ABB - Installation Products K656LR-G0300 - 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.760 inch to 0.950 inch. Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185.

ABB Installation Products K656LR-G0300 15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud…

UPC: 075114252065


Documents & Media
Installation InstructionsSpecification SheetManufacturer Product Website

Contact for Pricing

Call +1 (262) 252-1600 (toll-free 877-268-3700) or email [email protected] for pricing and availability.

Overview

ABB K656LR-G0300 is a 15/25kV 600 Amp Series Deadbreak Elbow with an integrated test point, designed for reliable medium-voltage cable connections in industrial and utility applications. This deadbreak elbow features a fully insulated plug, cap, stud, lug, and cable adapter, ensuring safe and secure terminations in underground or pad-mounted switchgear. The aluminum compression lug supports conductor sizes from 350mm² compressed/stranded to 400mm² compact/solid, with cable insulation diameters ranging from 0.760 inch to 0.950 inch. The deadbreak design allows for load-break operations without de-energizing the system, improving operational flexibility and safety. Commonly used in utility substations, renewable energy installations, and industrial power distribution systems, this elbow meets the demands of high-current, medium-voltage environments. The compression lug ensures low-resistance connections, reducing heat buildup and extending service life. Compatible with standard 600A bushings, it integrates seamlessly with existing ABB and third-party equipment. The test point enables safe voltage verification without cable disconnection, streamlining maintenance and troubleshooting. This product is part of ABB’s Installation Products catalog, a trusted brand in electrical infrastructure solutions.
  • 15/25kV rated voltage for medium-voltage applications
  • 600 Amp continuous current rating
  • Integrated test point for safe voltage verification
  • Supports cable insulation diameters from 0.760" to 0.950"
  • Aluminum compression lug for 350-400mm² conductors

Specifications

Amperage Rating
600 A
Application
15/25kV, 600 Amp Deadbreak Elbow Connection
Color
Black
Conductor Range
350 kcmil , 400 kcmil
Connection Type
Deadbreak Elbow with Test Point
Current Rating
600 A
Environmental Conditions
Fully Submersible
Insulation
True
Length
13 in
Length
330.2 mm
Material
Aluminum
Material
Housing - EPDM-Rubber
Series
K656LR
Size
Cable Insulation Diameter 0.760 inch to 0.950 inch, Conductor Size Compressed/Stranded 350 or Compact/Solid 400 or mm2 Compact 185
Special Features
Fully Shielded, Fully Submersible Molded Rubber Housing. 100 percent Peroxide-Cured Construction includes Insulation and Conductive EPDM Materials. Can be Easily Connected or Disconnected using Standard Hand Tools and Equipment in a De-Energized State. Non-Corrosive, Capacitive Test Point
Standard
ANSI/IEEE Standard 386
Temperature Rating, Maximum
149 F
Temperature Rating, Maximum
65 C
Temperature Rating, Minimum
-40 F
Temperature Rating, Minimum
-40 C
Type
Deadbreak Elbow Connector with Test Point
Voltage Rating
25 kV
Voltage Rating
15/25 kV
Width
10.36 in
Width
263.144 mm
Package Dimensions (L x W x H)
0.01 IN x 0.01 IN x 0.01 IN
Package Dimensions (L x W x H)
0.0254 cm x 0.0254 cm x 0.0254 cm
Package Weight (Imperial)
1.0000 L
Package Weight (Metric)
0.4540 kg
35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.

756LR-M0300-S

35kV 600 Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter). Aluminum Compression Lug. Cable Insulation Diameter 1.370 inch to 1.630 inch. Conductor Size AWG or kcmil, Compressed Stranded 350 /Compacted Solid 400 /mmSquared Compact 185. Cold-Shrinkable Jacket Seal Included.
Single cable clamp 150-300mm2 for power terminal type 5

45000034

Single cable clamp 150-300mm2 for power terminal type 5
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. No Sealing Kit

K656LR-F0240

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compressed/Stranded 1/0 or Compact/Solid 2/0. No Sealing Kit
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compact/Solid #2. No Sealing Kit.

K656LR-F0210

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.640 inch to 0.820 inch. Conductor Size Compact/Solid #2. No Sealing Kit.
15-25kv 600 Amp Elbow With Sealing Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 1000.

