ABB Installation Products 252LR-D5270 15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter…
UPC: 075114345996
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV, 200A deadbreak elbow connector with integrated test point
- Supports cable insulation diameters: 0.890-1.220" (22.61-30.99mm)
- Conductor size range: 270-4/0 AWG stranded/compressed or 250 kcmil solid/compact
- Bi-metal lug for compatibility with copper and aluminum conductors
- Compact design: 5.454 x 7.531 inches, 2.097-inch diameter
Specifications
Amperage Rating | 200 A |
Application | 15/25kV, 200 Amp Deadbreak Connector |
Color | Blue |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection | Compression |
Connection Type | Deadbreak Elbow |
Connection Type | Deadbreak Elbow Connector |
Current Rating | 200 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 7.531 in |
Length | 191.2874 mm |
Material | Bi-Metal Lug, Poly (assumed from description) |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal |
Series | 252LR |
Size | 5.454 x 7.531 inches (5.454 x 7.531 in) |
Size | 5.454 x 7.531 inches, 2.097 inch diameter |
Special Features | Fully Shielded, fully Submersible Molded Rubber Housing. Provision for Hot Stick Operation. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 5.454 in |
Width | 138.5316 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CETP-J0270
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Intergral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.980 to 1.180 inches (24.9-30.0mm). Aluminum Conductor Material, Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. No Sealing Kit.
K656LR-G0220
15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation .760 to .950 inch. Aluminum Compression Lug, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid
K656LR-G0230
15/25kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Cable Insulation .760 to .950 inch. Aluminum Lug, Conductor Size #1 Stranded/Compressed or 1/0 Compact/Solid
K656LR-H0270-SG3
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .850 to 1.050 inch. Aluminum Lug, Conductor Size 4/0 stranded/compressed or 250 Compact/solid. With Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K656LR-G0250-SG3
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .760 to .950 inch. Aluminum Lug, Conductor Size 2/0 stranded/compressed or 3/0 Compact/solid. With Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K656LR-F0240-SG3
600 Amp, 15/25kv, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter, Cable Insulation .640 to .820 inch. Aluminum Lug, Conductor Size 1/0 stranded/compressed or 2/0 Compact/solid. With Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
252LR-A5220
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575-0.740 inches (14.61-18.80mm), Bi-Metal Lug, Conductor Size 220 - #2 Stranded/Compressed, #1 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.
252LR-A5210
15/25kV, 200 Amp, Deadbreak Elbow Connector with Test Point, Cable Insulation Diameter 0.575-0.740 inches (14.61-18.80 mm), Bi-Metal Lug, Conductor Size 210 - #3 Stranded/Compressed, #2 Solid/Compact. Kit Includes Elbow Connector Housing, Lug, Probe, Probe Wrench, Bail Assembly, V.D. Cap-Peroxide, Tube of Lubricant, Crimp Chart and Installations Instructions. 5.454 x 7.531 inches, 2.097 inch diameter.Frequently Asked Questions
What adapter is needed for small cable OD?
For cables with an outside diameter less than 0.565 in, order the 160CA-XX cable adapter.
Can this connector be operated with a hot stick?
Yes, the connector includes provisions for de-energized operation using standard hotstick tools.
Is a sealing and grounding kit recommended?
Yes, for safety purposes, a sealing and grounding kit is highly recommended with the deadbreak elbow.
What are the operating voltage limits for 25kV class?
For the 25kV class, the maximum phase-to-ground operating voltage is 15.2kV, and phase-to-phase is 26.3kV.
What are the operating voltage limits for 15kV class?
For the 15kV class, the maximum phase-to-ground operating voltage is 8.3kV, and phase-to-phase is 14.4kV.
What ANSI/IEEE standard does it meet?
The 252LR Elbow Connector meets ANSI/IEEE Standard 386, Latest Revision.
What is the voltage and current rating?
The connector is rated for 15/25kV voltage class and a continuous current of 200 Amps. It also handles 10kA Sym for 10 Cycles Momentary & Fault Close.
