ABB Installation Products K656LR-M0410 15/25kv, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.370-1.630…
UPC: 075114253024
Contact for Pricing
Call (262) 252-1600 or email [email protected] for pricing and availability.
Overview
- 15/25kV voltage rating
- 600 Amp continuous current rating
- Integrated test point for circuit testing
- Cable insulation diameter range: 1.370-1.630 inch (34.798-41.402mm)
- Universal aluminum compression lug for 1000 kcmil conductors
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 1000 kcmil |
Connection Type | Deadbreak Elbow with Test Point |
Current Rating | 600 A |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Aluminum |
Material | Housing - EPDM-Rubber |
Series | K656LR |
Size | Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm), 410 Wire Size - 1000 kcmil Stranded/Compressed |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 15/25 kV |
Voltage Rating | 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

756LR-N0410
35kV, 600 Amps, Deadbreak Elbow with Test Point. Cable Insulation Diameter Range 1.515 to 1.780 inch, Aluminum Lug, Conductor Size 1000 Stranded/Compressed. No Sealing Kit.
K656LR-G-0270-SG3
15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 or Solid 250 or mm2 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K655LR-N0420
15-25kv Dead Break Elbow, No-sealing. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compact/Solid 1250.
K656LR-H-0290-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-N0320
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compact/Solid 500. No Sealing Kit.
K656LR-N2410
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Copper Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compressed/Stranded 1000.
K656LR-N0280
15/25kV, 600 Amp, DeadBreak, Elbow with Test Point (includes Insulated Plug, Cap, Stud, Lug and Cable Adapter). Cable Insulation 1.515-1.780 inches, Aluminum Compression Lug, Conductor Size 250 Stranded/CompressedFrequently Asked Questions
What is the continuous current rating of the K656LR elbow connector?
The continuous current rating for the K656LR elbow connector is 600 Amps.
What is the momentary short-circuit current rating?
The momentary short-circuit current rating is 25kA Sym for 10 Cycles.
What is the maximum operating voltage for this elbow connector?
The elbow connector is rated for 15kV and 28kV voltage classes, with maximum operating voltages of 8.3kV phase-to-ground for 15kV class and 16.2kV phase-to-ground for 28kV class.
What conductor sizes can this elbow connector accommodate?
It can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the insulation diameter range for compatible cables?
The compatible insulation diameter range is from 0.640 inches to 1.935 inches.
What is the impulse withstand rating for the 28kV voltage class?
For the 28kV voltage class, the impulse withstand rating is 140kV BIL (1.2 x 50 microsecond wave).
What is the AC one-minute withstand voltage for the 15kV class?
For the 15kV voltage class, the AC one-minute withstand voltage is 34kV.
What is the corona extinction rating for the 28kV voltage class?
The corona extinction rating for the 28kV voltage class is 21.5kV AC at 3pC sensitivity.
Is a grounding device recommended when using this elbow connector?
Yes, an ECS cable seal grounding device is highly recommended for safety when used on metallic tape shield or drain wire cable.
What standards does the K656LR elbow connector meet?
The K656LR elbow connector meets ANSI/IEEE Standard 386, Latest Revision.
How to Install Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides comprehensive instructions for the safe installation, wiring, and connection of Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors to high voltage apparatus. Ensure all safety precautions are followed.
Estimated time: 1h
Tools needed:
Wire brush, Crimping tool, Hotstick, Suitable sensing device for capacitive test points, Torque wrench (for mating parts), Wire strippers
Supplies needed:
Elbow connector, Cable adapter, Compression lug, Insulating plug (if applicable), Lubricant (silicone), Threaded stud, No. 14 AWG Copper wire (or equivalent) for grounding, Suitable grounding connector, Tape marker, Protective caps (for elbow and mating part), HV insulated cap(s) or connector(s) (if replacing shipping covers)
- Prepare for Installation and Safety Check
DANGER: All apparatus must be de-energized during installation or removal. Do not touch or move energized products. Inspect all package contents to ensure they are complete and undamaged. Verify all components for proper fit with the cable and/or mating products. Have all required tools at hand and maintain cleanliness throughout the procedure. This product should only be installed by competent personnel trained in high voltage electrical equipment safety practices.
- Prepare the Cable
Assemble the cable in its final position with enough slack to allow for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product. Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent back concentric neutral wires. Remove the outer jacket (if applicable) and prepare the cable according to the specific cable type (e.g., Unishield, Jacketed, Non-Jacketed, Flat Metallic Tape Shield, Fabric Tape Shield, or Longitudinally Corrugated Shield) as detailed in the product documentation, ensuring correct dimensions for insulation and semi-con shield removal.
- Install the Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Prepare the Conductor
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Be careful not to cut or nick the cable adapter or the conductor. The length of the exposed conductor must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly.
- Crimp the Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor immediately before fully inserting it into the compression lug. Measure the 'Check Dimension' before crimping; it should be less than 6-3/8 inches. Crimp the compression lug following the instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. The distance from the end of the compression lug to the cable adapter after crimping should be between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If dimensions are incorrect, redo the assembly.
- Install the Elbow Connector
Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; if not, reposition the cable adapter. Remove the tape marker.
- Connect Mating Products
WARNING: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud, supplied with the elbow, into the mating part if it is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring surfaces remain clean. Push the elbow onto the mating part, aligning the hole in the compression lug with the stud on the mating part.
- Complete the Connection and Torque
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the specific instructions supplied with that mating part. CAUTION: When constructing 600-amp L-Kits, ensure each component is tightened to the specified torque per instructions provided.
- Install Insulating Plug (if applicable)
If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap on the elbow and push down hard until it snaps into place.
- Ground the Cable Shield
Insert one end of a piece of wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist to make a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The shield of the cable must be grounded. Ground according to the instructions supplied with the grounding device. If no grounding device is used, the shield must be grounded through an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.
- Perform Voltage Test
The ELASTIMOLD deadbreak elbow connector is equipped with an integral capacitance test point. Remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the specific meter used. Test with a suitable sensing device, made for use with separable connectors manufactured with capacitive test points, to determine if the cable is energized. Contamination, moisture, dirt, or incorrect equipment can provide a false 'no voltage' indication. To prevent serious or fatal injury, treat the elbow as energized until the 'no voltage' test point indication is confirmed by other means. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.