K655LR-N0410-SG3

15-25kv 600 Amp Elbow With Sealing Kit. Cable Insulation Diameter 1.515 inch to 1.780 inch. Aluminum Compression Lug. Conductor Size kcmil Compressed/Stranded 1000.
15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 or Solid 250 or mm2 125. With Cold-Shrinkable Jacket Seal.

K656LR-G0270-S

15/25 KV, Elbow Connector with Test Point, 600 Amp, Dead Break, Cable Insulation Diameter 0.760 inch to 0.950 inch. Aluminum Compression Lug. Conductor Size AWG Compressed/Stranded 4/0 or Solid 250 or mm2 125. With Cold-Shrinkable Jacket Seal.
15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold-Shrinkable Jacket Seal Included.

K656LR-H0290-S

15/25kV 600 Amp Series Deadbreak Elbow with Test Point (with Insulated Plug, Cap, Stud, Lug and Cable Adapter), Aluminum Compression Lug. Cable Insulation Diameter 0.850 inch to 1.050 inch. Conductor Size Compressed/Stranded 300 or Compact/Solid 350 or mm2 Compact 150. Cold-Shrinkable Jacket Seal Included.
15/25kv, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm). Universal Aluminum Compression Lug. 410 Wire Size - 1000 kcmil Stranded/Compressed. No Sealing kit.

K656LR-M0410

15/25kv, 600 Amp, Deadbreak Elbow with Test Point. Cable Insulation Diameter 1.370-1.630 inch (34.798-41.402mm). Universal Aluminum Compression Lug. 410 Wire Size - 1000 kcmil Stranded/Compressed. No Sealing kit.

Frequently Asked Questions

What is the maximum operating voltage for the K656LR elbow connector?

For the 15kV voltage class, the maximum operating voltage is 8.3kV phase-to-ground. For the 28kV voltage class, it is 16.2kV phase-to-ground.

What conductor sizes can the K656LR handle?

The K656LR can be used with conductor sizes from #2 AWG to 1250 kcmil for both aluminum and copper conductors.

What is the insulation diameter range for the K656LR?

The K656LR is designed for insulation diameters ranging from 0.640 inches to 1.935 inches.

What standards does the K656LR meet?

The K656LR meets ANSI/IEEE Standard 386, Latest Revision.

What is the continuous current rating of the K656LR?

The K656LR has a continuous current rating of 600 Amps.

What is the momentary current rating for the K656LR?

The K656LR has a momentary current rating of 25kA Sym for 10 Cycles.

What is the impulse withstand rating for the K656LR?

For the 15kV class, it's 95kV BIL. For the 28kV class, it's 140kV BIL.

What is the AC one-minute withstand voltage for the K656LR?

For the 15kV class, it is 34kV AC. For the 28kV class, it is 45kV AC.

What is the corona extinction rating for the K656LR?

For the 15kV class, it is 11kV AC at 3pC sensitivity. For the 28kV class, it is 21.5kV AC at 3pC sensitivity.

What is the purpose of the test point on the K656LR?

The test point is a non-corrosive, capacitive test point that allows for testing.

How to Install 655/675LR and K655/K675LR Deadbreak Elbow Connectors

This guide provides detailed instructions for the safe installation of 600-ampere and 900-ampere Deadbreak Elbow Connectors (including K656LR-G0300 variants) on 15kV and 25kV class systems. It covers cable preparation, lug crimping, and connection to high voltage apparatus. Ensure all apparatus are de-energized before beginning any work.

Estimated time: 2h

Tools needed:

Wire strippers, Knife or utility blade, Crimping tool, Wire brush, Measuring tape or ruler, Hotstick, Suitable voltage sensing device

Supplies needed:

Elbow connector, Cable Adapter, Compression Lug, Insulating Plug (if required), Lubricant, Threaded Stud, Tape marker, No. 14 AWG Copper wire (or equivalent), Suitable grounding connector, Waterproofing material

  1. Perform Initial Safety Checks and Cable Positioning

    DANGER: All apparatus must be de-energized during installation or removal of parts. Do not touch or move energized products. First, check the package contents to ensure they are complete and undamaged. Verify all components fit properly with the cable and/or mating products. Assemble the cable in its final position with enough slack to allow for elbow removal. For concentric neutral cable, unwind the concentric neutral wires. Cut the cable 1-3/4 inches (45mm) from the centerline of the mating product.

