Contact for Pricing
Overview
- 2-inch hub size for teck cable systems
- Handles outer jacket diameters from 2.1 to 2.375 inches
- Steel core with PVC coating for corrosion resistance
- Pop-on design eliminates disassembly during installation
- Splined gland and gripping features for secure cable termination
Specifications
Color | Black |
Finish | PVC |
Material | Steel |
Size | 2 Inches |
Standard | UL E38947, CSA 23086, CSA 4484 |
Type | Teck Cable Fittings |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 2.8000 L |
Package Weight (Metric) | 1.2700 kg |

ST200-551SPVC
Steel fitting with a hub size of 2 inches and will handle outer jacket diameters from 1.9 to 2.187 inches. PVC coated.
CCOP250
One piece strut clamp with saddle designed to secure rigid/EMT conduit or cable perpendicular to strut. It is made of steel with a galvanized finish. The clamp fits 2-1/2 in EMT and 2-1/2 in RMC and has a static load rating of 350 lbs.
ST250-478SPVC
Steel fitting with a hub size of 2-1/2 inches and will handle outer jacket diameters from 2.58 to 2.84 inches. PVC coated.
STX050-462S
Star Teck hazardous location steel jacketed cable fitting. Hub size of 1/2 inch. Range over jacket from 0.525 - 0.650 inch.
STX050-464SPVC
Steel PVC fitting with a hub size of 1/2 inch and the outer jacket diameters from 0.6 to 0.76 inch.
ASR1114-B2-10
Type ASR-ALCUL Splice Reducer with Solid Barrier Wire Stop, Conductor Range 14 - 1/0 AWGFrequently Asked Questions
What are the key features of this cable gland?
It offers excellent pullout strength, robust metallic construction, quick "pop-on" installation, and provides grounding continuity for cable armor.
What does the "SPVC" suffix mean for the product?
The "S" indicates a steel version, and "PVC" means it has a PVC coating. This option is available for aluminum and steel constructions.
What certifications does the ST200-474SPVC hold?
It conforms to CSA E60079-0/-7, CSA C22.2 No.25/-174, UL2279, UL514B/50, CSA C22.2-18.3/-94, and RoHS.
What is the cable armor range for the ST200-474?
The range over the cable armor for ST200-474 is from 2.015 inches minimum to 2.280 inches maximum.
What is the cable jacket range for the ST200-474?
The range over the cable jacket for ST200-474 is from 2.100 inches minimum to 2.375 inches maximum.
What is the NPT thread size for part number ST200-474?
The NPT thread size for part number ST200-474 is 2 inches.
What materials are available for the cable gland?
The cable gland is available in copper-free aluminum, zinc-plated steel, and stainless steel options.
What ingress protection rating does the product have?
The product has an ingress protection rating of Type 4 / 4X.
What is the operating temperature range for the fitting?
The normal operating temperature range is -40 to +90°C (-40 to +194°F).
What types of cables are compatible with this fitting?
It is suitable for jacketed Teck and ACWU, armored control and instrument (ACIC), and Type MC cables including jacketed interlocking and corrugated metal clad.
How to Install ST200-474SPVC Star Teck™ PVC Cable Fittings
This guide provides step-by-step instructions for the safe and proper installation of ST200-474SPVC Star Teck™ PVC cable fittings (part of the ST050-462PVC to ST350-483PVC series), including preparing the cable and securing the fitting to ensure an optimal seal.
Estimated time: 30m
Tools needed:
Strap wrenches, Hacksaw
Supplies needed:
ST200-474SPVC Cable Fitting, Cable, Wire pulling lubricant (optional, Cat. No. 15-236)
- Select the Appropriate Fitting and Disconnect Power
Before starting, read and understand all instructions and safety information. WARNING: Disconnect power to the system before installation to prevent risk of shock. Select the appropriate Star Teck™ PVC cable fitting (e.g., ST200-474SPVC) that matches your enclosure and cable specifications. CAUTION: Ensure installation is performed by a qualified electrician in accordance with national and local electrical codes.
- Prepare the Cable
Determine the required working length of the cable. Carefully remove a portion of the outer jacket to expose the cable armor. Use a hacksaw to cut the armor, then trim the outer jacket to achieve the exposed armor strip length specified in the product table (refer to Figures 1 and 2 in the original document for visual guidance).
- Prepare the Cable Boot
Determine where to cut the cable boot using one of two methods. Method 1: Unscrew the gland nut from the body, force the square-cut cable into the boot, and then cut the boot in front of the cable (Figure 3A). Method 2: Strip the cable jacket off the armor, then progressively cut slices off the boot until the opening can snugly slide onto the armor (Figure 3B). CAUTION: Do not over strip the boot; there should be no gaps between the boot and the cable jacket.
- Insert Cable into Gland Nut
Feed the prepared cable through the gland nut opening. Push the cable until its armor firmly hits the internal end stop of the fitting (refer to Figure 4 in the original document).
- Secure and Seal the Fitting
Using strap wrenches, tighten the gland nut until an appropriate seal is obtained or to the maximum torque specified in the product table for your specific fitting (refer to Figure 5 in the original document). Ensure the bushing seals evenly around the cable's outer jacket and that the cable remains centered to achieve an optimal and secure seal.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.