ABB Installation Products K656LR-N0360-S 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…
UPC: 783786472840
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Rated for 15kV and 25kV medium-voltage applications
- Supports cable insulation diameters: 1.515" to 1.780"
- Compatible with 650 kcmil (compressed/stranded) or 750 kcmil (compact/solid) conductors (400 mm² compact)
- Includes test point for safe voltage detection without de-energizing
- Cold-shrinkable jacket seal for moisture-tight, corrosion-resistant protection
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 650 kcmil , 750 to 800 kcmil |
Connection Type | Deadbreak Elbow |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K656LR |
Size | Cable Insulation Diameter 1.515 inch to 1.780 inch |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point. Cold-Shrinkable Jacket Seal Included |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 7.2500 L |
Package Weight (Metric) | 3.2890 kg |

K655LR-M0360-S
600 Series Elbow with insulated plug, cap, stud, lug and cable adapter, 15/25KV, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400. 200ECS Jacket Seal Included.
K656LR-H0240
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0.
K656LR-H0230-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded #1 or Compact/Solid 1/0 or mm2 Compact 50. Cold-Shrinkable Jacket Seal Included.
K655LR-N0330
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
K656LR-M0360
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size Compressed/Stranded 650 or Compact/Solid 750 or mm2 Compact 400.
K655LR-N0300
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K656LR-G0240-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase. For the 28kV voltage class, it is 16.2kV phase-to-ground and 28kV phase-to-phase.
What conductor sizes can the K656LR handle?
The K656LR can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating for this deadbreak elbow?
The K656LR elbow connector has a continuous current rating of 600 Amps.
What is the impulse withstand rating for the 28kV voltage class?
The impulse withstand rating for the 28kV voltage class is 140kV BIL for a 1.2 x 50 microsecond wave.
What insulation diameters does the K656LR accommodate?
The K656LR accommodates insulation diameters ranging from 0.640 inches to 1.935 inches.
Is a grounding device recommended for this product?
Yes, when used on metallic tape shield or drain wire cable, an ECS cable seal grounding device is highly recommended for safety.
What is the corona extinction rating for the 15kV voltage class?
The corona extinction rating for the 15kV voltage class is 11kV AC at 3pC sensitivity.
Can the K656LR be installed on de-energized equipment?
Yes, the K656LR can be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
What is the momentary current rating for the K656LR?
The K656LR has a momentary current rating of 25kA Sym for 10 Cycles.
How to Install Elastimold 655/675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of Elastimold 655/675LR and K655/K675LR deadbreak elbow connectors, including cable preparation, lug crimping, and connection to mating apparatus. All apparatus must be de-energized during installation.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Torque wrench, Hotstick, Suitable sensing device, Cleaning cloths
Supplies needed:
Elbow connector (655/675LR or K655/K675LR), Cable Adapter, Compression Lug, Insulating Plug (if used), Lubricant, Threaded Stud, No. 14 AWG Copper wire (or equivalent), Suitable ground connector, Waterproofing material
- Prepare the Cable for Installation
De-energize all apparatus. Assemble the cable in its final position with enough slack to provide adequate clearance for removing the elbows. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the center line of the mating product.
- Clean and Prepare Cable Surface
Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket (where applicable) and prepare the cable insulation, semi-con shield, and shield wires/tape according to the provided diagrams and dimensions (e.g., 9-3/4”, 10-3/4”, 12-3/4” tape markers).
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Ensure not to cut or nick the cable adapter or the conductor. Verify the length of the exposed conductor is between 4-1/4” – 4-9/16” (108mm-116mm); if not, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (should be less than 6-3/8”). Crimp the compression lug following its supplied instructions. Wipe all excess inhibitor from the lug and cable adapter. Verify the distance from the end of the lug to the cable adapter is between 6-3/8” to 7-1/8” (162mm-181mm) after crimping; if not, redo the assembly.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
Remove protective caps from both the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it is not already equipped with one. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean.
- Connect the Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to its specific instructions.
- Install Insulating Plug Cap (if used)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper ampacity equivalent) through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. Ground the cable shield according to the instructions supplied with the grounding device, or via an alternate method if no device is used. Waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Use a suitable sensing device, designed for capacitive test points, to determine if the cable is energized. Do not use conventional voltage measuring equipment. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.