ABB Installation Products K656CY-L0380 15-25kV 600 Series Deadbreak Separable Wye Joint Package (3-Way) with Test Point. Cable…
UPC: 783786396511
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Rated for 15-25 kV and 600 A continuous current
- Accommodates cable insulation diameters 1.180–1.465 inch
- Supports 700/750 kcmil (compressed stranded) or 900 kcmil (compacted solid) conductors
- 3-way deadbreak separable wye joint with test point for voltage verification
- Aluminum compression lug for reliable, low-resistance connections
Specifications
Amperage Rating | 600 A |
Application | Compact Design is suitable for small vaults and manholes |
Color | Black |
Conductor Range | 700 to 750 kcmil , 900 kcmil |
Connection | Compression |
Environmental Conditions | All Weather Conditions |
Insulation | True |
Length | 37.27 in |
Length | 946.658 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible, 100 Percent Peroxide Cured EPDM Molded Rubber |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Separable Wye Joint |
Voltage Rating | 15 to 25 kV |
Width | 8.12 in |
Width | 206.248 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 25.5000 L |
Package Weight (Metric) | 11.5670 kg |

K655LRTP-N0380
600 Amp, 25kV, Stick-Op Connector Kit. Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900.
K656CYH0240L0360L036
600 Amp, 15/25KV, Separable Wye Joint Package, 3-Way with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 1/0 /Solid 2/0 /mmSquared 53.49. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400. Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 650 /Compacted Solid 750 /mmSquared Compact 400.
K656CY-H0250
600 Amp, 15/25KV, Separable Wye Joint Package, 3-Way with Test Point, Cable Insulation Diameter 0.850 inch to 1.050 inch. Aluminum Compression Lug. Conductor Size AWG Compressed Stranded 2/0 /Solid 3/0 /mmSquared 67.43.
K656CY-K0330-S
600 Amp, 15/25KV, Separable Wye Joint Package, 3-Way with Test Point, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 500 /Compacted Solid 600 /mmSquared Compact 250/300. Cold-Shrinkable Jacket Seal Included.
M655YSR-M0300
600 Amp Separable Cable Joints, Straight Receptacle, 35KV, Dead Break, Splice, Cable Insulation Diameter 1.370 inch to 1.630 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed Stranded 350 or Solid 400 or mmSquared 185.
K656CY-DP0592548
600 Amp, 15/25KV, Separable Wye Joint Package, 3-Way with Test Point, G0240 - Cable Insulation Diameter 0.760 inch to 0.950 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 1/0 or Compacted/Solid 2/0. S - Cold Shrinkable Jacket Seal. L0270 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 4/0 or Compacted/Solid 250. SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring. L0270 - Cable Insulation Diameter 1.180 inch to 1.465 inch. Universal Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed/Stranded 4/0 or Compacted/Solid 250. SG3 - Cold Shrinkable Seal with Copper Braid and Constant Force Spring.
K656I-K0320-S
600 Amp, 15/25KV, Separable Straight Joint Package 2-Way with Test Point, Splice, Cable Insulation Diameter 1.090 inch to 1.310 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 450 /Compacted Solid 500/550. Cold-Shrinkable Jacket Seal Included.
K656I-L0380-S
600 Amp, 15/25KV, Separable Straight Joint Package 2-Way with Test Point, Splice, Cable Insulation Diameter 1.180 inch to 1.465 inch. Aluminum Compression Lug. Conductor Size AWG or kcmil, Compressed Stranded 700/750 /Compacted Solid 900. Cold-Shrinkable Jacket Seal Included.Frequently Asked Questions
What is the primary use of the K656CY-HP joint?
The K656CY-HP cable joint is used to join cables in a disconnectable 3-way joint, suitable for small vaults and manholes.
What is the continuous current rating for the 25kV class?
For both 15kV and 25kV voltage classes, the continuous current rating is 600 Amp.
How do I order the basic wye joint housing?
To order the basic wye joint housing only, specify K656CY-HP.
Does the K656CY-HP include a test point?
Yes, the K656CY-HP includes an integral capacitive test point.
What material is the K656CY-HP joint made from?
It is made from 100% peroxide cured EPDM molded rubber.
Which industry standard does the K656CY-HP meet?
The K656CY-HP meets ANSI/IEEE Standard 386, Latest Revision.
What is the maximum phase-to-ground operating voltage for 25kV class?
For the 25kV voltage class, the maximum phase-to-ground operating voltage is 16.2kV.
What is the continuous current rating for the 15kV class?
For both 15kV and 25kV voltage classes, the continuous current rating is 600 Amp.
What is the maximum phase-to-ground operating voltage for 15kV class?
For the 15kV voltage class, the maximum phase-to-ground operating voltage is 8.3kV.
Is the K656CY-HP joint submersible?
