ABB Installation Products 25PCJ1H1280 25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter…
UPC: 075114311878
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25kV rated power cable joint
- Single-piece housing for simplified installation
- Accommodates cable insulation diameters from 0.850" to 1.050"
- Designed for 250 AWG stranded aluminum conductors
- ABB Installation Products quality and reliability
Specifications
Application | For Direct Burial, Vault, Submersible and Other Severe Service Applications |
Color | Black |
Conductor Range | 250 kcmil |
Connection | Compression |
Insulation | Yes |
Material | EPDM Rubber |
Number Of Conductors | 2 |
Size | 14-3/8 inch long |
Special Features | Power Cable Joints utilize permanently crimped connectors. PCJ housings are fully insulated, shielded and sealed for direct-burial, vault, submersible and other servere service applications. Units have been designed and tested per IEEE Standard 404 to ensure system matched performance and ratings equal to the cable to which the splice will be installed. Power Cable Joints are available in two styles. Style 1 uses a single-piece housing that is sized to accommodate a specific range of cable - ideally suited to straight splicing of the same or similar cable. Style 2 designs incorporate a universal housing with separate cable adapters to allow transition splices of different types and sizes of cable |
Standard | IEEE Standard 404 |
Type | Power Cable Joint |
Voltage Rating | 25 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

15PCJ1-J2280
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.980 inch to 1.180 inch. Copper Conductor. Conductor Size AWG Stranded 250.
35PCJ1-H
35kV, PCJ - Power Cable Joint, with Single Piece Housing, Cable Insulation Diameter .850 - 1.050 inches, Housing Only
35PCJ1K1330
35kV Power Cable Joint Style 1, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 500 /Solid 600 /mmSquared 250/300.
35PCJ1H1280
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Compressed Stranded 250 /Solid 300.
25PCJ1K1330
25kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Conductor. Conductor Size AWG Stranded 500
35PCJ1J1300
35kV Power Cable Joint Style 1, Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 350 /Solid 400 /mmSquared 185.
35PCJ1K2270
35kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Conductor. Conductor Size AWG Stranded 4/0 /Solid 250.
15PCJ1H1290
15kV Power Cable Joint Style 1 with Single Piece Housing, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Conductor. Conductor Size AWG Solid 350.Frequently Asked Questions
Can copper connectors be used with aluminum conductors?
No, copper compression connectors are suitable for splicing copper conductors to copper conductors only and should NOT be used on aluminum conductors.
What is the short-time current rating?
The short-time current rating is equal to that of the cable rating, up to 35 kA.
What is the continuous current rating of the joints?
The continuous current rating of the PCJ power cable joints is equal to that of the cable rating.
What safety standards do PCJ joints meet?
The shield design meets IEEE 592 standard, and the connectors meet ANSI 119.4 Class A and Class 3 ratings.
What environments are suitable for PCJ cable joints?
PCJ power cable joints provide a permanent, fully shielded, fully submersible splice suitable for direct-burial, underground vault, and overhead applications.
What are the two styles of PCJ power cable joints?
Style 1 is for straight splicing of two similar cables. Style 2 uses separate cable adapters for transition splicing between different cable sizes.
What conductor types and sizes are compatible?
They are compatible with copper or aluminum conductors, supporting a wide range of sizes up to 1250 kcmil.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
What are Elastimold PCJ power cable joints used for?
They are used for straight splicing of two similar cables or transition splicing of different cable sizes, accommodating up to 1250 kcmil.
What voltage classes are available for PCJ joints?
Elastimold PCJ power cable joints are available in 15 kV, 25 kV, and 35 kV classes.
How to Install the 25PCJ1H1280 Straight Joint
This guide provides step-by-step instructions for the safe and proper installation of the 25PCJ1H1280 permanent, fully shielded, fully submersible straight joint for wire shielded cables, connecting aluminum to aluminum and/or aluminum to copper conductors.
Estimated time: 3h
Tools needed:
Cable knife, Measuring tape, Wire strippers, Wire brush, Crimping tool, T&B WT3D tool (recommended for 35kV cable ties)
Supplies needed:
25PCJ1H1280 Joint Housing, Splice (Conductor Contact), Lubricant (DO NOT SUBSTITUTE), Appropriate connector (for grounding wires), DELTECt Cable ties TYD5135 (for 35kV only), #14 AWG copper wire or equivalent (if shield wires are smaller than #14 AWG)
- Ensure Safety and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. This product should be installed only by competent personnel trained in good safety practices involving high voltage electrical equipment. Inspect all package contents and components to ensure they are complete, undamaged, and compatible with the cable and mating products. Read the entire installation instructions before starting and have all required tools at hand.
- Prepare Cables for Jointing
Overlap both cables and cut them to 12 inches (305mm) from the center line of the joint to ensure sufficient length of shield wires for rejoining. Where applicable, remove the cable jacket of Cable 1 to 37 inches (940mm) and Cable 2 to 21 inches (530mm). Fold back the shield wires. Finally, cut both cables precisely at the center line of the joint.
- Prepare Cable 1 and Store Joint Housing
Taper the edge of Cable 1's insulation at least 1/2 inch (13mm) to no greater than 1-1/2 inches (38mm). Clean and lubricate the insulation shield. Lubricate the inside bore of the joint housing on both ends. Carefully slide the joint housing onto Cable 1, moving it up to the shield wires for temporary storage.
- Prepare Cables for Splice Installation
Carefully remove the cable insulation from both Cable 1 and Cable 2 according to the specified dimensions for your conductor size (e.g., for 500-750 MCM, remove insulation to 'X' = 2 1/2 inches (64mm) and 'Y' = 6 1/4 inches (159mm)). Then, carefully remove the insulation shield from both cables. WARNING: DO NOT CUT OR NICK THE CABLE INSULATION OR CONDUCTOR during this process.
- Install the Conductor Splice
If conductors are aluminum, wire-brush them thoroughly and immediately insert them into the splice. Check the dimension against the 'Max Check Before' table (e.g., 6 inches (152mm) for 500-750 MCM). If it exceeds, redo the assembly. Crimp the splice following the manufacturer's recommendations. Wipe off any excess inhibitor. Check the distance between cable insulations against the 'Max Check After' table (e.g., 6 1/4 inches (159mm) for 500-750 MCM). If it exceeds, redo the assembly. Remove any sharp protrusions or burrs generated during crimping and ensure all metal chips/filings are removed from the splice and joint assembly area. Clean the cables where indicated and lubricate them in the direction of the arrows to create a build-up or ramp of lubricant at the edge of the insulation shield.
- Complete Joint Assembly and Grounding
Slide the joint housing into its final position, ensuring proper placement by observing and equalizing the deformation of the joint ends caused by the underlying cable insulation shield. For 35kV ONLY: Install two DELTECt Cable ties on each end of the cable entrance, with the outer ties approximately 1/4 inch from the splice edge and the second ties approximately 1/4 inch from the first, offsetting the locking heads. Use the T&B WT3D tool to tighten and trim the ties. Remove and discard the yellow pin from the joint grounding eye. Retrain the shield wires and secure them to the ends of the joint as shown in the diagrams. Insert one shield wire from Cable 1 (if #14 AWG or larger) through the joint grounding eye, and repeat for Cable 2. If shield wires are smaller than #14 AWG, use separate #14 AWG copper wire or equivalent. Connect the joint grounding wires and remaining shield wires using an appropriate connector. Finally, reconstruct the cable jacket (where applicable) over both cables and the joint housing.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.