ABB Installation Products K656LR-G0270-S 15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation…
UPC: 075114259002
Contact for Pricing
Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.
Overview
- Voltage Rating: 15/25 kV
- Current Rating: 600 A
- Cable Insulation Diameter: 0.760" - 0.950"
- Connection Type: Dead Break Elbow with Test Point
- Material: Aluminum Compression Lug
Specifications
Amperage Rating | 600 A |
Application | 15/25kV, 600 Amp Deadbreak Elbow Connection |
Color | Black |
Conductor Range | 4/0 STR/COMPR AWG , 250 kcmil |
Environmental Conditions | Fully Submersible |
Insulation | True |
Length | 13 in |
Length | 330.2 mm |
Material | Housing - EPDM-Rubber |
Special Features | Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point. Cold-Shrinkable Jacket Seal Included |
Standard | ANSI/IEEE Standard 386 |
Temperature Rating, Maximum | 149 F |
Temperature Rating, Maximum | 65 C |
Temperature Rating, Minimum | -40 F |
Temperature Rating, Minimum | -40 C |
Type | Deadbreak Elbow Connector with Test Point |
Voltage Rating | 25 kV |
Width | 10.36 in |
Width | 263.144 mm |
Package Dimensions (L x W x H) | 0.01 IN x 0.01 IN x 0.01 IN |
Package Dimensions (L x W x H) | 0.0254 cm x 0.0254 cm x 0.0254 cm |
Package Weight (Imperial) | 1.0000 L |
Package Weight (Metric) | 0.4540 kg |

K656CETP-J0270
25kv, 600 Amp Series, Deadbreak Combo-T. Connector Elbow with Intergral 200 Amp Loadbreak Tap Plug with Test Point. Cable Insulation Diameter 0.980 to 1.180 inches (24.9-30.0mm). Aluminum Conductor Material, Conductor Code 270 - 4/0 Stranded/Compressed or 250 Solid/Compact. No Sealing Kit.
K656LR-H0290-S
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold-Shrinkable Jacket Seal Included.
K656LR-M0410
15/25kv, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm). Universal Aluminum Compression Lug. 410 Wire Size - 1000 kcmil Stranded/Compressed. No Sealing kit.
K656LR-G-0270-SG3
15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 or Solid 250 or mm2 125. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K655LR-N0420
15-25kv Dead Break Elbow, No-sealing. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compact/Solid 1250.
K656LR-H-0290-SG3
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold Shrinkable Seal with Copper Braid and Constant Force Spring Included.
K656LR-N0320
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compact/Solid 500. No Sealing Kit.
K656LR-N2410
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Copper Compression Lug. Cable Insulation Diameter 1.515 inch to 1.780 inch. Conductor Size Compressed/Stranded 1000.Frequently Asked Questions
What is the maximum operating voltage for the K656LR elbow connector?
For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground and 14.4kV phase-to-phase. For the 28kV voltage class, it is 16.2kV phase-to-ground and 28kV phase-to-phase.
What conductor sizes can the K656LR connect?
The K656LR can be used with conductor sizes ranging from #2 AWG to 1250 kcmil for both aluminum and copper conductors.
What is the continuous current rating of the K656LR?
The K656LR elbow connector has a continuous current rating of 600 Amps.
Is a grounding device recommended for metallic tape shield or drain wire cable?
Yes, when used on metallic tape shield or drain wire cable, an ECS cable seal grounding device for safety is highly recommended.
What is the impulse withstand rating for the 28kV voltage class?
The impulse withstand rating for the 28kV voltage class is 140kV BIL for a 1.2 x 50 microsecond wave.
What is the AC one-minute withstand voltage for the 15kV class?
The AC one-minute withstand voltage for the 15kV voltage class is 34kV.
What is the AC corona extinction voltage for the 28kV class?
The AC corona extinction voltage for the 28kV voltage class is 21.5kV at 3pC sensitivity.
What is the momentary short circuit rating?
The K656LR has a momentary short circuit rating of 25kA symmetrical for 10 cycles.
What insulation diameters does the K656LR accommodate?
The K656LR accommodates insulation diameters ranging from 0.640 inches to 1.935 inches.
What is the maximum phase-to-phase operating voltage for the 15kV class?
The maximum phase-to-phase operating voltage for the 15kV voltage class is 14.4kV.
