ABB Installation Products 168FLR3-C5240 Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port…
UPC: 075114420785
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Nominal fuse voltage rating: 8.3kV
- Two capacitive test ports for safe diagnostic testing
- Cable insulation diameter range: 0.805"–1.060" (20–27mm)
- Compatible with 1/0 AWG stranded/compressed or 2/0 AWG solid/compact bi-metal conductors
- Molded construction for durable environmental and mechanical protection
Specifications
Amperage Rating | 200 A |
Application | Protect Light Duty Underground Distribution Systems |
Color | Black |
Conductor Range | 1/0 STR/COMPR AWG , 2/0 SOL/COMPT AWG |
Connection | Compression |
Insulation | EPDM Rubber |
Length | 21.12 in |
Length | 536.448 mm |
Material | Molded |
Material | EPDM-Rubber Housing |
Material | Bi-Metal |
Size | 0.805 inch - 1.060 inch / 20-27mm |
Size | 0.805-1.060 inch / 20-27mm |
Special Features | Full-Range Current-Limiting Fusing with 50kA Interrupting Capability. Hotstick Operable 15kV Loadbreak Elbow Switching |
Standard | IEEE 386, ANSI C37.40, ANSI C37.41, ANSI C37.47 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Fused Elbow Connector |
Voltage Rating | 8.3 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

168FLR1B5240
Molded Current Limiting Fuse Housing, Nominal Fuse Voltage Rating 8.3kV, Fuse Test Port - Two Capacitive Test Ports, Small Housing, Cable Insulation Diameter 0.635 inch - 0.905 inch / 16-23mm, Bi-Metal Conductor size 1/0 AWG Stranded/Compressed, 2/0 AWG Solid/Compact.
K675LR-M2360-SG3
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.370 inch to 1.630 inch. Copper Compression Lug. Conductor Size Compressed Stranded 650 kcmil or Compacted Solid 750 kcmil. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K675LR-F2250-SG3
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 0.640 inch to 0.820 inch. Copper Compression Lug. Conductor Size AWG Compressed Stranded 2/0 or Compacted Solid 3/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K655VSL2-LAC03
15/25kV, 600 Amps, 2-Way Vault-Stretcher with Shear Bolts. Cable Insulation Diameter range 1.18-1.465 inch. Connector Sizing AC03 - 500-750 kcmil Stranded, Compressed, Solid or Compact. Kit Includes (1) Vault Stretcher Housing, (2) Aluminum Shear Bolts, (2) Cable Adapters and (2) Insulated Plugs with Caps and (1) Stud.
K675LR-N-5410
900 Amp, 15/25kV, 600 Series Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.515 inch to 1.780 inch. Bi-Metal Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1000.
K655SR-K2330
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 1.090 inch to 1.310 inch. Copper Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300. Length 17 inches, Diameter 4-1/4 inch.
K656DLR-N0410
600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed Stranded 1000.Frequently Asked Questions
What is the frequency rating of the device?
The device has a frequency rating of 50/60 Hz.
What is the product's primary application?
The Elastimold 168FLR protects light duty underground distribution systems, including sub-loops and radial taps. It replaces existing 200 Amp loadbreak tap elbows.
What is the voltage class of the 168FLR?
The 168FLR is designed for the 15kV voltage class, with an 8.3kV nominal fuse voltage and 10kV maximum rated fuse voltage.
What is the current rating range for the fuses?
The current rating for the fuses in the 168FLR is between 3 and 80 Amps.
What is the interrupting capability of the fused elbow?
The fused elbow has a symmetrical interrupting capability of 50,000 Amps. It features full-range current-limiting fusing.
Can the 168FLR be operated with a hotstick?
Yes, the 168FLR features hotstick operable 15kV Loadbreak Elbow switching.
Is the 168FLR suitable for submersible applications?
Yes, the 168FLR is fully sealed and submersible.
How are blown fuses indicated on the 168FLR?
The 168FLR has built-in voltage test points for quick and convenient blown fuse indication.
What industry standards does the 168FLR meet?
The 168FLR meets IEEE 386, ANSI C37.40, ANSI C37.41, and ANSI C37.47, Latest Revision.
What types of conductors are compatible with the lugs?
Copper compression lugs are for copper conductors only. Bi-metal compression lugs are suitable for copper or aluminum conductors.
