Contact for Pricing
Overview
- Easy maintenance: hinged front cover allows quick access to all components; condenser coil can be cleaned while unit is still mounted to the cabinet
- Smooth surface with minimal use of visible fasteners
- Cleanable reusable aluminum mesh filter protects coils for maximum cooling performance
- R134a, R513A or R407C Refrigerant
- Models for 115, 230 and 460 single phase VAC power input
- Operating temperature range from -40 F/-40 C to 131 F/55 C (with optional low-ambient package)
- Reliable mechanical thermostat located behind the filter of the unit
- Robust reciprocating compressor
- Low-carbon mild-steel sheet-metal cover for rugged factory and outdoor environments
- High-performance fans and blowers designed for densely packed enclosures
Specifications
Amperage Rating | 2.5 A |
Application | Controls and Drives;Corrosive Environments;Hygienic Environments;Power Distribution |
Application | Power Distribution; Corrosive Environments; Hygienic Environments; Controls and Drives |
Btu Rating | 1,600 |
Color | Brushed |
Color | Unpainted |
Current Rating | 2.2/2.2A |
Depth | 222 mm |
Depth | 8.75 in |
Finish | Brushed #3 |
Frequency | 50/60Hz |
Frequency Rating | 50/60 Hz |
Frequency Rating, Maximum | 60 Hz |
Frequency Rating, Minimum | 50 Hz |
Height | 584 mm |
Height | 23 IN |
Housing Material | Stainless Steel |
Material | Stainless Steel 304 |
Material | SS304 |
Max Current | 1.7 A |
Mechanical Advantage | Stainless steel optional |
Model | Surface Mounted |
Nema Rating | Type 4X |
NEMA Rating | 4X Watertight, corrosion-resistant |
Nominal Capacity Btu/h | 1,733 Btu/h |
Nominal Capacity Watts | 508 W |
Nominal Voltage | 230 V |
Number Of Phases | 1 |
Operating Temperature | 131 deg F |
Operating Temperature | -40-131 °F |
Operating Temperature | -40-55 °C |
Power | 469 W |
Product Family | ProAir |
Protection Rating | NEMA Type 4X |
Remote Access Control | No |
Series | ProAir Harsh Environment |
Size | 4X CR23 |
Thickness | 1.21 mm |
Thickness | 18 ga |
Thickness | 51.40mm (2.024") |
Type | Air Conditioners |
Voltage AC | 200-250 V |
Voltage Rating | 230V |
Voltage Rating | 230 VAC |
Weight | 51.7 lb |
Weight | 26 kg |
Width | 254 mm |
Width | 10 IN |
Package Dimensions (L x W x H) | 15.3 IN x 12.7 IN x 26.3 IN |
Package Dimensions (L x W x H) | 38.862 cm x 32.258 cm x 66.802 cm |
Package Weight (Imperial) | 51.700 L |
Package Weight (Metric) | 23.451 kg |
How to Install the CR230226G002 Air Conditioner
This guide provides step-by-step instructions for the installation and initial setup of the CR230226G002 air conditioner, ensuring proper mounting, wiring, and configuration.
Estimated time: 45m
Tools needed:
Screwdriver, Wrench, Wire strippers, Multimeter
Supplies needed:
Mounting screws, Washers, Gasket kit
- Inspect the air conditioner
Check for any visible damage and verify functionality by connecting the power cord to a properly grounded power supply. Ensure the unit operates without excessive noise or vibration for 5-10 minutes.
- Prepare the mounting area
Using the cutout dimensions provided in the manual, prepare the air 'IN' and 'OUT' openings and the mounting bolt hole pattern on the enclosure.
- Install gaskets
Apply the gaskets from the mounting gasket kit to the rear of the air conditioner, ensuring proper placement as indicated in the manual.
- Mount the air conditioner
Secure the air conditioner to the enclosure using the provided mounting bolts and washers. Start bolts by hand to avoid cross-threading, then tighten with a wrench.
- Connect the power supply
Refer to the nameplate for electrical requirements and connect the power cord to a properly grounded power supply. Ensure the circuit is fused with a slow-blow or HACR circuit breaker.
- Adjust the temperature controller
If equipped with an automatic temperature controller, verify that it is preset for standard operation. If adjustments are needed, disconnect power, access the controller, and adjust the set point as required.
- Calibrate the system
After installation, allow the unit to remain upright for at least 5 minutes before starting. Turn on the unit and monitor for proper operation, ensuring all fans and the compressor are functioning.
Frequently Asked Questions about nVent
What industries and applications are nVent products used for?
nVent products are engineered for critical infrastructure and industrial applications across multiple demanding sectors. Key markets include Construction, Data Centers, Defense, Healthcare, Mining, Oil & Gas Refineries, Power Plants, Rail/Transit, Renewable Energy, Security, Ship Building, Steel Mills, Telecom, and Utilities. Their solutions are designed to withstand extreme environmental conditions, with temperature ranges from -55°C to 105°C and specialized features like UV resistance, oil resistance, and flame resistance.
What environmental ratings do nVent products have?
nVent enclosures feature comprehensive environmental ratings, including UL 508A, CSA, and NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications. They are rated IEC 60529 IP66, providing robust protection against dust, water, and corrosion in both indoor and outdoor environments. These products operate effectively in temperatures ranging from -40°F to 266°F, with enhanced UV inhibitors for outdoor weathering and oil-resistant gaskets for superior sealing.
What accessories are available for nVent products?
nVent offers a comprehensive range of accessories across multiple product lines, including EMC accessories like bonding cable clamps and strain reliefs, inline accessories such as lock inserts and mounting brackets, CONCEPT accessories including panel conversion kits and rack-mount angles, and seismic accessories for specialized mounting requirements. Key accessory categories include grounding kits, DIN rail mounting solutions, panel supports, handles, and various mounting hardware compatible with different enclosure types.
What certifications and standards do nVent products comply with?
nVent products meet critical international certifications including UL (United States), CSA (Canada), CE (European Community), and EAC (Russia). Our products are designed to comply with rigorous industrial standards such as NEMA enclosure ratings, IEC 60529 IP ratings, and international safety standards across multiple industrial markets including oil & gas, power, manufacturing, and infrastructure.
What is nVent's warranty policy?
nVent offers a standard 18-month warranty from invoicing date for most automation products, covering defects in workmanship and materials. The warranty requires proper transportation, handling, storage, and installation within specified environmental conditions. Warranty coverage includes repair or replacement at nVent's discretion, with certain conditions such as authorized service repairs and operation within designed capacity limits.
What technical support does nVent offer?
nVent offers comprehensive technical support through multiple global contact centers across North America, South America, Europe, Middle East, India, and Asia. Customers can reach technical experts by phone at regional numbers, with the North American headquarters in Minneapolis, MN providing primary support at +1.763.421.2240. Additionally, nVent provides online support resources through their website, including CAD drawing downloads and an 'Ask The Expert' feature to assist with product technical inquiries.