How to Install Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors
This guide provides step-by-step instructions for the safe and proper installation of Elastimold 655/675LR and K655/K675LR Deadbreak Elbow Connectors. These connectors provide fully shielded, submersible deadfront cable connections for high voltage apparatus and enable splicing/tapping of 600A or 900A systems on 15kV and 25kV class systems. Ensure all apparatus are de-energized before starting.
Estimated time: 2h
Tools needed:
Wire strippers, Wire brush (for aluminum conductors), Crimping tool, Torque wrench, Hotstick, Suitable capacitive voltage sensing device, Suitable grounding connector
Supplies needed:
655/675LR or K655/K675LR Elbow Connector kit (includes Elbow, Cable Adapter, Compression Lug, Insulating Plug, Lubricant, Stud Prepack), No. 14 AWG Copper wire (or equivalent) for grounding, Silicone lubricant, Tape marker, Grounding device (or alternative grounding method), Waterproofing material (for cable jacket)
- Prepare for Installation and Safety Check
DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products in the work area. Inspect all package contents and components for completeness, damage, proper rating, and compatibility with mating parts. Ensure all required tools are at hand and maintain cleanliness throughout the procedure.
- Position Cable and Make Initial Cut
Assemble the cable in its final position, ensuring enough slack for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.
- Clean Cable Outer Surface
Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.
- Prepare Cable for Connector
Remove the outer jacket (if applicable) and prepare the cable by removing the cable insulation to 9-3/4 inches (248mm), the semi-con shield to 10-3/4 inches (273mm), and marking the tape at 12-3/4 inches (324mm) from the cable end. Refer to specific instructions for 20MA/21MA grounding devices, 600ECS Jacket Cable Seals, or UNISHIELD/LEAD SHEATH cables requiring a 10TL adapter.
- Bevel Insulation and Install Cable Adapter
Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, working towards the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.
- Trim Insulation and Verify Conductor Length
Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Do not cut or nick the cable adapter or the conductor. The exposed conductor length must be between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If not, redo the assembly.
- Install and Crimp Compression Lug
For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it. Measure the 'Check Dimension' before crimping (must be less than 6-3/8 inches). Crimp the compression lug according to its supplied instructions. Wipe off all excess inhibitor from the lug and cable adapter. After crimping, the distance from the lug end to the cable adapter must be between 6-3/8 inches and 7-1/8 inches (162mm-181mm). If not, redo the assembly.
- Install Elbow onto Cable Adapter
Lubricate the cable adapter and the inside of the elbow's cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker; reposition if necessary. Remove the tape marker.
- Prepare and Connect Mating Products
DANGER: Do not connect or disconnect mating products while energized. Do not energize while disconnected. Remove protective caps from the elbow and the mating part. Hand tighten the threaded stud (supplied with the elbow) into the mating part if it's not already equipped. Clean and lubricate both the elbow and the mating part with the supplied lubricant, keeping surfaces clean.
- Connect Elbow to Mating Part
Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.
- Connect Second Mating Part or Insulating Plug
Clean and lubricate the mating part for the opposite end of the elbow. Insert this mating part into the elbow, engage the threads, and hand tighten. Torque the mating part according to its supplied instructions. If an insulating plug is used, clean and lubricate the inner surface of the voltage detection cap and push it onto the elbow until it snaps into place.
- Ground Cable Shield and Waterproof Jacket
Insert one end of a No. 14 AWG Copper wire (or equivalent) through the grounding eye and twist to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow instructions for the grounding device or use an alternate method. It is also recommended to waterproof the cable jacket at this point to prevent moisture ingress.
- Perform Voltage Test
Remove the test point cap with a hotstick, peeling it off at an angle. WARNING: The voltage test point is a capacitance device, not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device designed for capacitive test points to determine if the cable is energized. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means to prevent serious injury. After testing, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.
Frequently Asked Questions about ABB - Installation Products
How are Thomas and Betts products typically installed?
Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.
What accessories are available for Thomas and Betts products?
Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.
What environmental ratings do Thomas and Betts products have?
Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.
What communication protocols do Thomas and Betts products support?
Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.
What are the key features of Thomas and Betts products?
Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.
What are the main product lines offered by Thomas and Betts?
Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.
What technical support does Thomas and Betts offer?
Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.
What industries and applications are Thomas and Betts products used for?
Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.
What certifications and standards do Thomas and Betts products comply with?
Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.
What are the main product lines offered by Ocal?
Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.