Overview
- 900 Amp continuous current rating
- 15/25kV phase-to-phase voltage rating
- Integrated test point for safe voltage verification
- ComboT design combines elbow and plug in one unit
- Compatible with ABB 15/25kV cable systems
Specifications
Application | 15/25 kV, 900 Amps |
Connection Type | Elbow / Connecting Plug with Stud |
Current Rating | 900 A |
Material | Copper |
Series | ComboT |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Combo T Elbow - Connecting Plug |
Voltage Rating | 15/25kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

GG40250-2030
E-Z-Ground Ground Grid Copper Compression Connector, Cable Range 4/0 or 250 kcmil, Ground Rod 1/2 and 5/8 Inch, Direct Burial
80024
Grounding pigtail with an insulated lead and a GSH grounding screw on one end. It is designed to make grounding an electrical circuit fast and easy. The lead is 9 inches long and uses 10 AWG wire.
776BGADDRK-S
35 kv, 600 Amp, Deadbreak, Ball Grounding Device Kit, includes Grounding Device with 1 inch Ball, Stud, Insulated Cap with Test Point.
776BGADDR
35 kv, 600 Amp, DeadBreak, Insulated Cap with Test Point, Fits 1 inch Ball Grounding DeviceFrequently Asked Questions
What is the BIL rating for the K676BCCP?
The K676BCCP has a Basic Impulse Level (BIL) impulse withstand rating of 140 kV (1.2 x 50 microsecond wave).
What is the continuous current rating for K676BCCP?
The K676BCCP connector has a continuous current rating of 900 A.
What is the voltage class for the K676BCCP connector?
The K676BCCP connector has a voltage class of 15/25/28 kV. Its maximum phase-to-phase operating voltage is 28.0 kV.
What do the color-coded interfaces on ComboT indicate?
IEEE 386 color-coded PBT interfaces indicate voltage class: red for 15 kV reducing tap and blue for 25 kV reducing tap.
How much stack height does the ComboT reduce?
Each combination elbow/connecting plug reduces the stack height by 2.67 inches. This allows it to work in smaller cabinets and tighter spaces.
What stud size is used for ComboT assembly?
ComboT assembly utilizes a standard 5/8 inch–11 stud that threads into the equipment bushing.
What is the primary safety precaution for ComboT installation?
The system needs to be de-energized before initiating any installation. Always refer to the complete instruction sheet.
What is the required torque for K676BCCP bus insertion?
For the K676BCCP (connecting tap), the CCP bus or BIP should be torqued to 50 to 60 ft.-lbs.
What is the primary safety precaution for ComboT installation?
The system needs to be de-energized before initiating any installation. Always refer to the complete instruction sheet.
What do the color-coded interfaces on ComboT indicate?
IEEE 386 color-coded PBT interfaces indicate voltage class: red for 15 kV reducing tap and blue for 25 kV reducing tap.
How to Install K655/K656CCP Deadbreak Elbow Connectors
This guide provides detailed instructions for installing K655/K656CCP Deadbreak Elbow Connectors, ensuring fully shielded and submersible deadfront cable connections for 15kV or 25kV class high voltage systems. It covers cable preparation, connector assembly, and proper grounding procedures.
Estimated time: 2h
Tools needed:
Cable cutters, Wire strippers, Crimping tool, Wire brush (for aluminum conductors), 600 ATM assembly tool, Hotstick, Suitable sensing device (for capacitive test points)
Supplies needed:
K655/K656CCP Elbow Connector kit (Elbow, Cable Adapter, Connector, Stud, Compression Lug, Lubricant), Vinyl plastic tape (if applicable), Tape retainer (if applicable), Tape marker (if applicable), Ground wire (minimum No. 14 AWG Copper), Suitable grounding connector, HV insulated cap(s) or connector(s) (if replacing shipping covers), Silicone grease
- De-energize and Inspect Components
DANGER: All apparatus must be de-energized during installation or removal of parts to prevent serious or fatal injury. Inspect all components for damage, proper rating, and compatibility with mating parts. If the product is supplied with protective shipping covers, remove them and replace with appropriate HV insulated caps or connectors before submerging or energizing the circuit.
- Position and Clean Cable
Position the cable in its final assembled location, ensuring enough slack for adequate clearance to remove the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable Outer Jacket and Shield
Remove the cable's outer jacket to a dimension of 12 3/4” (324mm). Follow the specific instructions for your cable shield type: For shield wires, fold them back. For flat metallic tape shield, remove it and secure with vinyl plastic tape to 10 3/4” (273mm). For fabric tape shield, remove it and install a tape retainer and tape marker to 9 3/4” (248mm) and 10 3/4” (273mm) respectively. For longitudinally corrugated shield, remove it and install a tape marker flush to 10 3/4” (273mm). For semi-con shield, remove it and install a tape marker to 9 3/4” (248mm) and 10 3/4” (273mm), ensuring not to cut or nick the cable insulation. Note: If using UNISHIELD* or lead sheath cable, refer to the installation instructions supplied with the 10TL cable shield adapter.
- Prepare Cable Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Install Compression Lug
Remove the protruding cable insulation by cutting it even with the end of the cable adapter, taking care not to cut or nick the cable adapter or the conductor. Verify the exposed conductor length is 4 3/8”–4 11/16” (111mm–119mm); if incorrect, redo the assembly. For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the “Check Dimension” (must be less than 6 1/2” (165mm)) before crimping. Crimp the compression lug following its supplied instructions, locating the first crimp on the end closest to the cable. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter is 6 1/2”–7 1/4” (165mm–184mm); if incorrect, redo the assembly.
- Install Elbow and Connect to Mating Product
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further, ensuring the cable adapter remains flush with the tape marker. Reposition the cable adapter if necessary. Remove the tape marker. DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from both the elbow and the mating part. Install the stud in the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part. Using the 600 ATM assembly tool, thread the connector into the mating part until it bottoms. Apply 50 to 60 foot-pounds torque.
- Ground the Cable Shield
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with the grounding device; if no grounding device is used, ground the shield through an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test (K656CCP Only)
If applicable (K656CCP only), remove the test point cap with a hotstick, peeling off at an angle rather than pulling directly in line with the test point assembly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment; follow the manufacturer’s directions for the meter used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. WARNING: Contamination, moisture, dirt, etc., around the test point or use of the wrong measuring equipment can provide a false “no voltage” indication on an energized elbow. To prevent serious or fatal injury, treat the elbow as energized until the “no voltage” test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone grease and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.