Yes, it forms a fully shielded, fully submersible 3-way disconnectable cable joint.
How to Install Elastimold K656/K676 Series Deadbreak Receptacles
This guide provides step-by-step instructions for installing Elastimold K656/K676 series deadbreak receptacles, including cable preparation, crimping, assembly, and grounding for 15kV and 25kV applications.
Estimated time: 1h 30m
Tools needed:
Hex wrench, Torque wrench with 15/16 inch socket, Wire strippers, Wire brush (for aluminum cable), Safety solvent, Rag, 650ATY or 600RRT assembly tool, Measuring tape or ruler
Supplies needed:
Receptacle housings, Cable adapters, I, Wye or H Center sections, Aluminum holding collars, Elastimold approved lubricant, Hex-head bolts, Crimp connectors, Belleville washers, Flat washers, Nylon venting rod, Electrical tape, Conductive copper strip (for flat metallic tape shielded cable), No. 14 AWG copper wire (or equivalent), ECS grounding device (optional)
- De-energize and Inspect Apparatus
Before beginning any work, ensure all apparatus in the work area are completely de-energized. Do not touch or move energized products. Inspect all parts for damage, proper rating, and compatibility with mating components. Failure to follow these safety instructions can result in serious or fatal injury.
- Initial Cable Preparation
Wipe the outer jacket of the cable clean for a distance of 38 inches (96.5 cm) from the end. Cut the cable end squarely. If using an ECS grounding device, slide the ECS tube onto the cable 38 inches (96.5 cm) from the end. Then, slide the receptacle housing onto the cable 30 inches (76.2 cm) from the end.
- Prepare Cable for Adapter Installation
Perform the necessary cable preparation steps according to your cable type (Jacketed Concentric Neutral or Flat Metallic Tape Shielded) as detailed in the provided supplement. This typically involves removing specific lengths of the outer jacket, neutral wires/tape shield, and semi-conducting shield, beveling the insulation, and thoroughly cleaning the insulation. Lubricate the prepared cable and the inside of the cable adapter with supplied or approved lubricant. Slide the cable adapter, small end first, over the cable with a twisting motion until its end is flush with the designated tape marker.
- Prepare Conductor and Install Retaining Ring
Remove any protruding cable insulation, cutting it even with the end of the cable adapter. Ensure the exposed conductor measures 4 3/4 to 5 inches (12.06 to 12.7 cm); if not, redo the assembly. Assemble the aluminum retaining ring over the conductor, snugging it firmly against the cable adapter. Using the provided hex wrench, tighten the socket head screw hand tight. Confirm the exposed conductor now measures 4 3/8 to 4 3/4 inches (11.11 to 12.06 cm); if not, redo the assembly.
- Install and Crimp Connector
Remove the protective cap from the crimp connector. If using aluminum cable, wire brush the conductor immediately before insertion. Fully insert the conductor into the crimp connector barrel, ensuring it contains inhibitor. Measure the distance from the end of the connector to the holding collar; it must be 6 3/4 to 7 inches (17.14 to 17.78 cm) maximum. If over 7 inches, recheck previous work. Crimp the connectors following the instructions packaged with them, rotating each crimp 90 or 180 degrees. Re-measure the distance from the end of the connector to the holding collar; it must still be 6 3/4 to 7 inches (17.14 to 17.78 cm) maximum.
- Assemble and Torque Bolts
Assemble the washers and bolt in the following order: flat washer against the spade contact, Belleville washer (concave side down), then the hex-head bolt. Hand tighten the bolt. Using a torque wrench with a 15/16 inch socket, tighten all bolts to 50 to 60 ft. lbs. The splice and cables are now in their final positions; do not attempt to move or reposition any part of the assembly after bolts are tightened.
- Lubricate and Position Receptacle Housing
Apply the supplied or ELASTIMOLD approved lubricant generously to the outside of the cable adapter, the area of the splice section, and the inside mating surface of the receptacle housing. DO NOT SUBSTITUTE other lubricants. Slide the receptacle housing over the cable adapter and up to the edge of the interface. Insert the nylon venting rod (supplied).
- Final Receptacle Housing Assembly
Attach the appropriate assembly tool (650ATY or 600RRT) as shown in the instructions. Slowly raise the handle (for 650ATY) or turn the hex nut (for 600RRT) to slide the receptacle housing completely over the splice section. WARNING: DO NOT place hand on threaded rod or guide shaft with the assembly tool in place. Remove the venting rod. Repeat steps 7 and 8 for any remaining cables.
- Complete Grounding
Check all cable adapters to ensure they are properly located and remove any vinyl tape markers. Complete the installation of the ECS grounding device according to its specific instructions, if used. Alternatively, connect a short length of No. 14 AWG copper wire (or equivalent) to the grounding eyes of the housings, making a small loop and twisting tightly without damaging the eye, then connect to ground.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.