How to Install the 168FLR/274FLR Loadbreak Fused Elbow Connector
This guide provides step-by-step instructions for the safe installation and initial setup of the 168FLR or 274FLR Loadbreak Fused Elbow Connector, including cable preparation and assembly.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Allen Wrench (torque limiting), Wire brush, Crimp tool, Screwdriver
Supplies needed:
Cable Half Housing, Elbow Half Housing, Fuse, Compression Lug, Probe, Probe Connector, Hose Clamp, Lubricant, Optional 200ECS Cold Shrink Cable Seal, Copper wire (No. 14 AWG / 2.5mm), Appropriate connector (for ground)
- Ensure Safety and Inspect Components
Before beginning, ensure all apparatus are de-energized. Inspect all parts for damage, proper rating, and compatibility with mating components. Verify package contents are complete and undamaged, and check component fit with cable and/or mating products. Thread the probe into the compression lug to check threads; if resistance is encountered, replace damaged components. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Prepare the Cable for Termination
Using the bushing centerline as reference, cut excess cable off 20 inches minimum beyond the bushing. If using, slide the optional 200ECS Cold Shrink Cable Seal onto the cable. Remove the jacket from the excess cable length and an additional distance of 'A' (fuse body length) + 7-3/8 inches from the bushing centerline. If a Cable Seal kit is used, follow its instructions; otherwise, unwrap and fold the concentric neutral wires back over the jacket and bind them. Squarely cut off the cable a distance of 'A' from the bushing centerline, leaving 7-3/8 inches minimum of cable to terminate. Cut 1-1/8 inches from the cable end, taking care not to nick the conductor.
- Install Compression Lug and Prepare Insulation
Wire brush the bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread inhibitor. Crimp the unthreaded end of the compression lug to the conductor, referring to the crimp chart for tool information. Start crimping at the crimp line mark and rotate 180 degrees for each successive crimp. Carefully wipe excess inhibitor from the outside of the lug and cable. Remove the insulation shield 5-1/2 inches from the end of the lug and bevel the insulation end 1/8 inch maximum. Thoroughly clean the insulation to remove all traces of conductive residue.
- Lubricate and Assemble Cable Half Housing
Apply the supplied lubricant to the outside of the connector, cable insulation, conductive shield, and the cable entrance end of the Fused Elbow cable half. Do not substitute lubricant. Insert the connector and cable into the cable half of the Fused Elbow until the top end of the connector protrudes beyond surface 'A'. This allows the fuse to be tightened before bottoming on the rubber.
- Install and Tighten the Fuse
Insert the threaded terminal end of the fuse into the cable half of the Fused Elbow and thread it into the cable connector. Hand tighten the fuse. CAUTION: The fuse stud will fracture if over-torqued. Pull the housing up against the bottom of the tightened fuse.
- Assemble Probe Connector and Orient Test Point
Assemble the probe connector to the fuse terminal. Rotate the probe connector so that its flats are perpendicular to the bushing with which it will mate. Lock the probe connector in position and tighten the setscrews using the special torque-limiting allen wrench supplied in the fuse kit. Rotate the cable half of the Fused Elbow so that the test point is perpendicular to the flats on the probe connector.
- Connect Elbow Half and Probe
Apply lubricant to the elbow half of the fused elbow and assemble it to the cable half. The cuff of the cable half will overlap the elbow half by 3/4 inch. Ensure the probe connector faces the opening of the fused elbow half and that the two test points are in line with each other. Insert the probe into the probe connector; it may be necessary to push on the cable to align the probe with the fuse. Start the threads by hand, taking care not to cross-thread the probe. To tighten, use the special torque-limiting allen wrench supplied, inserting the short end into the hole in the probe and tightening until the wrench bends and remains bent. Position the hose clamp as shown in the diagram and tighten it, but do not overtighten.
- Connect Concentric Neutral Wires
Using a separate copper wire (No. 14 AWG / 2.5mm) or equivalent, insert one end through each grounding eye on the elbow housing and cable housings. Twist tightly, taking care not to damage the eyes. If used, finish installing the 200ECS jacket seal. Twist all neutral wires, exercising care not to damage the grounding eyes, and connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Lubricate and Connect to Bushing (De-energized)
Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE-ENERGIZED. The elbow is now ready for operation per the operating instructions, but DO NOT OPERATE BY HAND.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.