Is a sealing and grounding kit recommended?
Yes, for safety purposes, a sealing and grounding kit is highly recommended with the deadbreak elbow.
What is the voltage and current rating?
The connector is rated for 15/25kV voltage class and a continuous current of 200 Amps. It also handles 10kA Sym for 10 Cycles Momentary & Fault Close.
What ANSI/IEEE standard does it meet?
The 252LR Elbow Connector meets ANSI/IEEE Standard 386, Latest Revision.
How to Install 252LR Deadbreak Elbow Connectors
This guide provides detailed instructions for the safe installation, cable preparation, and connection of 252LR Deadbreak Elbow Connectors to UD cable and 25kV class deadbreak bushings, including grounding and post-installation voltage testing.
Estimated time: 1h
Tools needed:
Wrench, Wire brush, Crimp tool, Hot stick, Capacitive voltage sensing device
Supplies needed:
Lubricant, No. 14 AWG (2.5mm) copper wire, Appropriate ground connector, HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Perform Initial Safety Checks and Inspect Components
DANGER: Ensure all apparatus is de-energized during installation or removal of parts. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating parts. Verify the package contents are complete and undamaged. Check the elbow housing cable entrance size and compression lug size for proper fit with the cable. Thread the probe into the compression lug by hand to check threads; if resistance is encountered, check for damage and replace the component. If the product has protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. If the test point cap is not installed, lubricate the cap and test point, then install the cap.
- Train the Cable
Train the UD cable as shown in the documentation to ease operation, ensuring a minimum of 20 inches (508.0mm) beyond the end of the cable pad mount transformer. Cut any excess cable squarely at the center line of the bushing.
- Prepare the Cable
Unwrap and bind the concentric neutral wires 8-1/2 inches (216.0mm) back from the end of the cable. Remove the shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush the bare aluminum conductors and immediately install the compression lug, rotating it to spread the inhibitor. Position the compression lug so its contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable. Remove the semi-con shield 6-7/8 inches (175.0mm) from the end of the cable. Bevel the insulation end a maximum of 1/8 inch (3.2mm). Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow
Clean and lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; DO NOT SUBSTITUTE other lubricants. Slide the elbow connector onto the cable using a back and forth twisting motion. Wipe off all excess silicone lubricant. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, ensuring not to cross-thread. Tighten the probe with the supplied wrench until the wrench bends, indicating proper torque.
- Assemble the Hold-down Bail
Place the hold-down bail into the hold-down bracket. Compress the bail and insert it securely into the brackets.
- Connect Concentric Neutral Wires
Using a separate No. 14 AWG (2.5mm) copper wire or equivalent, insert one end through the grounding eye on the elbow. Twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Ensure adequate slack in the wires to allow for elbow operation.
- Connect Elbow to Bushing Plug
Clean the receptacle portion of the elbow connector and the mating bushing. Lubricate these surfaces with the supplied lubricant ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. Use a fully insulated hot stick to place the elbow onto the bushing. DO NOT OPERATE BY HAND. DO NOT SEPARATE IF ENERGIZED.
- Secure Elbow with Bail
Pull the hold-down bail up over the crown or top of the elbow so that the eyebolt on the bail is directly over the operating eye. Tighten down on the elbow locator by turning the eyebolt in a clockwise direction. Adjust the nut on the eyebolt until it allows the eyebolt to seat securely in the locator, acting as a stop to prevent excessive force on the elbow. Once the nut is in its final position, it will not require readjustment for future removal and replacement of the elbow.
- Perform Voltage Test
Remove the test point cap with a hot stick, peeling it off at an angle rather than pulling directly in line with the assembly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Test with a suitable sensing device designed for capacitive test points to determine if the cable is energized. Contamination, moisture, dirt, or incorrect measuring equipment can provide a false “no voltage” indication; treat the elbow as energized until the “no voltage” indication is confirmed by other means to prevent serious injury. After voltage detection, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.