ABB Installation Products K656LR-N0360 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…
UPC: 783786059591
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating for medium voltage applications
- 600 Amp continuous current rating
- Integrated test point for system diagnostics
- Accommodates cable insulation diameters from 1.515" to 1.780"
- Compatible with 650 kcmil (Compressed/Stranded), 750 kcmil (Compact/Solid), or 400 mm² (Compact) conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 650 kcmil , 750 to 800 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655L3-LM0360
15/25kV 600 Series Deadbreak 3-Way L-Kit, Cable Insulation Diameter 1.280 inch to 1.430 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
K656LR-F0220-SG3
15/25kV, 600 Amp, Elbow with Sealing Kit, With Test Point (includes Insulating Plug, Stud, Lug and Cable Adapter), Cable Insulation Diameter .640-.820 inches, Aluminum Lug, Conductor Size #2 Stranded/Compressed or #1 Compact/Solid
K655LR-M5300
25kV, 600 Amp, Deadbreak Elbow, No Sealing Kit, without Test Point, Cable Insulation 1.370-1.630 inches, Bi-Metal Lug, Conductor Size kcmil Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K656LR-N0300-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-G0250
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 2/0 or Compact/Solid 3/0 or mm2 Compact 70.
K656LR-H0240-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. Cold-Shrinkable Jacket Seal Included.
K656LR-M0300
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K656LR-G0240
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase. For the 28kV voltage class, it is 16.2kV phase-to-ground and 28kV phase-to-phase.
What conductor sizes can the K656LR handle?
The K656LR can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for the K656LR?
The K656LR is designed for insulation diameters ranging from 0.640 inches to 1.935 inches.
What standards does the K656LR meet?
The K656LR meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous current rating for the K656LR?
The K656LR has a continuous current rating of 600 Amps.
What is the momentary current rating for the K656LR?
The K656LR has a momentary current rating of 25kA Sym for 10 Cycles.
What is the impulse withstand rating for the K656LR?
For the 15kV class, the impulse withstand is 95kV BIL. For the 28kV class, it is 140kV BIL.
What is the AC one-minute withstand voltage for the K656LR?
For the 15kV class, the AC one-minute withstand is 34kV. For the 28kV class, it is 45kV.
What is the DC fifteen-minute withstand voltage for the K656LR?
For the 15kV class, the DC fifteen-minute withstand is 53kV. For the 28kV class, it is 84kV.
What is the corona extinction rating for the K656LR?
For the 15kV class, the corona extinction is 11kV AC @ 3pC sensitivity. For the 28kV class, it is 21.5kV AC @ 3pC sensitivity.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K655/K675LR and 655/675LR Deadbreak Elbow Connectors, including cable preparation, lug crimping, and final assembly for high voltage systems.
Estimated time: 1h 30m
Tools needed:
Wire strippers, Crimping tool, Wire brush, Hotstick, Suitable sensing device for capacitive test points, Torque wrench
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug (if used), Lubricant, Threaded stud, HV insulated cap(s) or connector(s), Grounding wire (No. 14 AWG Copper or equivalent), Suitable connector for grounding wire, Waterproofing material (for cable jacket)
- Prepare for Installation and Ensure Safety
Before starting, ensure all apparatus is de-energized. Verify the package contents are complete and undamaged, and all components fit properly with the cable and/or mating products. Gather all required tools and maintain a clean work area. This product must be installed only by competent personnel trained in high voltage electrical equipment safety practices.
- Assemble Cable and Clean Outer Surface
Position the cable in its final assembled position with enough slack to allow for elbow removal. For concentric neutral cable, unwind the neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare the Cable End
Follow the specific cable preparation instructions for your cable type (e.g., 20MA/21MA grounding device, 600ECS Jacket Cable Seal, UNISHIELD/LEAD SHEATH with 10TL adapter, or Jacketed/Non-Jacketed cable). Remove the outer jacket (if applicable) and prepare the cable dimensions as specified in the provided diagrams for semi-con shield, cable insulation, and tape markers.
- Install and Lubricate the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Expose the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping; this dimension must be less than 6-3/8 inches. Crimp the compression lug according to the crimping instructions supplied with the lug. Wipe off all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Install the Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Make sure the cable adapter is still flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare Mating Products
Remove any protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean. DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED.
- Connect the Elbow to the Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Install the Opposite Mating Part (if applicable)
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to the instructions supplied with that mating part. If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow, pushing down hard until the cap snaps into place.
- Ground the Cable Shield
Insert one end of a grounding wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded; ground according to the instructions supplied with the grounding device, or through an alternate method if no grounding device is used. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test (Optional but Recommended)
If performing a voltage test, remove the test point cap with a hotstick by peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Test with a suitable sensing device designed for capacitive test points, following the meter manufacturer’s directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious or fatal injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.