ABB Installation Products R2T28J4-N2330 Ranger2 Termination for 25/28KV outdoor application, cable insulation diameter 1.30…
UPC: 075114373074
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 25/28 kV voltage rating for outdoor power distribution
- Accommodates cable insulation diameters from 1.30 to 2.10 inches
- Compatible with Concentric Neutral (CN) and Jacketed Concentric Neutral (JCN) cables
- Copper 2-hole spade connector for #2 - 1250 kcmil conductors
- Designed for stranded/compressed 500 kcmil or compact/solid 600 kcmil conductors
Specifications
Application | Cable Termination, Outdoor Application, 28kV |
Cable Type | Concentric Neutral Wire |
Color | Gray |
Conductor Size | 500 to 600 kcmil |
Connection Type | 2-Hole Spade |
Earthing | Products Includes Their Own Grounding System |
Material | Copper |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Size | 1.30 - 2.10 inches |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 28 kV |
Voltage Rating | 25/28 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

R2T28M4-N0330-B4
Ranger2 Termination. Type - Outdoor, 28kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - 1.30 inch - 2.10 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 330 -Stranded or Compressed 500 kcmil or Compact or Solid 600 kcmil. Cable Mounting Bracket B4 - 1.80 to 2.40 inch (45-61mm).
R2T15J1-H0300
15 kv, Ranger2 Terminator, OutDoor, Concentric Neutral/Jacketed Concentric Neutral, .64 inch to 1.12 inch Insulation Range, Connector Type - Aluminum 1 hole Spade #2-500 kcmil, Conductor Code 300 - Standard or Compressed 350, Compact or Solid 400.
PCT1-3
15kV, Housing Only, Pre-Molded Cable Termination, 2-Hole Spade Lug, For use with Insulation Diameter Range from .830 inch to 1.180 inch.
PCT2-3
25kV, Housing Only, Pre-Molded Cable Termination, 2-Hole Spade Lug, For use with Insulation Diameter Range from .830 inch to 1.180 inch.
69TCT232231PNAN
69kV, Transmission Cable Termination (TCT). Base and Top Module, Housing Size 3, Connection Type 2 - 2 Hole NEMA, Connector Type - Copper, Conductor Size 31P, Metallic Screen Kit - Not Required, Armour Kit - Jacketing Tape and Mastic, No Bracket Required.
R2T15J1-N0380
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250 kcmil, Stranded or Compressed 700, Compact or Solid 900.
R2IT15J1-N0380
Indoor Ranger2 Cable Termination. 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral. Insulation Range - .64 inch - 1.12 inch. Aluminum 2-Hole Spade #2-1250 kcmil, Conductor 750 Stranded/Compressed or 900 Compact/Solid
69TCT23NNNNNNBN
69kV, Transmission Cable Terminator, Base and Top Module, Housing Size 3 - Bore Diameter 1.975 inch, Type of Connection - None, Connector Type - None, Conductor Size - None, Metallic Screen Kit - None, Armour Kit - Heat Shrink, No Bracket RequiredFrequently Asked Questions
What is the IEEE classification for outdoor use?
The R2T28 has an IEEE Classification of Outdoor = Class 1A.
Where can I find installation instructions?
Installation instructions are available as IS-1134 for R2T28J, IS-1135 for R2T28M, and IS-1136 for R2T28L.
What is the maximum altitude for operation?
The maximum altitude range for operation is 3300 feet (1005 m).
What power system frequency is supported?
The R2T28 supports a power system frequency range of 48 to 62 Hz.
What is the operating ambient temperature range?
The R2T28 operates within an ambient temperature range of -22 to +149 °F (-30 to +65 °C).
What is the maximum design voltage to ground?
The maximum design voltage to ground for the R2T28 is 16 kV.
What is the voltage rating of the R2T28?
The R2T28 has a voltage rating of 25/28 kV.
What cable types are compatible with the R2T28?
The R2T28 units accommodate popular XLP and EPR cable types and shield constructions.
What cable sizes does the R2T28 termination support?
The R2T28 termination supports cable insulation diameters from 0.84 in (21.3 mm) to 2.10 in (53 mm), covering #2 AWG through 1250 kcmil.
What is the IEEE classification for outdoor use?
The R2T28 has an IEEE Classification of Outdoor = Class 1A.
How to Install the R2T15/28J Ranger 2 Cable Termination
This guide provides step-by-step instructions for the safe and proper installation of 15kV & 28kV Ranger 2 Cable Terminations for indoor/outdoor applications on concentric and jacketed concentric neutral cables. All apparatus must be de-energized during installation. This product should be installed only by competent personnel trained in high voltage electrical equipment safety.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Approved solvent, Aluminum oxide abrasive (grit 120 or finer, optional)
Supplies needed:
Silicone Rubber Termination, Lubricant, Grey Silicone Rubber Tape, Sealing Mastic, Gloves, Elastimold copper or aluminum lugs, Cable Support Bracket (optional), High voltage insulated cap(s) or connector(s), Vinyl tape or binding wire
- Prepare the Cable
Verify the cable size fits within the kit range. Train the cable into position and cut to the required length, allowing sufficient neutral wire length for grounding. Prepare the cable jacket, semi-con, and insulation to specified dimensions, accounting for terminal lug depth and conductor growth during crimping.
- Apply Mastic and Secure Neutral Wires
Using 50% stretch, carefully wrap one band of sealing mastic around the cable jacket 1/4” (6mm) from the jacket end; cut flush without overlap. Bend neutral wires back over and press into the mastic, securing them to the cable jacket 4-6” (100-150mm) from the cut edge using vinyl tape or binding wire. Apply a second mastic band over the neutral wires and previous mastic, cutting flush. Wrap two half-lapped layers of vinyl tape over the mastic seal.
- Install the Lug or Connector
If using non-Elastimold lugs that won't fit through the termination core, clean the insulation and slide the termination onto the cable before installing the lug. Position the connector/lug and crimp according to directions, leaving the last 1/4” to 3/8” uncrimped. Remove excess oxide inhibitor and sharp crimp flashings.
- Clean Cable Insulation and Lug Barrel
Wipe the cable insulation with an approved solvent, ensuring it does not touch the semi-con insulation shield. If necessary, use aluminum oxide abrasive (grit 120 or finer) on the insulation only, being careful not to reduce the cable insulation diameter. Do not use abrasive on the semi-con insulation shield.
- Create Lug Base Moisture Seal
Wrap a band of grey silicone rubber tape around the base of the terminal lug to create a track-resistant moisture seal. If the barrel diameter is equal to or greater than the cable primary insulation, the tape band should not exceed 2 layers. If smaller, use the tape strip to form the tape band equal to the insulation diameter.
- Apply Silicone Grease and Prepare Termination Core
Apply a liberal coating of silicone grease to the edge of the semi-con insulation shield to fill the step at the cut-off. For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom.
- Install Termination Body
Slide the termination body onto the cable, aligning it with the forward edge of the mastic seal. Carefully remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Do not push or pull the termination assembly while removing the core material.
- Lubricate and Fold Down Skirt
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal.
- Complete Lug Area Moisture Seal
Using the remaining grey silicone rubber tape, complete the lug area moisture seal. Overlap the termination insulator by approximately 1” and extend the tape wrapping over a non-crimped region of the lug/connector barrel with a half-lap configuration.
- Ground Neutral Wires and Confirm High-K Step
Twist the concentric neutral wires together and connect them to the system ground. Confirm that the High-K step does not exceed 1.5”.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.