Contact for Pricing
Minimum Qty: 15
Multiplier: 15
*Contact for lower quantities*
Overview
- 15kV voltage rating
- 200 Amp current rating
- Accommodates cable insulation diameters from 0.805 to 1.060 inches (Insulation Letter Code 'C')
- Designed for 2/0 stranded wire size
- Features a bi-metal compression lug for secure connections
- Includes a test point for circuit testing
Specifications
Amperage Rating | 200 A |
Application | 15kV, 200 Amp |
Color | Black |
Conductor Range | 2/0 STR/COMPR AWG , 3/0 SOL/COMPT AWG |
Connection | Push-In |
Connection Type | Loadbreak Elbow Connector with Test Point |
Connection Type | Compression Lug |
Current Rating | 200 A |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Material | Housing - EPDM-Rubber |
Material | Bi-Metal Compression Lug |
Material | Bi-Metal |
Series | 162LR |
Size | 7.76 inch (197.1 mm) X 9.03 inch (229.4 mm), 2.92 inch (74.2 mm) Diameter |
Size | Cable Insulation Diameter 0.805 inch to 1.060 inch, 2/0 Stranded Wire Size |
Size | 0.805-1.060 Inch Cable Insulation Diameter |
Special Features | 15kV, 200 Amp Loadbreak Elbow. Fully shielded, fully submersible molded rubber housing. 100 percent peroxide-cured construction includes insulation and conductive EPDM materials. Provision for hot stick operation. Provision for ground wire connection. Wide cable range with minimum number of sizes. Long bi-metal compression lug is standard. Non-corrosive capacitive test point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Loadbreak Elbow Connector with Test Point |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.1300 L |
Package Weight (Metric) | 0.9660 kg |

162LR-B5250-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.635 inch to 0.905 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS-G3 Jacket Seal and Grounding Kit Included.
162LR-C5250-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS-G3 Jacket Seal and Grounding Kit Included.
162LR-C5260
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 3/0 Stranded Wire Size, Bi-Metal Compression Lug
162LR-C5250-S
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43. 200ECS Jacket Seal Included.
162LR-C5270-SG3
200 Amp, 15kV, Loadbreak Elbow Connector, Cable Insulation Diameter 0.805 inch to 1.060 inch. Bi-Metal Compression Lug. Conductor Size AWG Compressed Stranded 4/0 /Solid 250 /mmSquared 126.67. 200ECS-G3 Jacket Seal and Grounding Kit Included.
162LR-C5270
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 4/0 Stranded Wire Size, Bi-Metal Compression Lug
162LR-C5240
15kV 200 Amp, Loadbreak Elbow Connector with Test Point, .805 inch - 1.060 Inch Cable Insulation Diameter, 1/0 Stranded Wire Size, Bi-Metal Compression LugFrequently Asked Questions
What is the maximum voltage rating for this loadbreak elbow connector?
The ABB 162LR-C5250 loadbreak elbow connector has a maximum operating voltage rating of 15kV.
What is the continuous current rating of the 162LR-C5250 connector?
The 162LR-C5250 connector is rated for 200 Amps of continuous current.
What cable insulation diameter range does this connector support?
This loadbreak elbow connector is designed to fit cable insulation diameters between .805 inches and 1.060 inches.
What wire size is compatible with the bi-metal compression lug?
The bi-metal compression lug is designed for use with 2/0 stranded wire.
Does this connector have a test point for circuit verification?
Yes, the 162LR-C5250 features a test point for convenient and safe circuit testing.
How to Install 161LR/162LR Loadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of 161LR and 162LR Loadbreak Elbow Connectors, including cable preparation, elbow assembly, and grounding procedures.
