ABB Installation Products R2T15M1-N0270 Ranger2 Termination for 15KV outdoor application, cable insulation diameter 0.64 - 1.12…
UPC: 783786772964
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15kV outdoor termination with shrink-fit housing for 0.64"–2.10" insulation diameter cables
- Accommodates #2 AWG to 1250 kcmil conductors (stranded/compressed or compact/solid)
- Supports Tape Shield, Wire Shield, and UniShield cable constructions (XLP/EPR insulation)
- Non-tracking silicone housing with 4 sheds for superior creepage and strike distance
- Field-removable center core for simplified installation; optional insulating sleeves available
Specifications
Application | Cable Termination, Outdoor Application, 15kV |
Cable Type | Copper Tape Shielded Wire |
Color | Gray |
Conductor Size | 4/0 AWG , 250 kcmil |
Connection Type | 2-Hole Spade connector |
Earthing | Products Includes Their Own Grounding System |
Material | Aluminum |
Mounting | Product Need to have Cable Holder (not included) |
Number Of Terminals | (1) Single Phase |
Series | Ranger2 |
Size | 0.64-1.12 inches (insulation diameter) |
Special Features | Silicone Rubber Housing. Lightweight, Compact Design. Pull-Down Tabs for Easy Installation. Thick Wall Construction |
Standard | IEEE 48 |
Type | Cable Termination - Outdoor - Ranger2 |
Voltage Rating | 15 kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

PCT10270-3
15kV, Single Piece Terminator (Class 1), Two Hole Spade Lug. Power Cable Termination, Conductor Size - 4/0 Stranded/Compressed, Use for Insulation Diameter Range from .640 to 1.070 inches.
R2T15M1-N0210
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 210 -Stranded or Compressed N/A Compact or Solid #2.
R2T15M1-H0220
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Tape Shield/Wire Shield/ Unshield, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 1-Hole Spade #2-500 kcmil, Conductor Code - 220 -Stranded or Compressed #2 Compact or Solid #1.
R2T15L4-N0410
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for LC Shield Tape Shield/Wire Over Tape Shield. includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000.
R2T15J4N0410-B3
Ranger2 Termination for 15KV outdoor application, cable insulation diameter 1.30 - 2.10 inches for Concentric Neural and Jacketed Concentric Neutral Cable, includes Aluminum 2-Hole Spade connector for #2-1250 kcmil, Stranded or Compressed 1000. Stainless Steel Mounting Bracket 1.45 inch - 1.95 inch (37-50mm)
R2T15J1-N0240-B1
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 240 -Stranded or Compressed 1/0 Compact or Solid 2/0. Cable Mounting Bracket - B1 - Stainless Steel - Size .80 inch - 1.25 inch.
R2T15J1-N0230
Ranger2 Termination for 15KV outdoor application, cable insulation diameter .64 - 1.12 inches for Concentric Neural and Jacketed Concentric Neutral Cable, Aluminum 2 Hole Spade #2-1250kcmil, Stranded or Compressed #1 /Compact or Solid 1/0.
R2T15J1-N0220
Ranger2 Termination. Type - Outdoor, 15kV, Cable Type - Concentric Neutral/Jacketed Concentric Neutral, Insulation Range - .64 inch - 1.12 inch, Connector Type - Aluminum 2-Hole Spade #2-1250 kcmil, Conductor Code - 220 -Stranded or Compressed #2 Compact or Solid #1.Frequently Asked Questions
What cable insulation diameters does the R2T15M1-N0270 support?
The Ranger2 Termination supports cable insulation diameters ranging from 0.64 to 1.12 inches.
What cable types are compatible with this ABB termination?
This termination is compatible with Tape Shield, Wire Shield, and UniShield cable types.
What conductor sizes can the spade connector accommodate?
The included aluminum 2-hole spade connector accommodates #2 AWG up to 1250 kcmil conductors.
What types of conductors are supported by the connector?
The connector supports stranded or compressed conductors from #2 to 1250 kcmil, and compact or solid conductors from 4/0 to 250 kcmil.
Is this termination suitable for indoor use?
No, this Ranger2 Termination is specifically designed for 15KV outdoor applications.
How to Install the R2T15M1 Silicone Rubber Termination for Tape Shielded Cables
This guide provides step-by-step instructions for the safe and proper installation of the R2T15M1 Ranger 2 Shrink-fit Silicone Rubber Termination on tape shielded cables, including cable preparation, ground braid installation, and termination placement.
