Contact for Pricing
Overview
- Hub size: 3 inches
- Outer jacket diameter range: 2.79–3.06 inches
- Aluminum construction with PVC coating for corrosion resistance
- Integral sealing chamber with liquid or putty sealant options
- Disconnectable design for reduced cable preparation time
Specifications
Application | For Hazardous Locations |
Color | Black |
Finish | PVC |
Material | Aluminum |
Size | 3 Inches |
Standard | CSA 23086 |
Type | Teck Cable Fittings |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 6.0000 L |
Package Weight (Metric) | 2.7220 kg |

ST250-478PVC
Star Teck PVC coated jacketed cable fitting hub size 2-1/2 inches. Range over jacket 2.58 inches minimum, 2.84 inches maximum.
95138
Clamp-on service entrance cap for 4-inch EMT and rigid/IMC conduit. It is made of aluminum with a silver color and no additional finish. The enclosure is listed as Weatherhead.
STX300-478PVC
Star Teck XP hazardous location PVC coated jacketed cable fitting hub size 3 inches Range over jacket 2.580-2.840 inches.
STX250-475PVC
Star Teck XP hazardous location PVC coated jacketed cable fitting hub size 2-1/2 inches Range over jacket 2.300-2.565 inches.
ST300-479SS
Stainless steel fitting with a hub size of 3 inches and will handle outer jacket diameters from 2.79 to 3.06 inches.
STX075-465PVC
Aluminum PVC coated fitting with a hub size of 3/4 inch and the outer jacket diameters from 0.725 to 0.885 inch.
UYY 00 SP
Aluminum 2-3/4 inch Service Entrance Compression Splice for Wire Range, End A: 1/0 ACSR, 1/0 STR, Yellow, End B: 1/0 ACSR, 1/0 Stranded, Yellow, Die: 5/8, with Seal Plug.How to Install the STX300-479PVC Star Teck PVC Cable Fitting
This guide provides detailed instructions for installing the STX300-479PVC Star Teck PVC cable fitting, including cable preparation, assembly, and sealing with liquid compound. This fitting is suitable for hazardous locations and requires careful adherence to safety procedures and sealing compound application.
Estimated time: 4h
Tools needed:
Hacksaw, Strap wrenches, Wire strippers, Multimeter, Damp cloth
Supplies needed:
SC4-KIT-1 LIQUID SEALANT (6 units), Fiber damming material, Lubricant, Gloves and other PPE
- De-energize Circuits and Prepare Workspace
WARNING: Before beginning installation or performing maintenance, verify that all circuits are de-energized to prevent the risk of electrical shock. Ensure a qualified electrician performs the installation in accordance with national and local electrical codes. Gather all required tools and supplies.
- Prepare Cable Armor and Jacket
Determine the required working length of conductors inside the enclosure. Remove a portion of the outer jacket to expose the cable armor. Carefully cut the armor using a hacksaw, taking caution not to nick or cut the conductor insulation. Trim the outer jacket to the appropriate strip length as indicated in the product table for your specific cable type (refer to the document's table for STX300-479PVC).
- Prepare and Position Cable Boot
Choose a method to cut the cable boot: Method 1 involves unscrewing the gland nut, forcing the square-cut cable into the boot, and cutting the boot in front of the cable. Method 2 involves stripping the cable jacket off the armor and progressively cutting slices off the boot until it snugly slides onto the armor. Apply lubricant where indicated before screwing the gland nut. Feed the cable through the gland nut opening and push until the cable armor firmly hits the end stop.
- Tighten Gland Nut and Disassemble Fitting
Tighten the gland nut until an appropriate seal is obtained, or to the maximum torque specified in the product table for STX300-479PVC. Ensure the bushing seals evenly around the cable's outer jacket and the cable remains centered for an optimal seal. Next, disassemble the hub from the body sub-assembly by loosening the union, then unscrew the sealing chamber from the body sub-assembly.
- Prepare Conductors and Pack Damming Material
Trim the inner jacket to a length of 1/8 to 3/8 inches to expose the conductor bundle. If working with shielded data cables, refer to Section 2 of the original document for additional steps to remove shields and filler materials. Pack the fiber damming material tightly into all voids between the conductors and the body. Spread the strands of any uninsulated grounding conductor, if applicable.
- Apply Liquid Sealing Compound (SC4-KIT-1)
Screw the sealing chamber back onto the body sub-assembly until it completely seats. Position the cable and fitting vertically. Mix the SC4-KIT-1 liquid sealing compound according to its package instructions. For STX300-479PVC, fill approximately HALF of the sealing chamber. Wait 2 hours for this portion to set, then fill the remaining half of the sealing chamber to the top. CAUTION: Wear gloves and other proper PPE. Remove all excess compound from the outside of the sealing chamber with a damp cloth; do not use abrasive cleaners.
- Mount Hub and Secure Assembly
Mount the hub in the desired location. After the sealing compound has solidified (approximately 1 hour after the final pour), place the encapsulated assembly into the hub. Secure it in position by tightening the union until it bottoms out, ensuring metal-to-metal contact.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.