Estimated time: 1h 30m
Tools needed:
Probe Wrench, Wire brush, Crimp tool (specific to compression lug), Hotstick, Cable cutting tool, Wire strippers
Supplies needed:
Compression Lug, Probe, Lubricant (Do Not Substitute), Separate copper wire (No. 14 AWG / 2.5mm or equivalent), Wire connectors (for neutral connection), Vinyl tape (if using jacketed cable with drain wires), Optional: Sealing kit components (e.g., cold shrink tube, conductive copper tape)
- Perform Initial Safety Checks and Cable Training
DANGER: Confirm all apparatus is de-energized before beginning installation. Do not touch or move energized products in the work area. Inspect all package contents for completeness and damage. Verify all components are compatible and fit properly with your cable and mating products. Thread the probe into the compression lug by hand to check for free movement; replace any damaged components if resistance is encountered. Train the cable to ensure sufficient slack (24 to 36 inches or 610 to 914mm) beyond the bushing centerline for ease of operation.
- Prepare Cable Jacket and Neutral Wires
Cut the cable squarely at the centerline of the bushing. For non-jacketed concentric neutral cable, bind the neutrals 7-3/4 to 8 inches (195 to 203mm) back from the bushing center and unwrap neutral wires to the binding. For jacketed concentric neutral cable, remove the outer jacket 9-5/8 inches (240mm) back from the bushing centerline and unwrap neutral wires past the bushing centerline. For jacketed cable with drain wires, remove 9-5/8 inches (240mm) of the outer jacket, unwrap drain wires, bind them, fold them back, and wrap vinyl tape around the cable covering the wire ends. For jacketed copper tape shield cable, remove 9-5/8 inches (240mm) of the outer jacket and 7-1/8 inches (180mm) of the copper tape shield; wrap conductive copper tape (if supplied with kit) over the end of the copper shield to hold it in place. If using a cold shrink sealing kit, slide the cold shrink tube onto the cable, loose end first.
- Prepare Conductor and Insulation
Remove the shield and insulation 2-1/8 inches (55mm) from the cable end, cutting squarely and taking care not to nick the conductor. Wire brush bare aluminum conductors immediately and install the compression lug. Rotate the lug to spread inhibitor. Position the lug so the contact threaded hole aligns with the bushing bore. Crimp the lug starting at the crimp line mark, rotating 180 degrees for each successive crimp. Carefully wipe excess inhibitor from the lug and cable. Remove the insulation shield 6-7/8 inches (175mm) from the end of the main insulation. Bevel the insulation end 1/8 inch (5mm) maximum. Thoroughly clean the insulation to remove all traces of dirt or excess inhibitor.
- Assemble the Elbow Connector
Lubricate the cable insulation and the inside of the elbow housing with the supplied lubricant. DO NOT SUBSTITUTE. Keep insulation clean of dirt and grime. Slide the elbow connector onto the cable using a back-and-forth twisting motion. Wipe off all excess lubricant. Align the elbow with the compression lug's threaded hole. Thread the probe into the lug by hand, ensuring it turns freely for approximately four turns before becoming snug. Tighten the probe with the supplied wrench until the wrench bends.
- Complete Grounding and Neutral Connection
Insert one end of a separate copper wire (No. 14 AWG / 2.5mm or equivalent) through the grounding eye on the elbow. Twist it tightly, taking care not to damage the eye. Twist all neutral wires together and connect them to ground using an appropriate connector. Ensure adequate slack in the wires for elbow operation. If using a cold shrink grounding kit, refer to its specific instructions to complete the installation.
- Connect Elbow to Bushing Plug
DANGER: CONFIRM THAT THE TRANSFORMER AND ELBOW ARE DE-ENERGIZED before connecting. Lubricate the receptacle portion of the elbow connector and the mating bushing with the supplied lubricant. Securely fasten a hotstick to the loadbreak connector pulling eye. Insert the probe tip approximately 2 inches (50mm) into the bushing. Immediately push the elbow home with a fast, firm, straight motion, using sufficient force to engage the internal lock. DO NOT HOLD IN THE PARTIALLY INSERTED POSITION.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.