  2. Clean Cable Outer Surface

    Clean the outer surface of the cable for a distance of 24 inches (610mm) or up to the bent-back concentric neutral wires.

  3. Prepare Cable Jacket and Shield

    Remove the outer jacket (if applicable) and prepare the cable according to its specific type (e.g., non-jacketed, jacketed shield wires, flat metallic tape shield, fabric tape shield, or longitudinally corrugated shield) as shown in the product diagrams. If using a 20MA or 21MA grounding device, 600ECS Jacket Cable Seal, or 10TL cable shield adapter, refer to their specific installation instructions for cable outer jacket removal, shield connection, and grounding.

  4. Bevel, Clean, Lubricate, and Install Cable Adapter

    Bevel the end of the cable insulation at a 45-degree angle, approximately 1/4 inch (6mm) back. Thoroughly clean and then lubricate the cable insulation, always working toward the semi-con shield. Install the cable adapter, small end first, until it is flush with the edge of the tape marker.

  5. Trim Cable Insulation and Verify Conductor Length

    Remove the protruding cable insulation by cutting it even with the end of the cable adapter. Exercise caution not to cut or nick the cable adapter or the conductor. Verify that the length of the exposed conductor is between 4-1/4 inches and 4-9/16 inches (108mm-116mm). If the length is outside this range, redo the assembly.

  6. Prepare and Crimp Compression Lug

    For copper conductors, fully insert the conductor into the compression lug. For aluminum conductors, wire brush the conductor and immediately fully insert it into the compression lug. Measure the 'Check Dimension' before crimping; this dimension must be less than 6-3/8 inches. If not, redo the assembly. Crimp the compression lug following the crimping instructions supplied with the lug. Wipe all excess inhibitor from the compression lug and cable adapter surface after crimping. Verify the distance from the end of the compression lug to the cable adapter after crimping is between 6-3/8 inches to 7-1/8 inches (162mm-181mm). If not, redo the assembly.

  7. Lubricate and Install Elbow

    Lubricate the cable adapter and the inside of the elbow cable entrance. Install the elbow onto the cable adapter until it cannot advance further. Ensure the cable adapter remains flush with the tape marker. If it is not, reposition the cable adapter. Remove the tape marker.

  8. Prepare Mating Products for Connection

    WARNING: DO NOT CONNECT OR DISCONNECT MATING PRODUCTS WHILE ENERGIZED. DO NOT ENERGIZE WHILE DISCONNECTED. Remove any protective caps from the elbow and the mating part. Hand tighten the threaded stud, supplied with the elbow, into the mating part if the mating part is not already equipped with a stud. Clean and lubricate both the elbow and the mating part with the supplied lubricant, ensuring all surfaces remain clean.

  9. Connect Elbow to Mating Part

    Push the elbow onto the mating part, carefully lining up the hole in the compression lug with the stud on the mating part.

  10. Connect Opposite Mating Part (if applicable)

    Clean and lubricate the mating part intended for the opposite end of the elbow. Insert this mating part into the elbow. Engage the threads and hand tighten. Torque the mating part according to the specific instructions supplied with that mating part.

  11. Install Insulating Plug (if used)

    If an insulating plug is used as a mating part, clean and lubricate the inner surface of the voltage detection cap. Place the cap onto the elbow and push down firmly until it snaps into place. Proceed to the voltage test directions.

  12. Ground Cable Shield and Waterproof Jacket

    Insert one end of a wire with ampacity at least equivalent to No. 14 AWG Copper through the grounding eye and twist it to form a small loop, taking care not to damage the eye. Connect this wire to ground using a suitable connector. The cable shield must be grounded; follow the instructions supplied with your grounding device, or use an alternate method if no device is present. It is also recommended to waterproof the cable jacket at this point to prevent moisture from entering the cable.

  13. Torque Components for 600-amp L-Kits

    CAUTION: When constructing 600-amp L-Kits, ensure that each component is tightened to its specified torque according to the instructions provided with the kit.