Estimated time: 2h
Tools needed:
Cable preparation tools (knife, wire strippers), Crimping tool, Approved solvent, Abrasive (aluminum oxide, grit 120 or finer, optional), Measuring tape/ruler
Supplies needed:
R2T15M1 Silicone Rubber Termination kit, Lubricant (Silicone grease), Gray silicone rubber electrical tape, Sealing mastic, Copper foil tape, Preformed ground braid, Constant force spring, Terminal lug/connector, Vinyl tape
- Safety First: De-energize Apparatus and Inspect Components
De-energize all apparatus in the work area before beginning installation. Do not touch or move energized products. Inspect all kit contents for completeness and damage. Verify all components are compatible with the cable and mating parts. Read the entire installation instructions thoroughly before starting.
- Prepare the Cable for Termination
Confirm the cable size is within the insulation range specified in the Termination Selection Chart. Train the cable into its final position and cut it to the required length, allowing for terminal lug depth and growth allowance. Remove the cable jacket to the length specified as 'A' in Table 1, plus 2 inches (50mm) for terminal lug depth and growth allowance. Remove the tape shield 1 inch (25mm) from the jacket end. Secure the edge of the tape shield with a single wrap of the supplied copper foil tape to prevent unrolling. Provide additional exposed conductor distance for aluminum lugs: 1/4 inch (6mm) for 2/0-350 Kcmil, 1/2 inch (13mm) for 400-650 Kcmil, and 3/4 inch (19mm) for 750-1000 Kcmil.
- Install the Ground Braid Assembly
Wrap one band of sealing mastic around the cable jacket, 1/4 inch (6mm) from the jacket end, using 50% stretch. Cut the mastic flush without overlapping. This band also serves as a termination positioning marker. Position the preformed ground braid with its short tail over the tape shield and the solder block centered over the mastic strip. Secure the ground braid to the cable jacket using vinyl tape and press the solder block firmly into the mastic. Apply a second band of mastic over the solder block and the first mastic band, maintaining the 1/4 inch (6mm) dimension, using 50% stretch. Cut flush. Wrap two half-lapped layers of vinyl tape around the mastic seal, carefully maintaining the 1/4 inch (6mm) dimension. Wrap the ground braid around the cable tape shield for one complete wrap, trim any excess to prevent overlap, and secure it in place with the constant force spring. Wrap the spring in the same direction as the ground braid. Cinch (tighten) the constant force spring after wrapping the final winding and secure it with two wraps of vinyl tape.
- Install the Terminal Lug or Connector
Before crimping, check that the termination assembly (with its core intact) can slide over the selected lug. If it cannot, clean the cable insulation and slide the termination onto the cable before installing the lug. Position the connector or lug and crimp it according to the manufacturer's instructions. Avoid crimping the last 3/8 to 1/2 inch (10-13mm) of the connector. Remove any excess oxide inhibitor and all sharp crimp flashings or edges after crimping.
- Clean Cable Insulation and Prepare for Termination
Wipe the cable insulation thoroughly with an approved solvent using saturated pads. Ensure the solvent does not touch the semi-conductive insulation shield. If abrasive cleaning is necessary, use only aluminum oxide abrasive (grit 120 or finer) on the insulation, not the semi-conductive shield. Exercise caution to avoid reducing the cable insulation diameter below the kit's specified allowance. Create a track-resistant moisture seal by wrapping a band of gray silicone rubber electrical tape around the base of the terminal lug. If the lug barrel diameter is equal to or greater than the cable primary insulation, use no more than two layers. If smaller, build up the tape band to match the insulation diameter. Apply a liberal coating of silicone grease to the edge of the semi-conductive insulation shield to fill the step at the cut-off point.
- Install the Silicone Rubber Termination Body
For lower terminations with a fold-down skirt, pull the loose end of the removable core through the top of the termination until the core is flush with the bottom of the termination. Slide the termination body onto the cable. Align the termination with the forward edge of the mastic seal (under the vinyl tape). Carefully begin to remove the core by unwinding it counter-clockwise, starting with the loose end. Ensure the termination body, not the core, is butted up to the leading edge of the mastic seal. Continue removing the core completely. Do not push or pull on the termination assembly while removing the core.
- Complete the Termination Sealing and Grounding
Apply a thin film of silicone lubricant to the skirt and mastic seal area, but do not lubricate the skirt tabs. Carefully fold down the skirt over the mastic seal. Complete the lug area moisture seal using the remaining gray silicone rubber electrical tape. Overlap the termination insulator by approximately 1 inch (25mm) and extend the tape wrapping over a non-crimped region of the lug/connector barrel using a half-lap configuration. Connect the ground braid securely to the system ground. Confirm that the High-K step of the termination does not exceed 1.5 inches (38mm) over the cable semi-conductive shield.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.