ABB Installation Products K655LR-N0330-S 600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and…
UPC: 075114191708
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- 600 Amp rated for medium-voltage applications
- Supports 15/25kV systems with 500/600 kcmil conductors
- Includes insulated plug, cap, stud, lug, and cable adapter
- Cable insulation diameter range: 1.515–1.780 inches
- Cold-shrinkable jacket seal for environmental protection
Specifications
Amperage Rating | 600 A |
Application | Designed to provide Fully Shielded, Dead-Front Submersible Cable Connections to High-Voltage Apparatus |
Color | Black |
Conductor Range | 500 kcmil , 600 kcmil |
Connection Type | Deadbreak Elbow |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum Compression Lug, Cold-Shrinkable Jacket Seal |
Material | Housing - EPDM-Rubber |
Series | 600 Series |
Size | Cable Insulation Diameter 1.515 inch to 1.780 inch |
Special Features | Fully shielded, fully submersible molded rubber housing. 100 Percent peroxide-cured construction includes insulation and conductive EPDM materials. Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state. Optional accessories allow visible external separation, by-pass, isolation, dead-ending, grounding, and testing as well as adding taps, surge arrestors, and fault current indicators |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector |
Voltage Rating | 15 to 25 kV |
Voltage Rating | 15/25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K655LR-J0330
600 Amp, 15/25kV, 600 Series Deadbreak, Elbow with Insulated Plug, Cap, Stud, Lug and Cable Adapter. Aluminum Compression Lug. Cable Insulation Diameter 0.980 inch to 1.180 inch. Conductor Size kcmil Compressed/Stranded 500 or Compact/Solid 600 or mm2 Compact 250/300.
K656LR-G0300
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.
K656LR-F0240
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. No Sealing Kit
K656LR-F0210
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compact/Solid #2. No Sealing Kit.
K655LR-N0410-SG3
15-25kv 600 Amp Elbow With Sealing Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 1000.
K656LR-G0270-S
15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 or Solid 250 or mm2 125. With Cold-Shrinkable Jacket Seal.
K656LR-H0290-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold-Shrinkable Jacket Seal Included.
K656LR-M0410
15/25kv, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm). Universal Aluminum Compression Lug. 410 Wire Size - 1000 kcmil Stranded/Compressed. No Sealing kit.Frequently Asked Questions
What conductor sizes does this elbow support?
The elbow supports 500 or 600 kcmil compressed/stranded conductors or 600 mm² compact conductors.
What is the operating voltage range?
The device operates at 15/25kV, suitable for medium-voltage systems.
What cable insulation diameter does this elbow accommodate?
The cable insulation diameter range is 1.515 inch to 1.780 inch.
Is a jacket seal included with this elbow?
Yes, a cold-shrinkable jacket seal is included for environmental protection.
What material is the compression lug made of?
The compression lug is made of aluminum.
How to Install K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe installation and wiring of 655/675LR and K655/K675LR Deadbreak Elbow Connectors on high voltage systems. Ensure all apparatus are de-energized during installation to prevent serious or fatal injury.
Estimated time: 1h 30m
Tools needed:
Hotstick, Wire brush, Crimping tool, Voltage sensing device, Wire strippers, Screwdriver
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug, Lubricant, Threaded stud, Grounding wire (No. 14 AWG Copper or equivalent), Suitable grounding connector, Silicone lubricant
- Prepare Cable Slack and Cut
Assemble the cable in its final position with enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4” (45mm) from the center line of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24” (610mm) or up to the bent back concentric neutral wires.
- Prepare Cable According to Type
Remove the outer jacket (if applicable) and prepare the cable insulation, semi-con shield, and shield wires to the specified dimensions (e.g., 9-3/4”, 10-3/4”, 12-3/4” from the tape marker), following the specific instructions for your cable type (non-jacketed, jacketed, tape shield, etc.).
- Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4” (6mm) back. Thoroughly clean and lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. Verify the exposed conductor length is between 4-1/4” and 4-9/16” (108mm-116mm); otherwise, redo the assembly.
- Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (must be less than 6-3/8”). Crimp the compression lug according to its supplied instructions, locating the first crimp on the end towards the cable adapter. Wipe all excess inhibitor. Verify the distance from the end of the compression lug to the cable adapter is between 6-3/8” to 7-1/8” (162mm-181mm) after crimping; otherwise, redo the assembly.
- Install Elbow
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare Mating Products
Remove protective caps from the elbow and the mating part. If the mating part is not equipped with a stud, hand tighten the threaded stud supplied with the elbow into the mating part. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Opposite Mating Part
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap and place it on the elbow. Push down hard until the cap snaps into place.
- Ground the Cable Shield
Insert one end of a wire (at least No. 14 AWG Copper ampacity) through the grounding eye and twist to make a small loop, ensuring not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded either via a grounding device (following its instructions) or an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test (Optional but Recommended)
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device; do not use conventional voltage measuring equipment. Use a suitable sensing device, designed for capacitive test points, to determine if the cable is energized. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.