  14. Perform Voltage Test (Post-Installation)

    To determine if the circuit is energized, remove the test point cap with a hotstick, peeling it off at an angle rather than pulling directly. WARNING: The voltage test point is a capacitance device and is not directly connected to the conductor. Do not use conventional voltage measuring equipment. Use a suitable sensing device specifically designed for separable connectors with capacitive test points, following its manufacturer’s directions. Treat the elbow as energized until the 'no voltage' indication is confirmed by other means, as contamination, moisture, dirt, or incorrect equipment can provide a false 'no voltage' indication. After voltage detection, clean and lubricate the inside surface of the cap with silicone lubricant and replace it on the test point.

Frequently Asked Questions about ABB - Installation Products

How are Thomas and Betts products typically installed?

Thomas and Betts products are installed using a variety of methods tailored to specific applications, including the use of flexible cords and cable fittings, non-metallic cable glands, and armored cable fittings. Proper selection of fittings is crucial to match the cable type and installation environment, ensuring durability and preventing physical damage. Tools such as the Blackburn® Comfort Crimp® and HEX-FLEX® systems enhance installation efficiency and reliability, reducing labor time and ensuring secure connections.

What accessories are available for Thomas and Betts products?

Thomas and Betts offers a comprehensive range of accessories for their products, including various cord and cable fittings, non-metallic cable glands, service entrance cable fittings, and armored cable fittings. Their accessories are designed to enhance installation efficiency and ensure compatibility with different cable types and environmental conditions, providing reliable connections for a wide array of applications.

What environmental ratings do Thomas and Betts products have?

Thomas and Betts products feature robust environmental ratings, including NEMA Type 1, 2, 3, 4, 4X, 12, and 13 certifications, as well as IEC 60529 IP66 protection. These ratings ensure that their products are designed to withstand harsh industrial environments, with capabilities to resist dust, water, and corrosion, and operate effectively in a wide temperature range.

What communication protocols do Thomas and Betts products support?

Thomas and Betts products support a wide range of industrial communication protocols, including Ethernet, DeviceNet, PROFIBUS, Modbus, CANopen, and others. This extensive compatibility ensures seamless integration and reliable communication across various industrial automation systems, catering to diverse application needs.

What are the key features of Thomas and Betts products?

Thomas and Betts products are known for their innovative designs, high performance, and compliance with industry standards such as the National Electrical Code and Underwriters' Laboratories. They offer a comprehensive range of rugged and reliable electrical fittings, including liquidtight and dust-tight connections, which enhance installation efficiency and reduce overall project costs. Their products are engineered for durability in harsh environments, ensuring long-term reliability and lower installed costs.

What are the main product lines offered by Thomas and Betts?

Thomas and Betts offers a comprehensive range of product lines including electrical connectors, cable management systems, grounding and bonding solutions, and industrial automation components. Their products are designed for durability and reliability in demanding industrial environments, ensuring optimal performance and safety across various applications.

What technical support does Thomas and Betts offer?

Thomas and Betts offers comprehensive technical support, including access to field application engineers for onsite training and installation assistance. Their technical support staff is available to address inquiries related to product specifications and installation practices, ensuring optimal performance and safety of electrical systems. Additionally, they provide a variety of training programs to enhance the knowledge and skills of users in the field.

What industries and applications are Thomas and Betts products used for?

Thomas and Betts products are utilized across various industries including electrical construction, industrial automation, telecommunications, and utilities. Their extensive range of cord and cable fittings, electrical boxes, and metal framing systems are designed for applications that require durability and reliability in harsh environments, ensuring optimal performance in both permanent and temporary installations.

What certifications and standards do Thomas and Betts products comply with?

Thomas and Betts products comply with critical international certifications including UL (Underwriters Laboratories), CSA (Canadian Standards Association), and CE (European Community). Our products are designed to meet rigorous industrial standards such as NEMA enclosure ratings and IEC 60529 IP ratings, ensuring safety and reliability across various industrial applications.

What are the main product lines offered by Ocal?

Ocal offers a comprehensive range of corrosion-resistant conduit systems, including PVC-coated conduit and fittings, conduit bodies, hazardous location fittings, and strut accessories. Their products are designed to provide superior corrosion protection, featuring a hot-dipped galvanizing process and UL listed Type 4X PVC-coated conduit bodies, ensuring durability in the most demanding environments.