Overview
- 15kV Voltage Rating
- 200 Amp Continuous Current Rating
- Jacket Seal for Environmental Protection
- Integrated Test Point for Diagnostics
- Bi-Metal Compression Lug for 4/0 AWG Stranded Wire
Specifications
Amperage Rating | 200 A |
Application | 15 kv, 200 Amp |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Connection Type | Loadbreak Jacket Seal Elbow Connector with Test Point |
Current Rating | 200 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Bi-Metal Compression Lug |
Material | Housing - EPDM-Rubber |
Series | 162LRJS |
Size | .635 inch - .905 inch Cable Insulation Diameter, 4/0 Stranded Wire Size |
Special Features | 15kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Built in cable jacket seal. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point and Jacket Seal |
Voltage Rating | 15 kV |
Voltage Rating | 15kV |
Width | 8.2 in |
Width | 208.28 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.2400 L |
Package Weight (Metric) | 1.0160 kg |

656ETP-H0270-DRG-S
600 Series Elbows with IEEE 386 Capacitive Test Points, 600 Amp, 15kV, Test and Ground Connector Kit, Insulated Cap. 200ECS Cold-Shrinkable Jacket Seal Included. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.
162LRJS-D5240
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .890 inch - 1.220 Inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-C5240
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-C5260
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 3/0 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-C5230
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, #1 Stranded Wire Size, Bi-Metal Compression Lug
162LRJS-D5270
15kV 200 Amp, Loadbreak Jacket Seal Elbow Connector with Test Point, .890 inch - 1.220 Inch Cable Insulation Diameter, 4/0 Stranded Wire Size, Bi-Metal Compression Lug
261LR-B5240
25/28kV, 200 Amp, Loadbreak Elbow Connector, .635 inch - .905 inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression Lug.Frequently Asked Questions
What is the significance of RUS acceptance for this product?
RUS acceptance from the USDA authorizes its use in rural infrastructure construction and improvements.
Is an optional integral jacket seal available?
Yes, the enhanced Elastimold 200 amp loadbreak elbow offers an optional integral jacket seal.
What is the function of the rigid probe support?
The internal rigid probe support ensures proper switching and easy probe installation.
What material is the pulling eye made from?
The pulling eye is made from robust stainless steel, promoting durable hotstick control.
What standards and certifications does the product meet?
The product is IEEE 386 compliant, ANSI certified, and has Rural Utilities Service (RUS) acceptance.
Does the loadbreak elbow have RUS acceptance?
Yes, the enhanced Elastimold 200 amp loadbreak elbow has Rural Utilities Service (RUS) acceptance from the USDA.
What are the voltage ratings for this loadbreak elbow?
The Elastimold 200 amp loadbreak elbow is available for 15 kV and 25 kV series applications.
What is the Elastimold 200 amp loadbreak elbow?
It is an enhanced 200 amp loadbreak elbow available for 15 kV and 25 kV series, designed for switching operations.
Is an optional integral jacket seal available?
Yes, the enhanced Elastimold 200 amp loadbreak elbow offers an optional integral jacket seal.
Does the loadbreak elbow have RUS acceptance?
Yes, the enhanced Elastimold 200 amp loadbreak elbow has Rural Utilities Service (RUS) acceptance from the USDA.
How to Install 161LRJS/162LRJS Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and preparation of 161LRJS and 162LRJS Loadbreak Elbow Connectors with Jacket Seal on UD cable, including cable training, preparation, assembly, and connection.
Estimated time: 1h 30m
Tools needed:
Probe wrench, Hotstick, Wire brush, Crimp tool, Suitable sensing device (for capacitive test points)
Supplies needed:
Lubricant (Do Not Substitute), Mastic strips, Vinyl tape, No. 14 AWG / 2.5mm copper wire (or equivalent), Appropriate grounding connector, HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Prepare for Installation and Safety Checks
De-energize all apparatus in the work area before beginning installation. Ensure the product is installed only by competent personnel trained in high voltage electrical equipment safety practices. Check the package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products. Check threads by threading the probe into the compression lug; if resistance is encountered, check for damage and replace the component. Read the entire installation instructions before starting. Have all required tools at hand and maintain cleanliness throughout the procedure. If the 162LRJS (with test point) is being installed and the test point cap is not present, lubricate the cap and test point, then install the cap. If the product is supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit. Inspect all parts for damage, rating, and compatibility with mating parts.
- Train the Cable
Train the cable to ensure sufficient slack for ease of operation. Provide an extra length of concentric neutral wires or grounding braid wire to facilitate the connection of the neutral to the tank ground and the operation of the hotstick. Mark the centerline of the bushing with tape and pull extra cable 24-26 inches beyond the centerline. Remove the outer jacket 7 3/4 to 8 inches back from the centerline. Connect the neutral wires to the tank ground with a jumper or grounding braid. Unwrap the neutral wire back past the bushing centerline. Cut the excess cable squarely at the centerline of the bushing.
- Prepare the Cable End
Wrap one strip of mastic, stretching slightly, around the cable jacket. Bend all neutral wires straight back over the mastic and along the cable, pressing the wires into the mastic. Wrap the second strip of mastic completely around the outer jacket, overlapping the neutral wires embedded into the first mastic strip. Use a third strip of mastic if needed to build up the outer diameter in the area of the first mastic location. Cover all mastic with vinyl tape. Remove the insulation shield and insulation from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors and immediately install the compression lug. Rotate the lug to spread the inhibitor. Position the compression lug so the contact threaded hole aligns with the bushing bore. Crimp the lug according to the crimp chart packaged with the lug, starting at the crimp line mark and rotating 180 degrees for each successive crimp. Carefully wipe excessive inhibitor from the outside of the lug and cable. Remove the insulation shield as shown in the cable cut back template. Bevel the insulation end a maximum of 1/8 inch. Thoroughly clean the insulation to remove all traces of conductive residue.
- Assemble the Elbow Housing
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant; do not substitute. Keep the insulation clean of dirt and grime. Slide the elbow connector onto the cable with a back-and-forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug’s threaded hole. Thread the probe into the lug by hand, taking care not to cross-thread. The probe must turn freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Connect Concentric Neutral
Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and/or rolling the seal down. Insert one end of a separate copper wire (No. 14 AWG / 2.5mm) or equivalent through the grounding eye on the elbow. Twist the copper wire tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Provide adequate slack in the wires for elbow operation.
- Connect Elbow to Bushing Plug
DANGER: Ensure the transformer and elbow are known to be de-energized before lubricating and connecting. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. Securely fasten the hotstick to the loadbreak connector pulling eye. Confirm positive control of the elbow connector. Insert the probe tip approximately 2 inches (50mm) into the bushing. Immediately push the elbow home with a fast, firm, straight motion, using sufficient force to engage the internal lock on the elbow connector and bushing interface. WARNING: Do not operate by hand; loadbreak connectors must be operated with a fully insulated hotstick type live-line tool.
- Perform Voltage Test (162LRJS only)
If using the 162LRJS with an integral capacitance test point, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly in line with the test point assembly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter that is used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. WARNING: Contamination, moisture, dirt, or use of the wrong measuring equipment can provide a false 'no voltage' indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection has been made, clean and lubricate the inside surface of the cap with silicone lubricant supplied and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.