Contact for Pricing
Overview
- 600 Amp current rating
- 15/25kV voltage rating
- Basic Combo T Connecting Plug configuration
- Includes stud connection for secure termination
- Features integrated test point for safe testing
Specifications
Application | 15/25 kV, 600 Amps |
Connection Type | Basic Combo T Connecting Plug with Stud |
Current Rating | 600 A |
Series | Basic Combo T |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Combo-T Connecting Plug |
Voltage Rating | 15/25kV |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K650RTW
15/25kV 600 Series Deadbreak Reducing Tap Well. Length 5.37 inch. Width 3 inch not counting bracket. 600/200 Amps
K675CPSP
15/25kV, 900 Amp Deadbreak, Connecting Plug, with Factory Assembled Stud which is not field removable.
K651CPSP
15/25kV, 600 Amp, Deadbreak, Connecting Plug. Use 600ATM assembly tool. Factory assembled Stud, which is not field removable.
K655BLR-J0270
15/25kV 600 Series Deadbreak Elbow without Test Point (with Stud), Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 4/0 /Compacted Solid 250 /mmSquared Compact 125.Frequently Asked Questions
Does the K656BCCP include a test point?
Yes, the K656BCCP ComboT elbow/connecting plug includes a test point.
What is the torque specification for the 600ATM?
The 600ATM should be torqued to 50 to 60 ft.-lbs during installation.
What is a critical safety precaution before installation?
The system must be de-energized before initiating any installation of the ComboT connector.
What is the BIL impulse withstand voltage?
The BIL impulse withstand (1.2 x 50 microsecond wave) for K656BCCP is 140 kV.
What is the continuous current rating for K656BCCP?
The continuous current rating for the K656BCCP series is 600 A.
What is the max phase-to-ground operating voltage?
The maximum phase-to-ground operating voltage for the K656BCCP series is 16.2 kV.
What is the voltage class for K656BCCP?
The K656BCCP series has a voltage class of 15/25/28 kV.
What do the ComboT color-coded interfaces indicate?
Red interfaces are for 15 kV reducing taps, and blue are for 25 kV reducing taps, providing visibility and seating indication.
How much stack height does the ComboT reduce?
Each combination elbow/connecting plug reduces stack height by 2.67 inches.
Does the K656BCCP include a test point?
Yes, the K656BCCP ComboT elbow/connecting plug includes a test point.
How to Install K655/K656CCP Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K655/K656CCP Deadbreak Elbow Connectors on 15kV or 25kV class systems, including cable preparation, lug crimping, and connection to mating apparatus.
Estimated time: 2h
Tools needed:
Crimping tool, Wire brush (for aluminum conductors), 600 ATM assembly tool, Hotstick (for K656CCP voltage test), Suitable sensing device (for K656CCP voltage test)
Supplies needed:
Lubricant (supplied), Vinyl plastic tape (if applicable), Tape retainer (if applicable), Tape marker (if applicable), Wire (at least No. 14 AWG Copper), Suitable ground connector, Silicone grease (for K656CCP test point cap), Compression Lug (supplied), Cable Adapter (supplied), Elbow (supplied), Stud (supplied)
- Prepare for Installation and Safety Check
Review the contents of the package to ensure all parts are complete and undamaged. Inspect all components for proper fit with the cable and/or mating products. Ensure all apparatus are de-energized during installation or removal of parts to prevent serious or fatal injury. Have all required tools at hand and maintain cleanliness throughout the procedure.
- Position and Cut Cable
Position the cable in its final assembled location, allowing enough slack for adequate clearance to remove the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare Cable Jacket and Shield
Follow the instructions that apply to your specific cable type for removing the outer jacket and preparing the shield. This may involve removing the outer jacket to 12-3/4 inches (324mm), folding back shield wires, removing flat metallic tape shield and securing with vinyl plastic tape, or removing fabric/corrugated shields and installing tape retainers/markers. For UNISHIELD* or lead sheath cables, refer to the 10TL cable shield adapter instructions.
- Prepare Semi-Con Shield and Cable Insulation
Remove the semi-con shield to the dimensions shown (9-3/4 inches or 248mm, and 10-3/4 inches or 273mm), ensuring not to cut or nick the cable insulation. Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back.
- Clean, Lubricate, and Install Cable Adapter
Thoroughly clean and then lubricate the cable insulation, always working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Insulation and Verify Conductor Length
Remove any protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The length of the exposed conductor should be 4-3/8 inches to 4-11/16 inches (111mm-119mm). If the length is incorrect, redo the assembly.
- Prepare Conductor and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping (it should be less than 6-1/2 inches or 165mm). Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be 6-1/2 inches to 7-1/4 inches (165mm-184mm); otherwise, redo the assembly.
- Lubricate and Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove protective caps from the elbow and the mating part. Install the stud in the mating part. Clean and lubricate both the elbow and the mating part with the lubricant supplied, ensuring surfaces remain clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part. Using the 600 ATM assembly tool, thread the connector into the mating part until it bottoms. Apply 50 to 60 foot-pounds of torque.
- Ground the Connector and Cable Shield
Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded according to the instructions supplied with any grounding device, or through an alternate method if no device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Install Additional Mating Connectors (Optional)
If applicable, clean and lubricate the entire male interface and either a DR(G), GLR, or LR connector of the appropriate voltage class with the supplied or ELASTIMOLD® approved lubricant. Install the DR(G), GLR, or LR to the bushing interface following the instructions supplied with those specific products.
- Perform Voltage Test (K656CCP Only)
For K656CCP connectors, remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the meter used. Test with a suitable sensing device designed for capacitive test points to determine if the cable is energized. Contamination, moisture, or incorrect equipment can give a false 'no voltage' indication; treat the elbow as energized until confirmed by other means. After testing, clean, lubricate the inside surface of the cap with silicone grease, and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.