ABB Installation Products K656DLR-L0330 600 Amp, 15/25kV, 600 Series Deadbreak Direct Test Elbow with Test Point, (with…
UPC: 783786813070
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Fully rated 15/25kV, 600 Amp Class deadbreak elbow connector
- Direct Test System (EDTS) with insulated port for conductor testing and diagnostics
- Aluminum compression lug for compressed stranded 500 kcmil, compacted solid 600 kcmil, or mm² compact 250/300 conductors
- Cable insulation diameter range: 1.180" to 1.465"
- Fully shielded, fully submersible molded rubber housing with 100% peroxide-cured EPDM construction
- Meets ANSI/IEEE Standard 386; rated for 8.3kV/16.2kV phase-to-ground, 95kV/140kV BIL impulse withstand
- Continuous 600 Amp operation; 25kA symmetrical momentary rating for 10 cycles
- Designed for easy connection/disconnection with standard hand tools in de-energized state
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amps |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions, Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators. Direct conductor test point equipped elbow |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Direct Test Elbow with Test Point |
Voltage Rating | 15 to 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656LR-L0330-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.180 inch to 1.465 inch. Conductor Size Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300. Cold-Shrinkable Jacket Seal Included.
K655DLR-N0380
15/25kV, Deadbreak, 600 Series Direct Test Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K655SR-J0330-SG3
600 Amp, 15/25kV, 600 Series Deadbreak Straight Receptacle with Cable Adapter, Lug and Retaining Ring. Cable Insulation Diameter 0.980 inch to 1.180 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 500 or Compacted Solid 600 or mmSquared Compact 250/300. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K655DLR-H0240
15/25kV, Deadbreak, 600 Series Direct Test Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 1/0 /Compacted Solid 2/0.
K655DLR-J0330
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation .980-1.180 inches, Aluminum Compression Lug, Conductor Size 500 Stranded/Compressed or 600 Solid/Compact
K655DLR-G0270
15/25kV, 600 Amp, Elbow with Direct Test and Sealing Kit. Cable Insulation Diameter - .760-.950 inch, Aluminum Lug, Conductor Size 270 - 4/0 Stranded/Compressed or 250 Compact/Solid.
K655DLR-G0280
15/25kV, 600 Amp, Elbow with Direct Test and Sealing Kit. Cable Insulation Diameter - .760-.950 inch, Aluminum Lug, Conductor Size 280 - 250 Stranded/Compressed or 300 Compact/Solid.
K655DLR-L0330
15/25kV, 600 Amp, Direct Test Elbow, DeadBreak, Cable Insulation 1.180-1.465 inches, Aluminum Compression Lug, Conductor Size 500 Stranded/Compressed or 600 Solid/CompactFrequently Asked Questions
What items are included in the kit?
Each kit contains an elbow connector housing, copper compression lug, stud, insulated plug with cap, lubricant, cable adapter, and installation instructions.
What materials are used in its construction?
It features 100% peroxide-cured construction, including insulation and conductive EPDM materials.
Is the elbow connector submersible?
Yes, the elbow connector features a fully shielded, fully submersible molded rubber housing.
What are the BIL ratings for the product?
The Basic Impulse Level (BIL) impulse withstand is 95kV for the 15kV class and 140kV for the 28kV class.
What are the operating voltage ranges?
For 15kV class, max phase-to-ground is 8.3kV and phase-to-phase is 14.4kV. For 28kV class, max phase-to-ground is 16.2kV and phase-to-phase is 28kV.
What standards does this product meet?
The product meets ANSI/IEEE Standard 386, Latest Revision.
What is the continuous current rating?
The continuous current rating for both 15kV and 28kV voltage classes is 600 Amps.
What is the purpose of the EDTS test point?
The EDTS test point provides a direct path to the conductor for voltage testing, isolation, and grounding when used with a 600TC series meter adapter.
What is the K656DLR-W0X product?
It is a 15/25kV, 600 Amp Class deadbreak elbow connector with a Direct Test System (EDTS) for isolation, testing, and grounding.
What is the purpose of the EDTS test point?
The EDTS test point provides a direct path to the conductor for voltage testing, isolation, and grounding when used with a 600TC series meter adapter.
How to Install K656DLR Direct Test Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of K656DLR Direct Test Elbow Connectors, including cable preparation, component assembly, and connection to high voltage apparatus.
Estimated time: 2h
Tools needed:
Wire strippers, Crimping tool, Wire brush (for aluminum conductors), Torque wrench (for mating parts), High voltage insulated hot stick (for test point cap), Suitable grounding connector
Supplies needed:
K656DLR Elbow Connector kit (Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), Cable (appropriate type for application), Vinyl plastic tape (if required for shield type), Tape retainer (if required for shield type), Tape marker (if required for shield type), Grounding wire (at least #14 AWG copper), Waterproofing material (for cable jacket), Mating high voltage apparatus (bushing, tap plug, or tap well)
- De-energize Apparatus and Position Cable
DANGER: Ensure all apparatus is de-energized before beginning installation. Position the cable in its final assembled location, allowing sufficient slack to remove elbows. For concentric neutral cable, unwind the neutral wires. Cut the cable 1 3/4 inches (45mm) from the centerline of the mating product.
- Prepare the Cable Outer Jacket and Shield
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires. Refer to the specific instructions for your cable type (e.g., outer jacket, shield wires, flat metallic tape, fabric tape, longitudinally corrugated, semi-con shield) and remove the outer jacket and shield to the specified dimensions. If using UNISHIELD or lead sheath cable, refer to the 10TL cable shield adapter instructions. Do not cut or nick the cable insulation when removing the semi-con shield.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare Conductor and Crimp Compression Lug
Remove any protruding cable insulation, cutting it even with the end of the cable adapter. Ensure the exposed conductor length is between 4 3/8 inches (111mm) and 4 11/16 inches (119mm). For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. For copper, fully insert the conductor. Measure the 'Check Dimension' before crimping (must be less than 6 1/2 inches / 165mm). Crimp the compression lug according to the supplied instructions. Wipe off any excess inhibitor. After crimping, the distance from the end of the lug to the cable adapter should be between 6 1/2 to 7 1/4 inches (165mm to 184mm).
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Verify that the cable adapter remains flush with the tape marker. If not, reposition the cable adapter. Remove the tape marker.
- Prepare and Connect to Mating Product
DANGER: Do not connect or disconnect mating products while energized, and do not energize while disconnected. Remove protective caps from both the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into it. Clean and lubricate both the elbow and the mating part with the supplied lubricant. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud. For the opposite end of the elbow, clean and lubricate the mating part, insert it into the elbow, engage the threads, and hand tighten. Torque the mating part according to its specific instructions.
- Ground the Cable Shield
Insert one end of a grounding wire (at least No. 14 AWG copper) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded according to the instructions supplied with any grounding device used, or via an alternate method if no device is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Install Insulating Plug (If Applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps into place. Refer to separate instructions for direct voltage testing procedures, if required.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.