches (22.61-30.99mm).
What components are included in the kit?
The kit includes the elbow connector housing, lug, probe, probe wrench, lubricant tube, crimp chart, and installation instructions.
Does this connector have a test point?
Yes, the 262LR-D2260 features a built-in test point for testing energized circuits.
How to Install 261LR and 262LR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation and initial setup of Elastimold 261LR and 262LR Loadbreak Elbow Connectors on various types of UD cables.
Estimated time: 1h 30m
Tools needed:
Probe wrench, Hotstick, Wire brush, Crimp tool, Cable cutting tool, Wire strippers, Vinyl tape
Supplies needed:
261LR or 262LR Loadbreak Elbow Connector Kit (includes housing, compression lug, probe, lubricant), No. 14 AWG / 2.5mm copper wire, Appropriate connector for neutral to ground connection, Elastimold cable shield or grounding device (if required for specific UD cable types), Cold shrink sealing kit (e.g., 200ECS, 200ECS-G1, 200ECS-G2, if applicable), Conductive copper tape (if using 200ECS-G2 kit)
- De-energize and Prepare Cable for Termination
DANGER: Ensure all apparatus is de-energized before beginning installation. Train the cable to ensure adequate slack for future operation. Cut the cable squarely at the centerline of the bushing. Depending on cable type, remove the outer jacket (9-5/8" or 240mm) and/or copper tape shield (7-1/8" or 180mm). Unwrap neutral or drain wires and bind them back, or wrap conductive copper tape over the end of the copper shield. If using a cold shrink sealing kit, slide the cold shrink tube onto the cable, loose end first.
- Prepare Cable End and Install Compression Lug
Remove the shield and insulation 2-1/8" (55mm) from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush the bare aluminum conductors thoroughly. Immediately install the compression lug, rotating it to spread the inhibitor and ensuring the contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart provided with the lug, rotating 180 degrees for each successive crimp. Carefully wipe any excess inhibitor from the lug and cable. Remove the insulation shield 6-7/8" (175mm) from the lug end. Bevel the insulation end by a maximum of 1/8" (5mm). Thoroughly clean the insulation to remove all traces of dirt or excess inhibitor.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE other lubricants, as they may be harmful. Slide the elbow connector onto the cable using a back-and-forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the probe wrench until the wrench bends, indicating proper torque.
- Ground the Elbow Connector
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow and twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to the ground using an appropriate connector. Ensure adequate slack in the wires to allow for elbow operation. If using a cold shrink grounding kit, refer to its specific instructions for completion.
- Connect Elbow to Bushing (De-energized)
DANGER: CONFIRM THAT THE TRANSFORMER AND ELBOW ARE DE-ENERGIZED before proceeding with this step. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. Securely fasten a hotstick to the loadbreak connector pulling eye. Insert the probe tip approximately 2" (50mm) into the bushing. Immediately push the elbow home with a fast, firm, straight motion, using sufficient force to engage the internal lock on the elbow connector and bushing interface. DO NOT OPERATE BY HAND.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.