ABB Installation Products 35PCJ1M1380 35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.370 inch to 1.630 inch.…
UPC: 075114311946
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Voltage rating: 35 kV for medium-voltage systems
- Conductor compatibility: AWG 700/750 (stranded) or AWG 900 (solid)
- Insulation diameter range: 1.370 inch to 1.630 inch
- Material: Aluminum compression lug for low-resistance connections
- Series: 35kV Power Cable Joint Style 1 by ABB
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 750 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 35 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

35PCJ1N1380-S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold Shrinkable Jacket Seal included.
35PCJ1N1360S
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cold Shrinkable Jacket Seal included.
35PCJ1M1400
35 kV, Power Cable Joint, Style 1 - 14-3/8 X 2-25/32 inches, Cable Insulation Diameter - 1.370-1.630 inches, Aluminum Connector, Conductor Size - 1000 kcmil.
35PCJ1N1330
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 500.
35PCJ1N1330-S
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Conductor. Conductor Size AWG Stranded 500. Cold-Shrinkable Jacket Seal Included.
69TCJS1P240PNDNNB
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size P Bore Diameter at Jacket/Insulation Transition 1.570. Connector Type - Copper, Connector Code 40P - Conductor Diameter Range - 1.036-1.100 inch (26.31-27.94mm), Heatsink Bore - N - 1.500 inch Diameter. Type Shield - D - Copper Tape and Neutral Wire, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - Heat Shrink
69TCJS1N230PEBNNB
69 kv, Transmission Cable Joint, Housing Type - Shieldbreak, Housing Style 1, Housing Size N Bore Diameter at Jacket/Insulation Transition 1.390. Connector Type - Copper, Connector Code 30P - Conductor Diameter Range - .636-.686 inch (16.15-17.42mm), Heatsink Size/Bore - E - .921 inch Diameter. Type Shield - B - Copper 1/3 Neutral Wire, Metallic Screen Continuity Kit - N - not required, Armor Kit - N - not required, Outer Jacket Restoration Kit - B - HeatShrink
69TCJN4-5-4Q
69 kv, Transmission Cable Joint, Housing Type - Non-Shieldbreak, Housing Style 4, Housing Size 5, 4QFrequently Asked Questions
What is the maximum conductor size supported by PCJ joints?
PCJ power cable joints support conductor sizes up to 1250 kcmil for both stranded/compressed and compacted/solid types.
What are the available voltage classes for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What types of conductors are compatible with PCJ joints?
PCJ joints can be used with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between different cable sizes.
What is the continuous current rating for PCJ joints?
The continuous current rating for PCJ power cable joints is equal to that of the cable rating.
What is the short-time current rating for PCJ joints?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What standards do PCJ power cable joints meet?
The shield design meets IEEE 592 standard, and connectors meet ANSI 119.4 Class A and Class 3 ratings. Electrical ratings meet IEEE 404.
What is the BIL impulse withstand for a 35 kV class joint?
For a 35 kV class joint, the BIL impulse withstand (1.2 x 50 μsec. wave) is 300 kV.
What is the AC withstand for a 15 kV class joint?
For a 15 kV class joint, the AC withstand at 60 Hz for 1 minute is 35 kV.
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for copper-to-copper connections only and should not be used on aluminum conductors.
How to Install the 35PCJ1 Series Cable Joint
This guide provides detailed instructions for the permanent, fully shielded, and submersible installation of the 35PCJ1 series straight joint for aluminum and/or copper conductor cables. Ensure all safety precautions are followed.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush, Measuring tape, Tapering tool, T&B WT3D tool (for 35kV only, not included)
Supplies needed:
Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (user supplied), DELTECt Cable ties (TYD5135, for 35kV ONLY), #14 AWG copper wire (or equivalent, if shield wires are smaller)
- Prepare for Installation and Ensure Safety
DANGER: All apparatus must be de-energized during installation. This product should be installed only by competent personnel trained in high voltage electrical equipment safety. Failure to follow instructions will result in serious injury or product damage. Inspect all parts for damage and compatibility. Read instructions completely, have all tools ready, and maintain cleanliness throughout the procedure.
- Prepare Cables to Joint Centerline
Overlap both cables and cut to 12” (305mm) from the joint centerline. This ensures sufficient shield wire length. Where applicable, remove Cable 1 jacket to 37” (940mm) and Cable 2 jacket to 21” (530mm) from the centerline. Fold back shield wires, then cut both cables at the joint centerline.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1 insulation from 1/2” (13mm) to 1-1/2” (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Slide the housing onto Cable 1, up to the shield wires, ensuring no contamination of electrical interfaces.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation and then the insulation shield from both cables. DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR. Verify conductor exposure 'X' and insulation shield removal 'Y' dimensions match the provided table for your cable size (e.g., 500-750 MCM: X=2 1/2", Y=6 1/4"; 1000 MCM: X=2 3/8", Y=6 3/8").
- Install and Crimp the Splice
If conductors are aluminum, wire-brush them immediately before insertion into the splice. Insert conductors and check the dimension against the 'Max Check Before' table. Crimp the splice following its recommendations. Wipe off excess inhibitor and check the distance between cable insulations against the 'Max Check After' table. Remove any sharp protrusions/burrs and metal chips from the splice and joint area. Clean cables where indicated and lubricate to create a build-up at the insulation shield edge.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper positioning by equalizing the deformation of the joint ends. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance (1/4” from splice edge, 1/4” from first tie, offset locking heads) using the T&B WT3D tool. Remove the yellow pin from the joint grounding eye (35kV ONLY). Retrain shield wires and secure to joint ends. Insert one shield wire from each cable (or #14 AWG copper wire if smaller) through the joint grounding eye. Connect grounding wires and remaining shield wires with an appropriate connector. Reconstruct the cable jacket over both cables and joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.